EVCO S.p.A. | EV3C23 & EV3C33 | Instruction sheet ver. 1.0 | Code PRELIMINARY | Page 1 of 3 | PT 44/16
EV3C23 & EV3C33
Controllers for refrigerated cabinets, counters and islands,
with configurable outputs
E
ENGLISH
-
Controllers for low or medium temperature units, static or ventilated, with light.
-
Interval time defrost with configurable evaporator probe
-
Configurable outputs
-
Power supply 230 VAC or 115 VAC (according to the model).
-
Cabinet probe and auxiliary probe (PTC/NTC).
-
Door switch/multi-purpose input.
-
Compressor relay 16A res. @250 VAC or 30A res. @250 VAC (according to the model).
-
Cooling or heating operation.
1
MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
-
The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
-
Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
-
In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
N.B.
-
Use cables of an adequate section for the current running through them.
-
To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
PRECAUTIONS FOR ELECTRICAL CONNECTION
-
If using an electrical or pneumatic screwdriver, adjust the tightening torque.
-
If the device has been moved from a cold to a warm place, the humidity may have
caused condensation to form inside. Wait about an hour before switching on the pow-
er.
-
Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS.
-
Disconnect the power supply before doing any type of maintenance.
-
Do not use the device as safety device.
-
For repairs and for further information, contact the EVCO sales network.
3
FIRST-TIME
1.
Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2.
Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3.
Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use.
PAR.
DEF.
PARAMETER
MIN... MAX.
SP
0.0
setpoint
r1... r2
P0
1
probe type
0 = PTC
1 = NTC
P2
0
temperature unit of measurement
0 = °C
1 = °F
d1
0
defrost type
0 = electric
1 = hot gas
2 = compressor stopped
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
7.
Power up the device.
4
USER INTERFACE AND MAIN FUNCTIONS
4.1
Switching the device on/off
1.
If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED
ON
OFF
FLASHING
compressor on
compressor off
- compressor protection active
- setpoint setting active
defrost or pre-dripping
active
-
- defrost delay active
- dripping active
evaporator fan on
evaporator fan off
evaporator fan stop active
HACCP
saved HACCP alarm
-
new HACCP alarm saved
energy saving active
-
-
request for compres-
sor service
-
- settings active
- access to additional functions
active
°C/°F
view temperature
-
overcooling or overheating active
device off
device on
device on/off active
AUX
Light on
Aux on
Light on due to door open
If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and
the keypad will lock automatically.
4.2
Unlock keypad
Touch a key for 1 s: the display will show the label “UnL”.
4.3
Set the SETPOINT
Check that the keypad is not locked.
1.
Touch the SET key.
2.
Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default “-50... 50”)
3.
Touch the SET key (or do not operate for 15 s).
4.4
Activate manual DEFROST (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1.
Touch the UP key for 2 s.
If P4 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
4.5
Cabinet LIGHT manual on/off switch mode
1.
Touch the light key. Function always unlocked.
-
Light manual command if u0 = 3 or u1= 3.
-
Auxiliary manual command if u0=1 and u1<>3 if the keyboard is unlocked.
4.6
Cabinet LIGHT or AUXILIARY manual on/off switch mode
1.
Touch the light key. Function always unlocked.
2.
Touch FNC key for auxiliary load with keyboard unlocked.
-
Load configuration u0 = 1(aux) and u1=3(light)
5
ADDITIONA FUNCTIONS
5.1
View/delete compressor functioning hours
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
CH
view compressor functioning hours (hundreds)
rCH
delete compressor functioning hours
3.
Touch the SET key.
4.
Touch the UP or DOWN key to set “149” (when label “rCH” is se-
lected).
5.
Touch the SET key.
6.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.2
View the temperature detected by the probes
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
Pb1
cabinet temperature
Pb2
auxiliary temperature
3.
Touch the SET key.
4.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
6
SETTINGS
6.1
Setting configuration parameters
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4.
Touch the SET key (or do not operate for 15 s): the display will
show the label “SP”.
5.
Touch the UP or DOWN key to select a parameter.
6.
Touch the SET key.
7.
Touch the UP or DOWN key within 15 s to set the value.
8.
Touch the SET key (or do not operate for 15 s).
9.
Touch the SET key for 4 s (or do not operate for 60 s) to exit the
procedure.
6.2
Restore the factory settings (default) and store customized settings as default
N.B.
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- the storing of customized settings overwrites the default.
