EVCO S.p.A. | EV3411M | Instruction sheet ver. 1.0 | Code 1043411ME103 | Page 1 of 2 | PT 46/17 

EV3411 

Multi-sensor

 

Universal controllers with one regulation output for industrial applications

 

 

 

 

 

EN

 

ENGLISH

 

power supply 230 VAC or 12-24 VAC/DC (according to the model) 

multi-sensor  input  (PTC/NTC/J/K/Pt  100/Pt  1000/Ni  120/0-20  mA/4-20  mA/0-10  V/ 
2-10 V) 

multi-purpose input 

analogue output 0-10V/PWM (alternatively to relay K1) 

K1 relay 16 A res. @ 250 VAC (alternatively to the analog output)

 

alarm buzzer 

TTL MODBUS slave port for programming key, for EVlink Wi-Fi module (EPoCA system), 
for EVlink BLE module (app EVconnect) or for TTL/RS-485 (BMS) serial interface 

on-off/PID control 

hot or cold mode regulation. 

 

MEASUREMENTS AND INSTALLATION

 

Measurements  in  mm  (in);  59.0  (2  5/16)  depth  with  fixed  screw  terminal  blocks,  81,5 

(3 3/16) depth with plug-in screw terminal blocks. 
To be fitted to a panel, snap-in brackets provided. 

 

 

 

INSTALLATION PRECAUTIONS 

the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in); 

ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 
SPECIFICATIONS
 section;

 

do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 
or shocks; 

in compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 
fixed in such a way as to need the aid of a tool to remove them.

 

 

ELECTRICAL CONNECTION

 

 

 

N.B. 

use cables of an adequate section for the current running through them. 

ensure that the thermocouple is properly insulated from contact with metal parts or 

use already insulated thermocouples. 

if necessary, extend the thermocouple cable using a compensating cable. 

-  in the models with power supply 12-24 VAC/DC, the analog output is available on 

condition that the device is powered at 24 VAC/DC. 

to reduce any electromagnetic interference locate the power cables as far away as 
possible from the signal cables.

 

 

 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

if using an electrical or pneumatic screwdriver, adjust the tightening torque; 

if the device has been moved from a cold to a warm place, humidity may have caused 
condensation to form inside. Wait about an hour before switching on the power; 

make  sure  that  the  supply  voltage, electrical  frequency  and  power are  within  the  set 

limits. See the section TECHNICAL SPECIFICATIONS;

 

disconnect the power supply before carrying out any type of maintenance; 

do not use the device as safety device; 

for repairs and for further information, contact the EVCO sales network.

 

 

FIRST-TIME USE

 

1. 

Install  following  the  instructions  given  in  the  section  MEASUREMENTS  AND 

INSTALLATION

2. 

Power  up  the  device  as  set  out  in  the  section  ELECTRICAL  CONNECTION:  an  internal 
test will start up. 

 

The test normally takes a few seconds; when it is finished the display will switch off. 

3. 

Configure the device as shown in the section Setting configuration parameters

 

 
 
 

 
 
 

 

 

Recommended configuration parameters for first-time use. 

PAR.

 

DEF.

 

PARAMETER

 

MIN... MAX.

 

SP 

0.0 

setpoint 

r1... r2 

P0 

 

 

 

 

 

 

 

 

 

 

 

 

type of probe 

set 

the 

parameter 

before 

connecting the probe 

 

 

 

 

0  = PTC 

  1  = 

NTC 

2  = J 

  3  = 

4  = Pt 100 3 wires  5  = 

Pt 100 2 wires 

6  = Pt 1000 3 wires 7  = 

Pt 1000 2 wires 

8  = 4-20 mA    9  = 

0-20 mA 

10 = 2-10 V 

  11= 

0-10 V 

12 = Ni 120 3 wires  13= 

Ni 120 2 wires 

P2 

temperature measurement unit

 

0  = °C 

1  = °F 

r5 

 

 

hot or cold mode regulation regulator 

 

= cold mode 

1  = hot mode

 

uA 

 

 

 

 

 

 

 

 

 

 

 

 

outputs configuration 

 

 

 

 

 

 

= analog  output  not  enabled,  K1 

relay with regulator 

1  = analog  output  proportional  to 

the  regulation  temperature,  K1 

relay not enabled 

2  = analog  outputwith  regulator,  K1 

relay not enabled

 

ub

 

type of analogue output

 

= 0-10 V 

1  = PWM

 

 

 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section 
CONFIGURATION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make  the  electrical  connection  as  shown  in  the  section  ELECTRICAL  CONNECTION 
without powering up the device. 

6. 

When connecting to an RS-485 network, connect the EVIF22TSX interface. To use the 
device with the EPoCA remote monitoring system, connect the EVIF25TWX module. To 
use the device with the Evconnect app, connect the EVIF25TBX module; see the relative 

instruction sheets. If using EVIF22TSX, set the bLe parameter to 0.

 

7. 

Power up the device. 

 

USER INTERFACE AND MAIN FUNCTIONS

 

 

 

 

4.1 

Switching the device on/off 

1. 

 

If POF = 1 (default), touch the ON/STAND-BY key for 4s.

 

If  the  device  is  switched  on,  the  display  will  show  the  P5  value  ("regulation  temperature" 
default); if the display shows an alarm code, see the section ALARMS. 

LED

 

ON

 

OFF

 

FLASHING

 

OUT1

 

regulator active 

 

 

regulator protection active 

setpoint being set

 

 

unused 

 

 

 

OUT2

 

unused 

 

 

 

 

alarm active 

 

 

 

 

analogue output active 

 

 

 

 

device switched off 

 

device switched on 

 

device being switched on/off 

 

°C/°F

 

temperature display 

 

 

 

percentage display 

 

 

 

Bar

 

pressure display 

 

 

 

 

When 30s have elapsed without the keys being pressed, the display will show the "Loc" label 
and the keypad will lock automatically. 

 

4.2 

Unlocking the keypad 

Touch a key for 1s: the display will show the label “UnL”.

 

 

4.3 

Setting the setpoint 

Check that the keypad is not locked. 

1. 

 

Touch the SET key: the display will show the label “SP”.

 

2. 

 

Touch the UP or DOWN key within 15s to set the value within the 
limits r1 and r2 (default "0... 350”).

 

3. 

 

Touch the SET key (or take no action for 15s).

 

 

4.4 

Silencing the buzzer (if A13 = 1) 

Touch a key. 

 

FUNCTION MODES

 

Cold mode regulation (r5 = 0). 

 

 

 

Hot mode regulation (r5 = 1). 

 

 

 

Operation  with  analogue  output  0-10  V  (ub  =  0,  default)  proportional  to  the  regulation 

temperature (ua = 1, default). 

 

 

 

 

 

 

 

Operation  with  analogue  output  PWM  (ub  =  1)  proportional  to  the  regulation  temperature 

(ua = 1, default). 

 

 

 

ADDITIONAL FUNCTIONS

 

6.1 

Displaying/setting the value delivered by the analogue output 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4s.

 

2. 

 

Touch the UP or DOWN key within 15s to select a label.

 

 

LAB.

 

DESCRIPTION

 

 

uA

 

displaying the value delivered by the analogue output

 

 

uM

 

modifying the value delivered by the analogue output

 

3. 

 

Touch the SET key.

 

4. 

 

Touch the UP or DOWN key to set the value (to select uM).

 

5. 

 

Touch the SET key.

 

6. 

 

Touch  the  ON/STAND-BY  key  (or  take no action  for  60s)  to  exit 

the procedure.

 

 

6.2 

Displaying the number of start-ups of the relay 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4s.

 

2. 

 

Touch the UP or DOWN key within 15s to select a label.

 

 

LAB.

 

DESCRIPTION

 

 

nS1

 

display of the number of start-ups of the K1 relay in thousands

 

3. 

 

Touch the SET key.

 

4. 

 

Touch  the  ON/STAND-BY  key  (or  take no action  for  60s)  to  exit 
the procedure.

 

 

6.3 

Displaying the temperature detected by the regulation probe 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4s.

 

2. 

 

Touch the UP or DOWN key within 15s to select a label.

 

 

LAB.

 

DESCRIPTION

 

 

Pb1

 

regulation temperature

 

3. 

 

Touch the SET key.

 

4. 

 

Touch  the  ON/STAND-BY  key  (or  take no action  for  60s)  to  exit 
the procedure.

 

 

SETTINGS

 

7.1 

Setting configuration parameters 

 

 

N.B. 
Changing  parameter  P2  from  °C  to  °F  (and  vice  versa)  causes  the  value  of  the 

parameters whose unit of measurement is °C or °F to be changed automatically.

 

 

1. 

 

Touch the SET key for 4s: the display will show the label “PA”.

 

2. 

 

Touch the SET key.

 

3. 

 

Touch  the  UP  or  DOWN  key  within  15s  to  set  the  PAS  value 
(default "-19").

 

4. 

 

Touch  the  SET  key  (or  take  no  action  for  15s):  the  display  will 
show the label “SP”.

 

5. 

 

Touch the UP or DOWN key to select a parameter.

 

6. 

 

Touch the SET key.

 

7. 

 

Touch the UP or DOWN key within 15s to set the value.

 

8. 

 

Touch the SET key (or take no action for 15s).

 

9. 

 

Touch the SET key for 4s (or take no action for 60s) to exit the 
procedure.

 

 

7.2 

Restoring factory settings (default) and saving customised settings 

 

 

N.B. 

Check  that  the  factory  settings are appropriate;  see  the  section  CONFIGURATION 
PARAMETERS
. 

Saving customised settings overwrites the factory settings.

 

 

1. 

 

Touch the SET key for 4s: the display will show the label “PA”.

 

2. 

 

Touch the SET key.

 

3. 

 

Touch the UP or DOWN key within 15s to set the value.

 

 

VAL.

 

DESCRIPTION

 

 

149 

value for restoring the factory information (default)

 

 

161 

value for saving customised settings

 

4. 

 

Touch  the  SET  key  (or  take  no  action  for  15s):  the  display  will 
show  the  label  “dEF”  (for  setting  the  “149”  value)  or  the  label 
MAP” (for setting the “161” value) 

 

5. 

 

Touch the SET key.

 

6. 

 

Touch the UP or DOWN key within 15s to set "4".

 

7. 

 

Touch  the  SET  key  (or  take  no  action  for  15s):  the  display  will 
show  “-  -  -“  flashing  for  4s,  after  which  the  device  will  exit  the 

procedure.

 

8. 

Disconnect the device from the power supply.

 

9. 

 

Touch  the  SET  key  for  2s  before  action  6  to  exit  the  procedure 
beforehand.

 

 

CONFIGURATION PARAMETERS

 

 

 

N.

 

PAR.

 

DEF.

 

SETPOINT 

MIN... MAX.

 

SP 

0.0 

setpoint 

r1... r2 

 

N. 

PAR. 

DEF.  ANALOGUE INPUTS

 

MIN... MAX.

 

CA1 

0.0 

regulation probe offset

 

-25... 25 °C/°F 

 
 
 

 
 
 

 
 
 

P0 

 
 
 

 
 
 

 
 
 

 
 
 

 
 
 

 
 
 

type of probe 

 
 
 

 
 
 

 
 
 

0  = PTC 

1  = NTC 

2  = J 

3  = K 

4  = Pt 100 3 wires 
5  = Pt 100 2 wires 

6  = Pt 1000 3 wires 
7  = Pt 1000 2 wires 
8  = 4-20 mA  9  = 0-20 mA 

10 = 2-10 V 

11 = 0-10 V 

12 = Ni 120 3 wires   
13 = Ni 120 2 wires 