background image

EVCO S.p.A. | EVHP523 & EVHTP523 | Instruction sheet ver. 1.0 | Code 104HTP523A104 | Page 1 of 2 | PT 30/19 

EVHP523 & EVHTP523

 

Humidity and 

temperature transducer

 

 

 

 

 

EN 

ENGLISH 

5... 95 % humidity working range 

-10... 70 °C temperature working range 

one 4-20 mA output (EVHP523), two 4-20 mA outputs (EVHTP523). 

 

Purchasing code 

Kind of transducer 

Output 

EVHP523 

humidity 

1 x 4-20 mA 

EVHTP523 

humidity and temperature 

2 x 4-20 mA 

 

MEASUREMENTS AND INSTALLATION 

Measurements in mm (inches). Wall mounting, fixing clip and screw provided. 

 

 

 

INSTALLATION PRECAUTIONS 

Install the device as shown in the picture 

Ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 

SPECIFICATIONS section 

Do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust,  mechanical vibrations 

or shocks 

Clean the protective cap periodically (unscrew the cap from the main part of the device 

and clean it using low pressure compressed air or distilled water). 

 

 

 

 

 

 

 

 

ELECTRICAL CONNECTION 

 

 

N.B. 

-  the  temperature  transducer  works  provided  that  the  humidity  one  is  correctly 

powered 

-  to reduce any electromagnetic interference locate the power cables as far away as 

possible from the signal cables. 

 
4.1 

Electrical connection EVHP523 

 

 

Transducer calibration: 

0... 100 % of relative humidity; they correspond respectively to 4 and to 20 mA. 

 
4.2 

Electrical connection EVHTP523 

 

 

Humidity transducer calibration: 

0... 100 % of relative humidity; they correspond respectively to 4 and to 20 mA. 

 

Temperature transducer calibration: 

-30... 70 °C; they correspond respectively to 4 and to 20 mA. 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

If  the  device  has  been  moved  from  a  cold  to  a  warm  place,  the  humidity  may  have 

caused  condensation  to  form  inside.  Wait  about  an  hour  before  connecting  it  to  the 

controller 

Disconnect the device from the controller before doing any type of maintenance 

For repairs and for further information, contact the EVCO sales network.

 

 

 

FIRST-TIME USE 

1. 

Install  following  the  instructions  given  in  the  section  MEASUREMENTS  AND 

INSTALLATION

2. 

Connect the device to the controller as shown in the section ELECTRICAL CONNECTION

3. 

Power up the controller. 

 

TECHNICAL SPECIFICATIONS 

 

Container: 

Plastic grey. 

Measurements (main part): 

Ø 20.0 x 185.0 mm (13/16 x 7 1/4 in). 

Mounting methods: 

Wall mounting, fixing clip and screw included. 

Degree  of  protection  provided  by  the 

covering: 

IP65 (main part). 

 

Connection method: 

Terminals. 

Operating temperature:

 

From -10 to 70 °C (from 14 to 158 °F).

 

Temperature sensor accuracy:

 

±1.5 °C.

 

Storage temperature:

 

From -25 to 70 °C (from -13 to 158 °F).

 

Operating humidity: 

 

Relative humidity  without  condensate  from  5 

to 95 %.

 

Humidity sensor accuracy:

 

±3 % between 5 and 80 %, ±5 otherwise.

 

Compliance: 

RoHS 2011/65/CE 

WEEE 2012/19/EU 

REACH (EC) Regulation no. 1907/2006 

EMC 2014/30/UE. 

Power supply: 

8... 24 VDC. 

Reverse polarity protection: 

Incorporated. 

Maximum load: 

 

[(power supply voltage - 8 VDC) / 0,02 A] ± 

50 Ohm 

Outputs: 

1 x 4-20 mA in EVHP523 

2 x 4-20 mA in EVHTP523. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 