EVCO S.p.A. | EVBOX Light JS200 | Instruction sheet ver. 1.0 | Code 104LJS200E103 | Page 1 of 3 | PT 48/17 

EVBOX Light JS200

 

Control solutions for cold rooms with 

remote moto-condensing unit

 

 

 

 

 

EN

 

ENGLISH

 

Degree of protection IP65. 

Power supply 115... 230 VAC. 

Cabinet probe and evaporator probe (PTC/NTC). 

Door switch input. 

Compressor relay 30 A res. @ 250VAC. 

Alarm buzzer. 

TTL  MODBUS  slave  port  for  EVconnect  app,  EPoCA  remote  monitoring  system  or  for 

BMS. 

Direct connection to the load. 

 

MEASUREMENTS AND INSTALLATION | Measurements in mm (inches)

 

1.1 

User interface 

To be fitted on-board, fixing screws not provided. 

 

 

N.B. 

To  ensure  the  degree  of  protection  IP65  of  the  whole  covering,  install  the  device 

using the appropriate holes only. 

 

 

 

1. 

If  the connecting  cables  come  from  above,  drill  a  hole having a  diameter  suitable  the 

cables to pass on the upper part of the  container using the proper drilling lead (5); if 

vice versa the cables come from below, drill the hole on the lower part of the container. 

 

The maximum diameter of the hole must be 14.0 mm (9/16 in). 

2. 

Make sure the gasket (2) is into the proper seat. 

3. 

If the connecting cables come from above, fasten the container against the wall with 2 

screws (1) using the proper holes on the lower part of the container (3); if vice versa 

the cables come from below, fasten the container using the holes on the upper part. 

 

Use cylindrical head screw. 

 

 

 

4. 

Screw the junction for rigid tube (9) to the cover cap (10)

5. 

Connect  the  user  interface  (11)  to  the  control  module  as  shown  in  the  section 

ELECTRICAL CONNECTION getting the cables to pass through the proper hole (5) and 

through the junction for rigid tube (9)

6. 

Fasten the user interface (11) pushing it from the front into the proper seat (6)

7. 

Make sure the gaskets (4) are into the proper seats. 

8. 

Fasten  the  cover  caps  (10) and (12)  on  the upper  part  and  on  the  lower  part  of  the 

container. 

9. 

Fasten the container against the wall with 2 screws (1) using the proper holes (7) on 

the cover cap (10)

10. 

Fasten the coverscrew caps (8) into the proper holes (7) of the cover cap (10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2 

Control module 

To be fitted on a DIN rail, in a control panel. 

 

 

 

INSTALLATION PRECAUTIONS 

Ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 

SPECIFICATIONS  section.

 

Do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 

or shocks. 

Any  metal  parts  close  to  the  control  module  must  be  far  enough  away  so  as  not  to 

compromise the safety distance. 

In compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them.

 

 

ELECTRICAL CONNECTION

 

 

 

N.B. 

Use cables of an adequate section for the current running through them. 

To reduce any electromagnetic interference connect the power cables as far away 

as possible from the signal cables.

 

 

 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

If using an electrical or pneumatic screwdriver, adjust the tightening torque. 

If  the  device  has  been  moved  from  a  cold  to  a  warm  place,  the  humidity  may  have 

caused condensat. to form inside. Wait about an hour before switching on the power. 

Make  sure  that  the  supply  voltage,  electrical  frequency  and  power  are  within  the  set 

limits. See the section TECHNICAL SPECIFICATIONS.

 

Disconnect the power supply before doing any type of maintenance. 

Do not use the device as safety device. 

For repairs and for further information, contact the EVCO sales network.

 

 

FIRST-TIME USE

 

1. 

Install  following  the  instructions  given  in  the  section  MEASUREMENTS  AND 

INSTALLATION

2. 

Connect the user interface to the control module as shown in the section  ELECTRICAL 

CONNECTION without powering up the device. 

3. 

Power up the device and an internal test will be run. 

 

The test normally takes a few seconds, when it is finished the display will switch off. 

4. 

Configure the device as shown in the section Setting configuration parameters

 

Recommended configuration parameters for first-time use. 

PAR.

 

DEF.

 

PARAMETER

 

MIN... MAX.

 

SP 

0.0 

setpoint 

r1... r2 

P0 

probe type 

0  = PTC 

1  = NTC 

P2 

temperature unit of measurement 

0  = °C 

1  = °F 

d1 

 

 

defrost type 

 

0  = electric 

1  = hot gas 

2  = compressor stopped 

 

 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section 

CONFIGURATION PARAMETERS

5. 

Disconnect the device from the mains. 

6. 

Make  the  electrical  connection  as  shown  in  the  section  ELECTRICAL  CONNECTION 

without powering up the device. 

7. 

