Страница 5: ...pressor Quantity 1 1 1 Compressor Model Rotary Rotary Rotary Fan Quantity 1 2 2 Fan Power Input W 75 75 X 2 150 X 2 Fan Rotate Speed RPM 850 850 900 Noise dB A 54 58 62 Water Pump Input kW 0 18 0 5 0...

Страница 6: ...5 Evo Flex Manual 2 3 Dimensions Evo Flex 10 Evo Flex 17 Evo Flex 25...

Страница 7: ...t pump is installed on a strong and stable platform A circuit breaker must be installed for the unit Use supply wires suitable for 75 C Caution Single wall heat exchanger not suitable for potable wate...

Страница 8: ...able to support the weight of a heavy unit such as a terrace roof the ground and any other places deemed suitable The location must have good ventilation The location must be free from heat radiation...

Страница 9: ...itial Start up of the Unit INSPECTION BEFORE TRIAL RUNNING Check the indoor unit make sure that the pipe connection is done correctly and the relevant valves are open Check the water loop to ensure th...

Страница 10: ...presents enabled 6 Setup key Click this key to check the unit status time factory parameters temperature curve timer setting and mute setting 7 Fault icon This icon will flash when there is an error o...

Страница 11: ...t temperature to be set a pop up keyboard will appear 3 Pressing 3 will allow the target temperature of cooling mode to be set through the keyboard When the target temperature is being set the followi...

Страница 12: ...Interface Key Name Key Function 1 Status Key Click this key to get into the status interface 2 Clock Key Click this key to set the operational time function 3 Mute Key Click to turn on off silent func...

Страница 13: ...g the fault records it will ask for a code The password will be according to the display date For example if the display date is 12 11 2016 then the password is 12 5 2 9 Colour Display Calibration Kee...

Страница 14: ...erloaded Check whether the system of the compressor is running normally Communication Fault E08 Communication failure between wire controller and mainboard Check the wire connection between remote wir...

Страница 15: ...on Fault DSP F11 DSP and Inverter board communication failure Check the communication connection Communication Fault Inverter Board F12 Communication failure between inverter board and main board Chec...

Страница 16: ...eakage and recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor do not run Power supply fail...

Страница 17: ...ral Valve 12 Drain Valve 5 Three way Valve 13 Non return valve 6 Y type Filter 14 Water Pump 7 Safety Valve 15 Fan Coil 8 Expansion Tank Installation Request 1 The Factory only offers one main unit 1...

Страница 18: ...the handle A can return close when the system is full of water Automatic filled water valve needs periodic cleaning When you must close the tap unscrew the plug D remove the inside filter net Reassem...

Страница 19: ...2 x 6mm2 6mm2 40A 32 40A 2 x 10mm2 10mm2 63A 40 63A 2 x 16mm2 16mm2 80A 63 75A 2 x 25mm2 25mm2 100A 75 101A 2 x 25mm2 25mm2 125A 101 123A 2 x 35mm2 35mm2 160A 123 148A 2 x 50mm2 50mm2 225A 148 186A 2...

Страница 20: ...19 Evo Flex Manual 7 3 Controller Interface Drawing...