EVCO S.p.A. | EVJ Basic Split | Instruction sheet ver. 1.0 | Code 104JBSE103 | Page 1 of 3 | PT 49/18 

EVJ Basic Split 

Split-version controllers for refrigerated units 

 

 

 

 

ENGLISH 

controllers for normal and low temperature units 

power supply 230 VAC 

cabinet probe and evaporator probe (PTC/NTC) 

door switch and multi-purpose input 

compressor relay 16 A res. @ 250 VAC 

sealed relays compliant with the standard EN 60079-15 

alarm buzzer 

TTL  MODBUS  slave  port  for  EVJKEY  programming  key,  EVconnect  app,  EPoCA  remote 

monitoring system or for BMS 

hot or cold mode regulation. 

 

Purchasing code 

Number of relays 

Power supply 

EVJSB24N7 

230 VAC 

 

MEASUREMENTS AND INSTALLATION | Measurements in mm (inches) 

1.1 

User interface 

To be fitted to a plastic or metal panel (with elastic holding flaps). 

 

 

N.B. 

The thickness of a metal panel must be between 0.8 and 1.5 mm (1/32 and 1/16 in), 

while that for a plastic panel must be between 0.8 and 3.4 mm (1/32 and 1/8 in). 

 

 

 

1.2 

Control module 

To be installed on an electrical panel, on spacers (not provided). 

 

 

N.B. 

Any metal parts must be far enough away so as not to compromise safety distances. 

 

 

 

INSTALLATION PRECAUTIONS 

ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 

SPECIFICATIONS section 

do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 

or shocks 

in compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL CONNECTION 

 

 

N.B. 

-  use cables of an adequate section for the current running through them 

-  to reduce any electromagnetic interference, locate the power cables as far away as 

possible from the signal cables. 

 

 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

if using an electrical or pneumatic screwdriver, adjust the tightening torque 

if the device is moved from a cold to a warm place, humidity may cause condensation 

to form inside. Wait for about an hour before switching on the power 

make  sure  that  the  supply  voltage, electrical  frequency  and  power are  within  the  set 

limits. See the section TECHNICAL SPECIFICATIONS 

disconnect the power supply before carrying out any type of maintenance 

do not use the device as a safety device 

for repairs and for further information, contact the EVCO sales network. 

 

FIRST-TIME USE 

1. 

Carry out the installation following the instructions given in the section MEASUREMENTS 

AND INSTALLATION

2. 

Power  up  the  device  as  set  out  in  the  section  ELECTRICAL  CONNECTION:  an  internal 

test will start up. 

 

The test normally takes a few seconds; when it is finished the display will switch off. 

3. 

Configure the device as shown in the section Setting configuration parameters

 

Recommended configuration parameters for first-time use: 

PAR. 

DEF. 

PARAMETER 

MIN... MAX. 

SP 

0.0 

setpoint 

r1... r2 

P0 

type of probe 

0  = PTC 

1  = NTC 

P2 

temperature measurement unit 

0  = °C 

1  = °F 

d1 

 

 

type of defrost 

 

0  = electric 

1  = hot gas 

2  = compressor stopped 

 

 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section  CONFIGURA-

TION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make  the  electrical  connection  as  shown  in  the  section  ELECTRICAL  CONNECTION, 

without powering up the device. 

6. 

To use the device with the Evconnect app, connect the EVIF25TBX module. To use the 

device  with  the  EPoCA  remote  monitoring  system,  connect  the  EVIF25TWX  module. 

When connecting to an RS-485 network, connect the EVIF22TSX interface. To activate 

real-time functions, connect the EVIF23TSX module. 

 

If using EVIF22TSX or EVIF23TSX, set the bLE parameter to 0

7. 

Power up the device. 

 

USER INTERFACE AND MAIN FUNCTIONS 

 

 

 

4.1 

Switching the device on/off 

1. 

 

If POF = 1 (default), touch the ON/STAND-BY key for 4 s. 

If the device is switched on, the display will show the P5 value ("regulation temperature" de-

fault); if the display shows an alarm code, see the section ALARMS. 