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15 s to set the value.
VAL.
DESCRIPTION
149
value to restore the factory settings (default)
161
value to store customized settings as default
4.
Touch the SET key (or do not operate for 15 s): the display will
show the label “dEF” (when value “149” is set) or the label
“MAP” (when value “161” is set).
5.
Touch the SET key.
6.
Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or do not operate for 15 s): the display will
show for 4 s “- - -“ flashing, then the device will exit the proce-
dure.
8.
Interrupt the power supply to the device.
9.
Touch the SET key 2 s before action 6. to exit the procedure be-
forehand.
7
CONFIGURATION PARAMETERS
N.
PAR.
DEF. SETPOINT
MIN... MAX.
1
SP
0.0
setpoint
r1... r2
N.
PAR.
DEF. ANALOGUE INPUTS
MIN... MAX.
2
CA1
0.0
cabinet probe offset
-25... 25 °C/°F
3
CA2
0.0
auxiliary probe offset
-25... 25 °C/°F
4
P0
1
probe type
0 = PTC
1 = NTC
5
P1
1
enable °C decimal point
0 = no
1 = yes
6
P2
0
temperature unit of measure-
ment
0 = °C
1 = °F
7
P4
1
auxiliary probe function
0 = disabled
1 = evaporator probe (de-
frost + fan)
2 = evaporator probe (fan)
3 = condenser probe
8
P5
0
value displayed
0 = cabinet temperature
1 = setpoint
2 = auxiliary temperature
9
P8
5
display refresh time
0... 250 s
N.
PAR.
DEF. REGULATION
MIN... MAX.
10
r0
2.0
setpoint differential
1... 15 °C/°F
11
r1
-50
minimum setpoint
-99 °C/°F... r2
12
r2
50.0 maximum setpoint
r1... 199 °C/°F
13
r4
0.0
setpoint offset in energy saving
0... 99 °C/°F
14
r5
0
cooling or heating operation
0 = cooling
1 = heating
15
r12
0
position of the r0 differential
0 = asymmetric
1 = symmetric
N.
PAR.
DEF. COMPRESSOR
MIN... MAX.
16
C0
0
compressor on delay after pow-
er-on
0... 240 min
17
C2
3
compressor off minimum time
0... 240 min
18
C3
0
compressor on minimum time
0... 240 s
19
C4
10
compressor off time during cabi-
net probe alarm
0... 240 min
20
C5
10
compressor on time during cabi-
net probe alarm
0... 240 min
21
C6
80.0
threshold for high condensation
warning
0... 199 °C/°F
differential = 2 °C/4 °F
22
C7
90.0
threshold for high condensation
alarm
0... 199 °C/°F
23
C8
1
high condensation alarm delay
0... 15 min
N.
PAR.
DEF. DEFROST (if r5 = 0)
MIN... MAX.
24
d0
8
automatic defrost interval
0... 99 h
0 = only manual
if d8 = 3, maximum interval
25
d1
0
defrost type
0 = electric
1 = hot gas
2 = compressor stopped
26
d2
8.0
threshold for defrost end
-99... 99 °C/°F
27
d3
30
defrost duration
0... 99 min
se P3 = 1, maximum duration
0= no defrost available
28
d4
0
enable defrost at power-on
0 = no
1 = yes
29
d5
0
defrost dealy after power-on
0... 99 min
30
d6
2
value displayed during defrost
0 = cabinet temperature
1 = display locked
2 = dEF label
31
d7
2
dripping time
0... 15 min
32
d8
0
defrost interval counting mode
0 = device on hours
1 = compressor on hours
2 = hours evaporator tem-
perature < d9
3 = adaptive
33
d9
0.0
evaporation threshold for auto-
matic defrost interval counting if
d8=2
-99... 99 °C/°F
34
d11
0
enable defrost timeout alarm dFd 0 = no
1 = yes
35
d15
0
compressor on consecutive time
for hot gas defrost
0... 99 min
36
d18
40
adaptive defrost interval if d8 =
3
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
37
d19
3.0
threshold for adaptive defrost
(relative to optimal evaporation
temperature)
0... 40 °C/°F
optimal evaporation tempera-
ture - d19
38
d20
180
compressor on consecutive time
for defrost
0... 999 min
0 = disabled
39
d22
2,0
if d8 = 3 adaptive
upper relative threshold to stand-
by the defrost interval counting
"evaporator temperatures aver-
age + d22”);
0..19.9C/F