SAFETY REMARKS 

Read and understand the safety remarks and guidelines in the (full) Instruction 

Manual of this UPS before attempting any switching operations. 

REQUIREMENTS FOR PREPARATION OF THE POWER 

SUPPLY AND RECEIVER SYSTEM

 

A) 

Shipping requirements.

 

 

CAUTION!

  Extreme  caution  is  required  during  shipping,  unloading  and 

installation of the device. 

  Transport the UPS units in the upright position as indicated on the packaging. 

  Protect the device against weather (i.e. protect from rain). 

  Prolonged  shipping  or  storage  below  0 

C  and/or  above  25 

C  is  NOT 

recommended due to the battery life and the condensation hazard. 

  The  devices  are  heavy  and  large.  This  require  proper  transport  and  handling 

facilities  (an  adequate  number  of  helpers,  a  forklift  truck  and  properly 

dimensioned handling routes). 

 

CAUTION! 

Contact  the  Technical  Service  if  any  damage  is  found  that 

may affect proper performance of this device. 

B) 

Location

 

 

CAUTION! 

Selection  of  the  installation  site  and  assurance  of  proper 

operating conditions for the device are the user's responsibility. 

  Install the UPS in a separate room (to isolate the constant noise during operation 

and protect the device from unauthorised access). 

  Do  not  expose  the  device  to  extreme  (high  and/or  low)  temperatures.  Extreme 

temperatures may shorten the battery life (the optimum temperature range is +18 

to +25 

ºC). 

  Do  not  install  the  device  in  rooms  with  dusty,  corrosive  and/or  flammable 

atmosphere  or  where  the  atmospheric  humidity  is  high  (the  recommended 

humidity is 90% without condensation). 

  If  the  device  is  installed  on  false/technical  access  floors,  consider  the  structural 

Содержание POWERLINE RT PLUS 10 000

Страница 1: ......

Страница 2: ...020 03 26 16 15 Pomoc Techniczna tel 48 61 6500 400 www ever eu 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY REMARKS 3 REQUIREMENTS FOR PREPARATION OF THE POWER SUPPLY AND RECEIVER SYSTEM 3 INSTALLATION GUIDELINES 5 ELECTRICAL SYSTEM 7 TECHNICAL ACCEPTANCE 9 NOTES 9 ...

Страница 3: ... and large This require proper transport and handling facilities an adequate number of helpers a forklift truck and properly dimensioned handling routes CAUTION Contact the Technical Service if any damage is found that may affect proper performance of this device B Location CAUTION Selection of the installation site and assurance of proper operating conditions for the device are the user s respons...

Страница 4: ...ents of local laws CAUTION Do not connect the PE line to the UPS with copper cable tips The power supply and receiver lines of the UPS shall be isolated It is recommended to specifically mark label the connection outlets to distinguish those of the isolated UPS network from the mains system outlets Connect the UPS to the nearest mains switching board with copper wires in reinforced shields e g coa...

Страница 5: ...measurements shall be carried out on the responsibility of the device buyer INSTALLATION GUIDELINES Consider the device weight when choosing the installation site The UPS shall only be operated in rooms where the dust temperature and humidity levels are within the device specifications Appropriate cooling conditions must be ensured for the UPS to work properly For this reason the ventilation openi...

Страница 6: ...RAMETERS Output system topology 1P3W Rated output voltage 230 V AC Rated current 26 1 A 43 5 A Minimum output wire size 4 mm2 10 mm2 Output line protection Switch disconnect or Qout 32 A 50 A ENVIRONMENTAL PARAMETERS Heat release under nominal operating conditions 1100 BTU h 1800 BTU h Operating temperature 1 0 40 C Storage temperature 0 40 C Humidity 95 Elevation 1000 m MECHANICAL PARAMETERS Dime...

Страница 7: ...POWERLINE RT PLUS 6 10 kVA UPS Installation diagram symbols Fm Fsb Switch fuses Qout Qsb Switch disconnectors PP1 PP2 PP3 Emergency power off EPO push buttons A Connection wires The list of safeguards and wire sizes used in specific locations for specific UPS models is shown in Table 2 Table 2 Safeguards and wire sizes MODEL Fm Fsb Qout Qsb A POWERLINE RT PLUS 6 kVA 32 A gG 32 A gG 32 A 32 A 4 mm2...

Страница 8: ...en designed for operation in TN systems The exact requirements are specified for a local UPS switching room located directly at the device Follow the applicable local requirements when selecting the wire sizes CAUTION Only trained personnel may switch power to the external bypass system Switching operations carried out against this procedure may result in damage to the UPS The external bypass syst...

Страница 9: ...re the output voltage in the mains operating mode Test the UPS switching from mains to batteries without interruption of the load power supply if possible test at the target load of the UPS circuit Measure the output voltage in the battery operating mode If a bypass is installed train the personnel designated by the buyer in the bypass operation Confirm the completed technical acceptance with the ...

Отзывы: