background image

PluraSens

®

Humidity & Temperature Transmitter

E2227

User Manual

Содержание PluraSens E2227

Страница 1: ...PluraSens Humidity Temperature Transmitter E2227 User Manual...

Страница 2: ...ription 4 Safety requirements 4 Operating conditions 4 Installation and connection 5 Delivery set 8 Emergency mode 8 Return to default settings 8 Modbus RTU Communication 9 Communication parameters 10...

Страница 3: ...ad resistance RL Us 2 V 22 mA for 4 20 mA RL 250 kOhm for 0 10 V mode RS485 fieldbus interface Up to 256 units on bus 1 8 unit load no galvanic isolation Modbus RTU protocol support Cable connections...

Страница 4: ...r Two freely configurable 4 20 mA 0 10 V analog outputs can be used to connect the transmitter to secondary instruments Each output can be independently assigned either to temperature relative humidit...

Страница 5: ...t near heat sources or air conditioning units near doors and windows in places where air circulation is limited or on poorly insulated and cold external walls Detach the base from the enclosure by pul...

Страница 6: ...en 4 20 mA closed 0 10 V J2 OUT2 type open 4 20 mA closed 0 10 V X6 Reset Modbus network parameters to default X4 terminals OUT1 4 20 mA 0 10 V output OUT2 4 20 mA 0 10 V output 0V 0 V 24 VAC Neutral...

Страница 7: ...interface should not exceed 1200 m Note The outputs are not galvanically isolated from external power supply and share common 0V Allowed load resistance limits are stated in the Specifications table...

Страница 8: ...s to signal if the connection with the sensor is lost The signal may be set to 3 8 mA or 21 5 mA See the table of Modbus registers for more information Return to default settings To reset the device s...

Страница 9: ...rity bit 1 2 3 4 default 1 17 RW write 42330 to restart 168 RW integrating time constant 0 32000 s 201 RW OUT1 parameter 0 none 1 T 2 RH 202 RW OUT2 parameter 0 none 1 T 2 RH 258 R temperature C 100 s...

Страница 10: ...ing registers Registers Reg are shown in hexadecimal 0 based format Modbus holding register numbers MHR are shown in decimal 1 based format and may be addressed either from 00001 or 40001 base Reg hex...

Страница 11: ...1000 32000 32000 32 000 32 000 0 0x00A7 4 0168 RW Change rate limit for humidity data RH 100 s 1 32000 0 01 320 00 RH s 0 no limit 0 0x00A8 4 0169 RW Integrating filter time constant for all channels...

Страница 12: ...this bit will be ignored bit 6 0 1 output 1 current voltage output read only bit 7 0 1 output 2 current voltage output read only 0x0102 4 0259 R Measured temperature C 100 signed integer 4000 12500 40...

Страница 13: ...e used to assign a new ID to the instrument with an unknown ID When addressing by ID 0 the device shall be the only Modbus instrument in the network The device will not respond to the Master command w...

Страница 14: ...nufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manufa...

Отзывы: