4. PC Connection
4.1 Things to Know before Connection
Warning
The connected or built-in peripherals with opposite polarities are not allowed.
Warning
The device only operates when connecting with grounded power. No operation is
allowed when the device power is ungrounded or only impedance is grounded.
Warning
Rated voltage of the device in use shall be in accord with power feature of the
product.
Note:
Only the peripheral devices approved for industrial application can be used. When
operating the PC, hot swappable IO modules (USB) can be used. The IO devices
without hot swap function can only be connected when the PC is powered off.
4.2 Product Grounding
Low impedance ground connection is more helpful to release the interference
produced by the external cables, the signal cables or the cables connecting the IO
module to the grounding system
Ground Terminals
The ground terminal (large surface
①
and large area contact) shall be connected
with the cabinet installed with the PC or
the central grounding busbar on the
device. The minimum cross section area
of the cable shall be no less than 2.5mm
2
,
and the grounding resistance shall be no
more than 0.1
Ω
.