 

 

LED 

ON 

OFF 

FLASHING 

 

compressor 

switched 

on 

 

compressor 

switched 

off 

 

-  compressor  protection  in  pro-

gress 

-  setpoint being set 

 

evaporator fan on 

 

evaporator fan off 

 

evaporator fan stop in progress 

 

 

cabinet light on 

 

cabinet light off 

 

cabinet light on by digital input 

 

AUX 1 

auxiliary load 1 on 

 

 

auxiliary load 1 off 

 

 

-  auxiliary load 1 on by digital in-

put 

-  auxiliary load 1 delay active 

AUX 2 

auxiliary load 2 on 

 

 

auxiliary load 2 off 

 

 

-  auxiliary load 2 on by digital in-

put 

-  auxiliary load 2 delay active 

 

defrost  or  pre-drip  ac-

tive 

 

-  defrosting delay in progress 

-  dripping active 

 

energy saving active 

 

 

 

 

time display 

 

 

set date, time and day of the cur-

rent week 

 

temperature display 

 

 

overcooling or overheating active 

 

HACCP 

HACCP  alarm  saved  in 

EVlink 

 

 

 

alarm active 

 

 

 

 

If Loc = 1 (default) and 30s have elapsed without the keys being pressed, the display will show 

the “Loc” label and the keypad will lock automatically. 

 

4.2 

Unlocking the keypad 

Touch a key for 1 s: the display will show the label “UnL”. 

 

4.3 

Setting the setpoint (if r3 = 0, default) 

Check that the keypad is not locked. 

1. 

 

Touch the SET key. 

2. 

 

Touch the UP or DOWN keys within 15 s to set the value within 

the limits r1 and r2 (default "-40... 50”) 

3. 

 

Touch the SET key (or take no action for 15 s). 

 

4.4 

Activating manual defrost (if r5 = 0, default) 

Check that the keypad is not locked and that overcooling is not active. 

1. 

 

Touch the DEFROST key for 4 s. 

If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than 

the d2 threshold. 

 

4.5 

Switching the cabinet light on/off (if u1c... u5c = 5) 

1. 

 

Touch the CABINET LIGHT key. 

 

4.6 

Switching the cabinet light on/off (if u1c... u5c = 10 or 11) 

1. 

 

Touch the CABINET LIGHT key (for 2 s if u1c... u5c = 5). 

If u1c... u5c = 6, the demisting heaters switch on for u6. 

 

4.7 

Silencing the buzzer (if u9 = 1, default) 

Touch a key. 

If u1c... u5c = 11 and u4 = 1, the alarm output is deactivated. 

 

ADDITIONAL FUNCTIONS 

5.1 

Activating/deactivating overcooling and overheating 

Check that the keypad is not locked. 

1. 

 

Touch the UP key for 2 s. 

 

FUNCTION 

CONDITION 

CONSEQUENCE 

overcooling 

 

r5  =  0  and  defrosting  not 

activated 

the  setpoint  becomes  “setpoint  - 

r6”, for the r7 time 

overheating 

 

r5 = 1 

 

the  setpoint  becomes  “setpoint  + 

r6”, for the r7 time 

 

5.2 

Activating/deactivating energy saving in manual mode (if r5= 0) 

Check that the keypad is not locked. 

1. 

 

Touch the DEFROST key. 

the setpoint becomes “s r4” maximum for the HE2 time. 

 

5.3 

Activating the high or low humidity function (if F0 = 5) 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 1 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select the label “rH”. 

3. 

 

Touch the SET key for 2 s until the display shows the right label 

for  the  function  (only  touch  the  key  to  see  the  function  acti-

vated). 

 

LAB. 

MEANING 

 

rhL 

 

low humidity function (evaporator fan with F17 and F18 if the compressor is 

off, on if the compressor is on) 

 

rhH 

high humidity function (evaporator fan on) 

4. 

 

Touch the ON/STAND-BY key (or take no action for 60 s) to exit 

the procedure. 

 

5.4 

Displaying/deleting compressor functioning hours 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 1 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select a label. 

 

LAB. 

MEANING 

 

CH1 

view compressor functioning hours (in hundreds) 

 

CH2 

view compressor 2 functioning hours (in hundreds) (if u1c... u5c = 1) 

 

rCH 

delete compressor and compressor 2 functioning hours 

3. 

 

Touch the SET key. 

4. 

 

Touch the UP or DOWN key to set “149” (to select rCH). 

5. 

 

Touch the SET key. 

6. 

 

Touch the ON/STAND-BY key (or take no action for 60 s) to exit 

the procedure. 

 

5.5 

Viewing the temperature detected by the probes 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 1 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select a label. 

 

LAB. 

MEANING 

 

Pb1 

cabinet temperature (if P4 = 0, 1, 2 or 4) 

 

incoming air temperature (if P4 = 3) 

 

Pb2 

evaporator temperature (if P3 = 1 or 2) 

 

Pb3 

auxiliary temperature (if P4 = 1, 2, 3 or 4) 

 

Pb4 

calculated product temperature (CPT; if P4 = 3) 

3. 

 

Touch the SET key. 