For  the  connection  in  an  RS-485  network  connect  the  interface  EVIF22TSX  or 

EVIF23TSX, to activate real time functions connect the module EVIF23TSX, to use the 

device with the EPoCA remote monitoring system, connect the EVIF25TWX module, to 

use  the  device  with  the  Android  APP  EVconnect  connect  the  interface  EVIF25TBX 

(EVlink);  see  the  relevant  instruction  sheets. If EVIF22TSX  or EVIF23TSX  is  used, 

set parameter bLE to 0

8. 

Power up the device. 

 

USER INTERFACE AND MAIN FUNCTIONS

 

 

 

 

4.1 

Switching the device on and off 

1. 

 

If POF = 1 (default), touch the ON/STAND-BY key for 2s.

 

If the device is switched on, the display will show the P5 value ("cabinet temperature" default); 

if the display shows an alarm code, see the section ALARMS

LED

 

ON

 

OFF

 

FLASHING

 

 

compressor on 

 

compressor off 

 

compressor protection active 

setpoint being set

 

 

evaporator fan on 

 

evaporator fan off 

 

evaporator fan stop active 

 

 

cabinet light on 

 

cabinet light off 

 

cabinet light on by digital input 

 

AUX 1 

auxiliary function 1 on 

 

 

auxiliary function 1 off 

 

 

auxiliary function 1 on by digital 

input 

-  auxiliary function 1 delay active

 

AUX 2 

auxiliary function 2 on 

 

 

auxiliary function 2 off 

 

 

-  auxiliary function 2 on by digital 

input 

-  auxiliary function 2 delay active

 

 

defrost 

or 

pre-drip 

active

 

 

-  defrost delay active 

-  dripping active

 

 

energy saving active 

-  low 

consumption 

active

 

 

 

 

 

 

view time 

 

 

set  date,  time  and  day  of  the 

current week

 

 

view temperature 

 

 

quick cooling active 

 

HACCP

 

saved HACCP alarm 

 

 

new HACCP alarm saved 

 

 

alarm active 

 

 

 

 

If Loc = 1 (default) and 30s have elapsed without the keys being pressed, the display will show 

the “Loc” label and the keypad will lock automatically. 

 

4.2 

Unlock keypad 

Touch a key for 1s: the display will show the label “UnL”.

 

 

4.3 

Set the setpoint (if r3 = 0, default) 

Check that the keypad isn’t locked. 

1. 

 

Touch the SET key.

 

2. 

 

Touch the UP or DOWN key within 15s to set the value within the 

limits r1 and r2 (default “-40... 50”)

 

3. 

 

Touch the SET key (or do not operate for 15s).

 

 

4.4 

Activate manual defrost  

Check that the keypad isn’t locked and that quick cooling isn’t active. 

1. 

 

Touch the DEFROST key for 2s.

 

If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than 

the d2 threshold. 

 

4.5 

Cabinet light on/off (if u1 or u11 = 0, default) 

1. 

 

Touch the CABINET LIGHT key.

 

 

4.6 

Button-operated load on/off (if u1 or u11 = 2) 

1. 

 

Touch the CABINET LIGHT key (for 2s if u1 or u11 = 0=).

 

If u1 or u11 = 1, the demisting switch on for the u6 duration. 

 

4.7 

Silence buzzer (if u9 = 1, default) 

Touch a key. 

If u1 or u11 = 3 and u4 = 1, the alarm output is deactivated. 

 

ADDITIONAL FUNCTIONS

 

5.1 

Activate/deactivate overcooling 

Check that the keypad isn’t locked and that defrosting isn’t active. 

1. 

 

Touch the UP key for 2s.

 

The setpoint becomes “setpoint - r6”, for the r7 duration. 

 

5.2 

Activate/deactivate energy saving in manual mode 

Check that the keypad isn’t locked. 

1. 

 

Touch the DEFROST key.

 

The setpoint becomes “se r4”, at maximum for HE2 duration. 

 

5.3 

Activate the high or low humidity functions (if F0 = 5) 

Check that the keypad isn’t locked. 

1. 

 

Touch the DOWN key for 1s.

 

2. 

 

Touch the UP or DOWN key within 15s to select the label  “rH”.

 

3. 

 

Touch  the  SET  key  for  2s  until  the  display  shows  the  right  label 

for  the  function  (only  touch  the  key  to  see  the  function 

activated).

 

 

LAB.

 

DESCRIPTION

 

 

rhL 

 

low humidity function (evaporator fan with F17 and F18 if the compressor is 

off, on if the compressor is on)

 

 

rhH

 

high humidity function (evaporator fan on)

 

4. 

 

Touch the ON/STAND-BY key (or do not operate for 60s) to exit 

the procedure.

 

 

 

 

 

 

 