background image

EVCO S.p.A. | EV3B24 | Data sheet ver. 1.0 | Code 1043B24E104 | Page 1 of 6 | PT 12/15

EV3B24 

Basic controller for low temperature bottle coolers, cabinets, refrigerated

cabinets, tables and pizza counters, with energy saving features

GB

ENGLISH

IMPORTANT

Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this
document with the device for future consultation.
Only use the device in the way described in this document; do not use the same as a safety device.

The device must be disposed of in compliance with local standards regarding the collection of electric and electronic
equipment.

1

DIMENSIONS AND INSTALLATION

1.1

Dimensions

Dimensions are expressed in mm (in).
59.0 (2.322) is the depth with fixed screw connection terminal blocks; 81.5 (3.208) is the depth with removable screw
connection terminal blocks.

-

disconnect the device power supply before proceeding
with any type of maintenance

-

position the power cables as far away as possible from
the signal cables

-

for repairs and information regarding the device, contact
the EVCO sales network.

3

USER INTERFACE

3.1

Preliminary notes

Operating statuses:
-

“on” status (the device is powered and is on; utilities
may be on

-

stand-by” status (the device is powered but is switched
off via software; utilities are off

-

the “off” status: the device is not powered; utilities are
off.

Hereafter, if the POF parameter is set to 0, with the word
“switch-on” means the passage from “off” status to “on”
status; the word “switch-off” means the passage from “on”
status to “off” status.
If the POF parameter is set to 1, with the word “switch-on”
means the passage from “stand-by” status to “on” status;
the word “switch-off” means the passage from “on” status
to “stand-by” status.
When the power is switched back on, the device displays the
status that it was in at the time it was disconnected.

3.2

Manual switch on/off of the device

If the POF parameter is set to 0:
1.

Connect/disconnect the device power supply.

If the POF parameter is set to 1:
2.

Make sure that the keyboard is not locked and that no
procedure is in progress.

3.

Touch the 

 key for 4 s: the 

 LED will flash,

after which it will turn off/on.

3.3

The display

If the device is switched on, during normal operation, the
display will show the magnitude established with P5, except
during defrost, when the device will show the magnitude
established with d6 parameter.
If the device is switched off (“stand-by” status), the display
will be switched off; the 

 LED shall be on.

If the device is in "low consumption" mode, the display will
be switched off and the   LED shall be on.

3.4

Temperature display as detected by the
probes

1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Touch the 

 key for 4 s: the display will show the

first label available.

3.

Touch the 

 or 

 key to select a label.

4.

Touch the 

 .

The following table shows the correspondence between the
labels and the temperature displayed.

Label Displayed temperature

Pb1

if the P4 parameter is set to 0, 1 or 2, room
temperature
if the P4 parameter is set to 3, incoming air tempe-
rature

Pb2

evaporator temperature

Pb3

if the P4 parameter is set to 1, condenser tempe-
rature
if the P4 parameter is set to 2, critical temperature
if the P4 parameter is set to 3, outgoing air tempe-
rature

Pb4

CPT temperature

To exit the procedure:
5.

Touch the 

 key or do not operate for 60 s.

6.

Touch the 

 key.

If the evaporator probe èis absent (that is to say, if the P3
parameter is set to 0), the “

Pb2

” label shall not be displayed.

If the fourth inlet function is to be a multifunction inlet (that
is to say, if the P4 parameter is set to 0) the “

Pb3

” label

shall not be displayed.
If the fourth inlet function is not to be an outgoing air prove
(that is to say, if the P4 parameter is not set to 3) the “

Pb4

label shall not be displayed.

3.5

Compressor operation hours

To show the compressor operation hours:
1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Touch the 

 key for 4 s: the display will show the

first label available.

3.

Touch the 

 or 

 key to select “

CH

”.

4.

Touch the 

 key.

To exit the procedure:
5.

Touch the 

 key or do not operate for 60 s.

6.

Touch the 

 key.

To cancel the compressor operation hours:
7.

From step 3. touch the 

 or 

 key to select

rCH

”.

8.

Touch the 

 key.

9.

Touch the 

 or 

 key within 15 s to set

149

”.

10. Touch the 

 key or do not operate for 15 s: the

display will show a flashing “

- - -

” for 4 s, after which

the device will exi

t the procedure.

3.6

“Rapid cooling” function enabling/disabling

1.

Make sure that the keyboard is not locked and that no
procedure is in progress, that the “rapid cooling” function
is not in progress, that there are no defrosting, dripping
or evaporator fan stop operations in progress, that the
r5 parameter is set to 0 and that the r8 parameter is set
to 1.

2.

Touch the 

 key : the 

°C

 LED  or the  

°F

 LED will

falsh/stop flashing; see also r6 e r7 parameters.

3.7

“Rapid heating” function enabling/disabling

1.

Make sure that the keyboard is not locked and that no
procedure is in progress, and that the r5 and r8
parameters are set to 1.

2.

Touch the 

 key : the 

°C

 LED  or the  

°F

 LED will

falsh/stop flashing; see also r6 e r7 parameters.

3.8

“Energy saving” function enabling/disabling
in manual mode

1.

Make sure that the keyboard is not locked and that no
procedure is in progress, that the r5 parameter is set to
0 and  that the r8 parameter is set to 2.

2.

Touch the 

 key : the   LED will turn on/off; see

also r4, F4, F5 e HE2 parameters.

3.9

Defrost manual activation

1.

Make sure that the keyboard is not locked and that no
procedure is in progress, that the “rapid cooling” function
is not in progress.

2.

Touch the

 

 key for 4 s.

If the evaporator probe functions as a defrost probe (that is
to say, if the P3 parameter is set to 1) and when the defrost
starts the evaporator temperature exceeds the value set
with the d2 parameter, the defrost shall not be activated.

3.10

Room light switch-on/off in manual mode

1.

Make sure that no procedure is in progress and that the
u1 parameter is set to 0; see also u2 parameter.

2.

Touch the 

key: the “

AUX

” LED will turn on/off.

3.11

Demister heating elements activation

1.

Make sure that no procedure is in progress and that the
u1 parameter is set to 1.

2.

Touch the 

key for 4 s: the “

AUX

” LED will turn

on; see also u6 parameter.

3.12

Turning on/off the auxiliary output in manual
mode

1.

Make sure that the keyboard is not locked, that no
procedure is in progress and that the u1 parameter is
set to 2; see also u2 parameter.

2.

Touch the 

key: the “

AUX

” LED will turn on/off.

3.13

Keyboard locking/unlocking

To lock the keyboard proceed as follows:
1.

Make sure no procedure is in progress.

2.

Do not operate for 30 s: the display will show the
message “

Loc

” for 1 s and the keybord shall lock

automatically.

To unlock the keyboard:
3.

Touch a key for 1 s: the display will show the message

UnL

” for 1 s.

1.2

Installation

Panel installation with snap-in brackets.

1.3

Installation warnings

-

the thickness of the panel on which the devise is to be
installed must be between 0.8 and 2.0 mm (0.031 and
0.078 in)

-

make sure that the device work conditions (tempera-
ture of use, humidity, etc.) lie within the limits indi-
cated; see chapter 8

-

do not install the device near to any heat sources (heating
elements, hot air ducts etc.), equipment containing
powerful magnets (large diffusers, etc.), areas affected
by direct sunlight, rain, humidity, excessive dust,
mechanical vibrations or shocks

-

in compliance with safety standards, the device must
be installed correctly and in a way to protect against
any contact with electric parts; all parts that ensure
protection must be fixed in a way that they cannot be
removed without the use of tools.

2

ELECTRIC CONNECTION

2.1

Electric connection

2.2

Warnings for the electric connection

-

do not use electric or pneumatic screwdrivers on the
device terminal board

-

if the device has been taken from a cold to hot place,
humidity could condense inside; wait about 1 hour
before powering it

-

check that the power supply voltage, mains frequency
and electric power fall within the set limits; see chapter
8

Содержание EV3B24

Страница 1: ...ed and that no procedure is in progress 2 Touch the key for 4 s the display will show the first label available 3 Touch the or key to select CH 4 Touch the key To exit the procedure 5 Touch the key or do not operate for 60 s 6 Touch the key To cancel the compressor operation hours 7 From step 3 touch the or key to select rCH 8 Touch the key 9 Touch the or key within 15 s to set 149 10 Touch the ke...

Страница 2: ...the operation requested is not available dEF defrost is in progress 6 ALARMS 6 1 Alarms Code Meaning AL Minimum temperature alarm Solutions check the room temperature or CPT tempera ture see A1 parameter Main consequences the alarm output will be switched on AH Maximum temperature alarm Solutions check the room temperature or CPT tempera ture see A4 parameter Main consequences the alarm output wil...

Страница 3: ...ee of voltage contact 5 VDC 2 mA Other inputs 1 input settable by way of a configuration parameter for analog condenser probe critical temperature probe or outflowing air probe or digital multifunction input inputs Displays 3 digit custom display with function icons Digital outputs 1 output SPST electromechanical relay with 16 A res 250 VAC for compressor management 1 output SPST electromechanical...

Страница 4: ...efrost see also d3 d3 0 99 min 30 if P3 0 or 2 defrost duration if P3 1 maximum defrost duration see also d2 0 defrost will not be activated d4 0 1 0 defrost when device is switched on 5 1 YES d5 0 99 min 0 if d4 0 minimum time between switching on of device and activation of defrost 5 if d4 1 delay in activation of defrost after device is switched on 5 d6 0 2 1 magnitude displayed during defrost ...

Страница 5: ...er input deactivation 22 2 EVAPORATOR FAN SWITCH OFF the evaporator fan shall be switched off for the duration of the i3 time max or until 5s after input deactivation 3 ROOM LIGHTING SWITCH ON the room lighting shall be switched on until 10 s after input deactivation 4 COMPRESSOR AND EVAPORATOR FAN SWITCH OFF AND ROOM LIGHTING SWITCH ON the compressor and evaporator fan will be switched off for th...

Страница 6: ... the defrost management will be switched off see also F1 parameter 5 the parameter has effect even after an interruption in the power supply that occurs while the device is switched on 6 the time set by paramenter C2 is counted also when the device is off stand by status 7 the differential of parameter is 2 0 C 4 F 8 if when the device is switched on the condenser temperature is already above that...

Отзывы: