EvoHeat CS-i Commercial Inverter Series Heat Pump 

4.8 Electrical Connection 

IMPORTANT: Always use a qualified Electrician to perform any electrical work. A licensed electrician must read the 

information before connecting. 

Ensure the power cable and circuit breaker are of a suitable size for the heater being installed. Also check that there 

is adequate voltage and current available at the heater connection to run the unit. 

Voltage range should be 220-230 volts for single phase, and 380-400 volts for 3 phase units. Voltage ranges outside 

these parameters will cause heater damage and void your warranty. 

1.

 

Ensure power is disconnected during installation or service. 

2.

 

Always comply with the national and local electrical codes and standards. 

3.

 

Ensure electrical cable size is adequate for heater requirements at the installation location. 

4.

 

The heater must be equipped with a circuit breaker and isolation device. 

5.

 

Circuit breaker must be installed between the heater and the water circulation pump if the water pump is 

hard-wired into the heater. Please note recommended circuit breaker sizes make no allowance for a water 

pump hard wired into the heater. 

6.

 

The unit must be well earthed. Remove the front panel to access the electrical connection terminals of the 

heater. The electrical wiring diagram is affixed to the inside of the front panel. 

 

4.9 Initial Start-up 

Note: in order for the unit to heat the pool or spa, the filter pump must be running to circulate water through the heat exchanger. 

After installation is completed, follow the steps below: 

1.

 

Turn on your filter pump. Check for water leaks and verify flow to and from the pool. 

2.

 

Turn on the electrical power supply to the unit, then press the key ON/OFF of wire controller, it should start after 

several seconds. 

3.

 

After running a few minutes make sure the air leaving the top of the unit is cooler (between 5-10 

4.

 

With the unit operating turn the filter pump off. The unit should also turn off automatically. 

5.

 

Allow the unit and pool pump to run 24 hours per day until desired pool water temperature is reached. (Note: 

this may take up to several days depending on the initial water temperature and the size and location of the 

pool). When the water-in temperature reaches the set temperature the unit will shut off. The unit will now 

automatically restart (as long as your pool pump is running) when the pool temperature drops more than 1

 

below the set temperature. 

 

TIME DELAY 

The unit is equipped with a 3-minute built-in solid-state restart delay included to protect control circuit components 

and to eliminate restart cycling and contactor chatter. This time delay will automatically restart the unit 

approximately 3 minutes after each control circuit interruption. Even a brief power interruption will activate the 

solid state 3-minute restart delay and prevent the unit from starting until the 5-minute countdown is completed. 

Power interruptions during the delay period will have no effect on the 3-minute countdown. 

 

 

 

 

 

 

Содержание CS-i Series

Страница 1: ......

Страница 2: ...Start up Shut Down ___________________________________________________________________ 9 5 2 2 Switching Modes Setting the Target Temperature ___________________________________________ 9 5 2 3 Clock...

Страница 3: ...130 Heat output at 27 C air 26 C water kW 65 130 Heat output at 15 C air 26 C water kW 50 100 Cooling output at 55 C air 35 C water kW 15 54 Cooling output at 45 C air 26 C water kW 30 73 C O P AT 27...

Страница 4: ...oHeat CS i Commercial Inverter Series Heat Pump 2 Unit Dimensions Evo CS i 65 unit mm Evo CS i 130 A L B W C H Water inlet outlet CS i 65 1750mm 830mm 1750mm 50 CS i 130 2260mm 1160mm 2127mm 100mm fla...

Страница 5: ...oad protection system After a previous stoppage the unit will not start for at least 3 minutes For unit cleaning or maintenance switch off and disconnect the power of the unit Do not install the unit...

Страница 6: ...on the front panel of the unit The gauge should be showing a pressure of approx 10 20 on the outside red band any less than this figure means there may be a leak in the refrigerant system and you shou...

Страница 7: ...nstalled a maximum of 5m below the water level of the pool spa If further than 5M please discuss with your EvoHeat specialist for the best advice Make sure the heat pump is not located where large amo...

Страница 8: ...in the air condenses on the fins of the evaporator During times of high humidity the condensate may be several litres per hour This may give the impression that the heater is leaking however this is a...

Страница 9: ...he unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger After installation is completed follow the steps below 1 Turn on your filter pump Check fo...

Страница 10: ...perature interface 7 Temperature Curve Click to view the temperature and power curve 8 Water Inlet Temperature Press to enter mode setting and the target temperature interface 9 LOCK Click to lock the...

Страница 11: ...nction 1 Timing Start Button Start Green End Grey Click this button to start or end the timing start setting function 2 Timing On Setting Click to set the start time of the timer 3 Timing End Button O...

Страница 12: ...check the failure record the main interface will display a static The failure record is in reverse order according to the time of occurrence Press the clean key to delete all fault records 5 2 6 Colou...

Страница 13: ...eaners to ensure proper water flow Is the current pool spa water temperature higher than the set temperature on the controller If so the unit will not operate until the pool spa water temperature fall...

Страница 14: ...If the water has chlorine it is a water leak and you need to contact EvoHeat tech support on 1300 859 933 Or Turn the heater off and run the water pump continuously for a period of 2 4 hours If the wa...

Страница 15: ...rcuit Flow Switch Prot E03 No water little water in water system Check the pipe water flow and water pump Waterway Anti freezing Prot E05 Water temp or ambient temp is too low Inlet and outlet temp to...

Страница 16: ...eck the input voltage measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication...

Страница 17: ...101 123A 2 x 35mm2 35mm2 160A 30mA less than 0 1 sec 123 148A 2 x 50mm2 50mm2 225A 30mA less than 0 1 sec 148 186A 2 x 70mm2 70mm2 250A 30mA less than 0 1 sec 186 224A 2 x 95mm2 95mm2 280A 30mA less t...

Страница 18: ...17 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 Wiring Diagrams 7 3 1 CS i 65...

Страница 19: ...18 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 2 CS i 130...

Страница 20: ...rature input 13 AI DI06 Water input temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch...

Страница 21: ...time 8 1 Energy Saving Tips If your pool water is allowed to cool significantly it may take several days to return to the desired swimming temperature For weekend use it is more economical to maintai...

Страница 22: ...y handling freighting or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b prov...

Отзывы: