background image

EVCO S.p.A. | EVJ LCD | Instruction sheet ver. 1.0 | Code 104JLCDA103 | Page 1 of 2 | PT 50/16 

EVJ LCD

 

Remote user interfaces

 

 

 

 

 

EN

 

ENGLISH

 

12 VAC/DC power supply not insulated 

alarm buzzer 

models with incorporated Bluetooth Low Energy sensor 

models with incorporated temperature and humidity sensor 

INTRABUS port 

device for indoor rooms

 

Purchasing code 

 

incorporated Bluetooth 

Low Energy sensor 

incorporated temperature 

and humidity sensor 

EVJD900N2VWIX 

no 

no 

EVJD900N2VWIV 

yes 

no 

EVJD920N2VWIX 

no 

yes 

EVJD920N2VWIV 

yes 

yes 

 

MEASUREMENTS AND INSTALLATION

 

Measurements in mm (inches). 

 

 

 

Wall mounting (with bolts and fastening screws) or in 502E or 503E flush mounting box (with 

fastening screws). 

1. 

Unhook the back shell from the front through a screwdriver and the proper seat. 

2.1 

In case of wall mounting: 

 

2.1.1  Lean the back shell against the wall in a position suitable to get the connecting 

cable to pass through the proper opening. 

 

2.1.2  Use  the  slots  of  the  back  shell  as  template  to  drill  4  holes  having  a  diameter 

suitable to the bolt. 

 

 

5.0 mm (3/16 in) diameter bolts are suggested. 

 

2.1.3  Insert the bolts in the holes drilled in the wall. 

 

2.1.4  Fasten the back shell at the wall with 4 screws. 

 

 

Countersunk head screws are suggested. 

2.2 

In  case  of  502E  or  503E  flush  mounting  box,  fasten  the  back  shell  at  the  box  with  4 

screws. 

 

Countersunk head screws are suggested. 

3. 

Make the electrical connection as shown in the section 

ELECTRICAL CONNECTION 

with-

out powering up the device. 

4. 

Fasten the front of the device at the back shell. 

 

INSTALLATION PRECAUTIONS 

Ensure  that  the  working  conditions  are  within  the  limits  stated  in  the 

TECHNICAL 

SPECIFICATIONS 

section

 

Do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 

or shocks 

In compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them.

 

 

ELECTRICAL CONNECTION

 

 

 

N.B. 

Use cables of an adequate section for the current running through them 

Connect to a INTRABUS network by using a twisted pair.

 

 

2.1 

Connectors and parts 

 

 

 

Description. 

 

Connector 1 

No.

 

DESCRIPTION

 

reference INTRABUS port 

signal INTRABUS port 

 

device power supply (12 VAC/DC). If the device is fed by DC power, connect terminal 

minus 

 

device power supply (12 VAC/DC). If the device is fed by DC power, connect terminal 

plus

 

reserved 

reserved

 

 

Connector 2 

USB port. 

 

Bluetooth Low Energy sensor 

Only available in EVJD900N2VWIV and EVJD920N2VWIV. 

 

Temperature and humidity sensor 

Only available in EVJD920N2VWIX and EVJD920N2VWIV. 

 

Connector 2 

No.

 

DESCRIPTION

 

 CAN port

 

signal - CAN port

 

reference (GND)

 

2.2 

Electrical connection 

Example of electrical connection. 

 

 

 

2.3 

Pre-setting for the programming 

To pre-set the device for the programming, place micro-switch 1 in position ON. 

 

 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

If using an electrical or pneumatic screwdriver, adjust the tightening torque 

If  the  device  has  been  moved  from  a  cold  to  a  warm  place,  the  humidity  may  have 

caused condensation to form inside. Wait about an hour before switching on the power 

Make  sure  that  the  supply  voltage,  electrical  frequency  and  power  are  within  the  set 

limits. See the section 

TECHNICAL SPECIFICATIONS

 

Disconnect the power supply before doing any type of maintenance 

Do not use the device as safety device 

For  repairs and  for  further  information,  contact  the  EVCO  sales  network;  possible  re-

turns without back shell will not be accepted.

 

 

USER INTERFACE

 

 

 

 

3.1 

Device configuration 

 

 

N.B. 

Turn off the power after changing the configuration. 

 

Accessing the procedure. 

1. 

 

Touch the DOWN key for 7 s. 

 

The display will show: 

 

Upper line 

Menu 

 

Lower line 

InFo 

 

Accessing the menu. 

2. 

 

Touch the UP or DOWN key to select a menu.

 

 

The display will show: 

 

Upper line 

Menu 

 

Lower line 

menu name. 

3. 

 

Touch the SET key. 

 

The display will show: 

 

Upper line 

the parameter 

 

Lower line 

the parameter value 

 

Setting configuration parameters of menu “PAr”.

 

3. 

 

Touch the SET key. 

 

The display will show: 

 

Upper line 

PSU 

 

Lower line 

0000 

4. 

 

Touch the SET key again. 

 

The display will show: 

 

Upper line 

PUSU 

 

Lower line 

a value flashing 

5. 

 

Touch the UP or DOWN key to set “

-019

”.

 

6. 

 

Touch the SET key. 

7. 

 

Touch the UP or DOWN key to select a parameter.

 

 

The display will show: 

 

Upper line 

the parameter 

 

Lower line 

the parameter value 

8. 

 

Touch the SET key. 

 

The display will show: 

 

Upper line 

the parameter 

 

Lower line 

the parameter value flashing 

9. 

 

Touch the UP or DOWN key to set the value.

 

10. 

 

Touch the SET key. 

 

Returning to the previous displays.

 

11. 

 

Touch the ON/STAND-BY key a few times. 

 

 

CONFIGURATION PARAMETERS 

 

 

N. 

PAR. 

DEF.  “InFo” MENU (READ ONLY) 

MIN... MAX. 

Prn 

project number 

Pru 

project version 

Prr 

project revision 

FUu 

firmware version 

FUr 

firmware revision 

FUS 

firmware subversion 

HUu 

hardware version 

HUr 

hardware revision 

 

N. 

PAR. 

DEF.  “PAr” MENU 

MIN... MAX. 

 

 

 

BKIL 

 

 

 

10 

 

 

 

backlight intensity 

 

 

 

0... 100 

15 

uneditable 

in 

EVJD920N2VWIX 

and 

EVJD920N2VWIV 

10 

 

 

 

 

BKIt 

 

 

 

 

241 

 

 

 

 

backlight timeout 

 

 

 

 

0... 241 s 

241 = always lit 

30 

uneditable 

in 

EVJD920N2VWIX 

and 

EVJD920N2VWIV 

11  EU3C 

OFF 

enable compatibility with Vled 3 

On... OFF 

 

N. 

PAR. 

DEF.  “nEt > IbuS” MENU (READ ONLY) 

MIN... MAX. 

12 

 

nOdE 

 

 

INTRABUS node 

 

1... 127 

if EU3C = On, nOdE = 3 

13 

StAt 

INTRABUS status communication  OK... Err 

14 

 

n_rH 

 

 

number  of  received  INTRABUS 

packages 

0... 999 

 

15 

 

n_tH 

 

 

number  of  transmitted  INTRA-

BUS packages 

0... 999 

 

16 

 

nErr 

 

 

number  of  INTRABUS  receipts  in 

error 

0... 999 

 

17  BAud 

INTRABUS baud rate 

19200 

18 

StPB 

INTRABUS bit stop number 

0... 2 

19 

PrtY 

INTRABUS parity 

0... 2 

 

N. 

 

 

PAR. 

 

 

DEF. 

 

 

“nEt > bLE” MENU (READ ONLY; 

AVAILABLE  IN  EVJD900N2VWIV 

AND EVJD920N2VWIV) 

MIN... MAX. 

 

 

20 

 

n_rH 

 

 

number  of  BLE  packages  re-

ceived 

0... 999 

 

21 

 

n_tH 

 

 

number  of  BLE  transmitted  re-

ceived 

0... 999 

 

22 

 

nErr 

 

 

number  of  intercepted  BLE  er-

rors 

0... 999 

 

23  BAud 

BLE baud rate 

19200 

24 

StPB 

BLE bit stop number 

0... 2 

25 

PrtY 

BLE parity 

0... 2 

 

N. 

PAR. 

DEF.  “diAG” MENU (READ ONLY) 

MIN... MAX. 

26 

MEm 

EEPROM memory status 

OK... Err 

27 

PSU 

power supply voltage status 

OK... Err 

 

N. 

PAR. 

DEF.  “dEb” MENU 

MIN... MAX. 

28 

PSU 

power supply voltage value 

29 

AI1 

reserved 

30 

AI2 

reserved 

31 

AI3 

reserved 

32 

AI4 

reserved 

33 

 

tI2C 

 

 

incorporated  sensor  temperature 

value 

 

34 

 

HI2C 

 

 

incorporated sensor humidity va-

lue 

 

 

N. 

PAR. 

DEF.  “dEb > un” MENU 

MIN... MAX. 

35 

dO1 

reserved 

36 

AI1t 

reserved 

 

N. 

PAR. 

DEF.  “ConF” MENU 

MIN... MAX. 

37 

PSU 

reserved 

 

TECHNICAL SPECIFICATIONS

 

 

Purpose of the control device:

 

Function controller.

 

Construction of the control device:

 

Built-in electronic device.

 

Container:

 

White, self-extinguishing.

 

Category of heat and fire resistance:

 

D.

 

Measurements: 

111.4 x 76.4 x 18.5 mm (4 3/8 x 3 x 3/4 in).

 

Mounting methods for the control device: 

 

 

Wall  mounting  (with  bolts  and  fastening 

screws)  or  in  502E  or  503E  flush  mounting 

box (with fastening screws). 

Degree  of  protection  provided  by  the  cover-

ing:

 

IP30. 

 

Connection method:

 

 

 

 

Fixed  screw  terminal  blocks  for  wires  up  to 

1 mm² 

Female Micro USB connector. 

 

Maximum permitted length for connection cables:

 

Power supply: 10 m (32.8 ft)

 

USB port: 1 m (3.28 ft)

 

INTRABUS port: 10 m (32.8 ft). 

Operating temperature:

 

From 0 to 40 °C (from 32 to 104 °F).

 

Storage temperature:

 

From -20 to 70 °C (from -4 to 158 °F).

 

Operating humidity: 

 

Relative  humidity  without  condensate  from  5 

to 95%.

 

Pollution status of the control device:

 

2. 

Compliance:

 

 

 

 

RoHS 2011/65/EC

 

WEEE 2012/19/EU

 

REACH (EC) Regulation no. 1907/2006

 

EMC 2014/30/UE 

R&TTE 1999/5/CE. 

Power supply: 

 

12 VAC/DC 

 

12  VAC  (±15%),  50/60  Hz  (±3  Hz),  max. 

10 VA not insulated

 

 

 

 

12 VDC (±15%), max. 10 W not insulated.

 

Earthing methods for the control device:

 

None. 

Rated impulse-withstand voltage:

 

4 KV.

 

Over-voltage category:

 

III.

 

Software class and structure:

 

A.

 

Displays: 

Two rows and function icons LCD display.

 

Alarm buzzer:

 

Built-in.

 

Incorporated sensors: 

Bluetooth 

Low 

Energy 

(only 

in 

EVJD900N2VWIV and EVJD920N2VWIV) 

temperature 

and 

humidity 

(only 

in 

EVJD920N2VWIX and EVJD920N2VWIV). 

Working range incorporated temperature and humidity sensor: 

0... 40 °C (32... 104 °F) 

10... 90 % of relative humidity. 

Communications ports:

 

1 INTRABUS port

 

1 USB port.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Отзывы: