Connections

1. Unscrew four lid screws and detach the lid from the device;

2. Attach the device to the wall using provided screws through the side mounting holes or
key slots (This step may be done before step 1, consider your convenience).

3. Use two M16 cable glands to let in the cables of the power supply and of the external
devices.

Connect the power terminals N and L to the 24 V power source if you are using detector
version -24 or to 230 V AC mains if you are using detector version -230 (see diagram
below).

The terminals on the E2630 series devices are suitable for a wide range of wires with
cross-section 0,2...1,5 mm

2

. We recommend to strip the wire end by 5...6 mm and use the

wire end sleeves. To connect the wire, loosen the screw, insert the wire end into the
terminal hole and tighten the screw. The outer diameter of the cable must not exceed 8
mm.

To use relay outputs, connect the chosen actuators to the relay terminals RE1 and/or RE2.

NOTE! Actuator short-circuits shall be avoided. To protect the instrument relays, use
external fuses or safety switches.

3. Place the lid back and fix it with the screws. Make certain that the cable glands are
properly tightened to ensure the conformity to IP65 protection class.

4. Turn on the power. It may take up to five minutes after switching on for the sensor to
stabilize.

For stable operating, it is recommended to keep the detector powered constantly, except
for periods of maintenance, calibration, replacement, etc.

13

Содержание E2630-VOC

Страница 1: ...Solvent Vapor Detector E2630 VOC User Manual...

Страница 2: ...pecifications 9 Product description 10 Safety requirements 10 Operating conditions 10 Installation guidelines 11 Mounting dimensions 12 Connections 13 Operation 14 Sensor probe handling 15 Maintenance...

Страница 3: ...ensity to air 2 0 Conversion 1 ppm 2 38 mg m3 Boiling point 56 11 C Low explosive limit LEL vol in air 2 5 Upper explosive limit UEL vol in air 12 8 Odor Characteristic pungent smell Hazards Highly fl...

Страница 4: ...Conversion 1 ppm 3 19 mg m3 Boiling point 80 C Low explosive limit LEL vol in air 1 2 Upper explosive limit UEL vol in air 7 8 Odor Hyacinth like odor Hazards Highly flammable Irritant Carcinogen May...

Страница 5: ...ow explosive limit LEL vol in air 3 3 3 Upper explosive limit UEL vol in air 19 Odor The characteristic smell of alcohol Hazards Highly flammable Gas air mixtures are explosive Inhalation of vapors le...

Страница 6: ...onversion 1 ppm 3 60 mg m3 Boiling point 77 1 C Low explosive limit LEL vol in air 2 Upper explosive limit UEL vol in air 11 5 Odor Sweet pear smell Hazards Flammable Short term exposure to high level...

Страница 7: ...Upper explosive limit UEL vol in air 6 75 7 1 Odor Characteristic chemical smell Hazards Highly flammable Gas air mixtures are explosive Inhalation possible effects irritation eyes nose lassitude wea...

Страница 8: ...s ortho xylene meta xylene para xylene Molar weight 106 Conversion 1 ppm 4 34 mg m3 Boiling point 144 4 C 139 C 138 35 C Low explosive limit LEL vol in air 0 9 1 1 Upper explosive limit UEL vol in air...

Страница 9: ...interface UART Relay outputs 2 SPDT max 5 A 30 VDC 250 VAC Alarm signaling Buzzer 2 kHz 85 dB red LED LEDs Green red operation fault red gas alarm Enclosure Grey ABS wall mount protection class IP65 D...

Страница 10: ...static electricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if the wrong power supply is connected External circuits connected...

Страница 11: ...affect the coverage area of the device however the coverage area for a detector is usually between 2 5 to 5 meters radius For early leakage detection install the sensor as close as possible to the pot...

Страница 12: ...E2630 VOC Rev 23 03 2021 Mounting dimensions 12...

Страница 13: ...mm2 We recommend to strip the wire end by 5 6 mm and use the wire end sleeves To connect the wire loosen the screw insert the wire end into the terminal hole and tighten the screw The outer diameter...

Страница 14: ...gas concentration exceeds the LOW alarm setpoint the bottom red LED starts flashing at a rate of 1 Hz and the relay RE1 switches over The first alarm stops automatically if the gas concentration drop...

Страница 15: ...lter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sensor Do not remove the filter as i...

Страница 16: ...Manufacturer with standard gas mixtures before delivery Provided that the sensor is used under moderate conditions field recalibration is recommended every 12 months Please contact your dealer for mor...

Страница 17: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Отзывы: