EVCO S.p.A. | EV3271/EV3281 | Instruction sheet ver. 1.0 | Code 1043271E103 | Page 1 of 2 | PT 05/22 

EV3271/EV3281 

Controllers for refrigerated units, 

with compressor protection against mains voltage fluctuations 

ENGLISH 

Controllers for normal temperature units 

Power supply 115... 230 VAC 

Cabinet probe (PTC/NTC)

Door switch/multi-purpose input 

Compressor  relay  rated  16  res.  A  @  250  VAC  (EV3271)  or  30  res.  A  @  250  VAC 

(EV3281) 

Compressor protection against mains voltage fluctuations 

Alarm buzzer 

TTL  MODBUS  slave  port  for  EVconnect  app,  EPoCA  remote  monitoring  system  or  for

BMS

Cooling or heating operation 

MEASUREMENTS AND INSTALLATION 

Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided. 

INSTALLATION PRECAUTIONS 

The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in) 

Ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 

SPECIFICATIONS section 

Do not install the device close to heat sources, equipment with a strong magnetic field,

in places subject to direct sunlight, rain, damp, excessive dust,  mechanical vibrations 

or shocks 

In compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them 

ELECTRICAL CONNECTION 

N.B. 

-

Use cables of an adequate section for the current running through them 

-

To reduce any electromagnetic interference connect the power cables as far away 

as possible from the signal cables 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

-

If using an electrical or pneumatic screwdriver, adjust the tightening torque 

-

If  the  device  has  been  moved  from  a  cold  to  a  warm  place,  the  humidity  may  have 

caused condensation to form inside. Wait about an hour before switching on the power 

-

Make  sure  that  the  supply  voltage,  electrical  frequency  and  power  are  within  the  set 

limits. See the section TECHNICAL SPECIFICATIONS

 

-

Disconnect the power supply before doing any type of maintenance 

-

Do not use the device as safety device 

-

For repairs and for further information, contact the EVCO sales network 

FIRST-TIME 

1. 

Install  following  the  instructions  given  in  the  section  MEASUREMENTS AND INSTALLA-

TION

2. 

Power up the device as shown in the section ELECTRICAL CONNECTION and an internal 

test will be run. 

The test normally takes a few seconds, when it is finished the display will switch off. 

3. 

Configure the device as shown in the section Setting configuration parameters

Recommended configuration parameters for first-time use. 

PAR. 

DEF. 

PARAMETER 

MIN... MAX.

SP 

0.0 

setpoint 

r1... r2 

P0 

probe type 

0  = PTC 

1  = NTC 

P2 

temperature unit of measurement 

0  = °C 

1  = °F 

d1 

defrost type 

0  = electric 

1  = hot gas 

2  = compressor stopped 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section  CONFIGURA-

TION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-

out powering up the device. 

6. 

For the connection in an RS-485 network, connect the EVIF22TSX or EVIF23TSX inter-

face. To activate real time functions, connect the EVIF23TSX module. To use the device 

with  the  app EVconnect,  connect  the  EVIF25TBX  interface.  To use  the  device  with  the 

EPoCA remote monitoring system, connect the EVIF25TWX module. If the EVIF22TSX 

or EVIF23TSX interface is used, set parameter bLE to 0.

7. 

Power up the device. 

USER INTERFACE AND MAIN FUNCTIONS 

4.1 

Switching the device on/off 

1. 

If POF = 1, touch the ON/STAND-BY key for 4 s. 

If the device is switched on, the display will show the P5 value ("cabinet temperature" default); 

if the display shows an alarm code, see the section ALARMS

LED 

ON 

OFF 

FLASHING 

compressor on 

compressor off 

-  compressor protection active 

-  setpoint setting active 

defrost active 

dripping active 

HACCP 

saved  HACCP  alarm  in 

EVlink 

energy saving active 

request  for  compres-

sor service 

-  settings active 

-  access  to  additional  functions 

active 

-  operation  with  EVconnect  APP 

active 

°C/°F 

view temperature 

overcooling or overheating active 

device off 

device on 

device on/off active 

If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and 

the keypad will lock automatically. 

4.2 

Unlock keypad 

Touch a key for 1 s: the display will show the label “UnL”. 

4.3 

Set the setpoint 

Check that the keypad is not locked. 

1. 

Touch the SET key. 

2. 

Touch  the  UP  or  DOWN  key  within  15  s  to  set  the  value  within 

the limits r1 and r2 (default “-50... 50”) 

3. 

Touch the SET key (or do not operate for 15 s). 

4.4 

Activate manual defrost (if r5 = 0, default) 

Check that the keypad is not locked and that overcooling is not active. 

1. 

Touch the UP key for 2 s. 

If P4 = 1 (default), defrost is activated provided that the evaporator temperature is lower than 

the d2 threshold. 

4.5 

Silence buzzer 

Touch a key. 

ADDITIONAL FUNCTIONS 

5.1 

Activate/deactivate overcooling, overheating and manual energy saving 

Check that the keypad is not locked. 

1. 

Touch the DOWN key. 

FUNCTION 

CONDITION 

CONSEQUENCE 

overcooling 

r5  =  0,  r8  =  1  and  defrost 

not active 

the  setpoint  becomes  “setpoint  - 

r6”, for the r7 duration 

overheating 

r5 and r8 = 1 

the  setpoint  becomes  “setpoint  + 

r6”, for the r7 duration 

energy saving 

r5 = 0 and r8 = 2 

the  setpoint  becomes  “setpoint  + 

r4”, at maximum for HE2 duration 

5.2 

View/delete  compressor  functioning  hours  and  view  compressor  start-up 

number 

Check that the keypad is not locked. 

1. 

Touch the DOWN key for 4 s. 

2. 

Touch the UP or DOWN key within 15 s to select a label. 

LAB. 

DESCRIPTION 

CH 

view compressor functioning hours (hundreds) 

rCH 

delete compressor functioning hours 

nS1 

compressor start-up number (thousands) 

3. 

Touch the SET key. 

4. 

Touch the UP or DOWN key to set “149” (when label “rCH” is se-

lected). 

5. 

Touch the SET key. 

6. 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

5.3 

View the temperature detected by the probes 

Check that the keypad is not locked. 

1. 

Touch the DOWN key for 4 s. 

2. 

Touch the UP or DOWN key within 15 s to select a label. 

LAB. 

DESCRIPTION 

Pb1 

cabinet temperature

 

Pb2 

auxiliary temperature (if P4 = 1 or 2)

 

3. 

Touch the SET key. 

4. 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

5.4 

View the project number and the firmware revision 

Check that the keypad is not locked. 

1. 

Touch the DOWN key for 4 s. 

2. 

Touch the UP or DOWN key within 15 s to select a label. 

LAB. 

DESCRIPTION 

PrJ 

view the project number

 

rEU 

view the firmware revison

 

3. 

Touch the SET key. 

4. 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

5.4 

View the mains voltage 

Assicurarsi che la tastiera non sia bloccata. 

1. 

Touch the DOWN key for 4 s. 

2. 

Touch the UP or DOWN key within 15 s to select “UOL”. 

3. 

Touch the SET key. 

4. 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

SETTINGS 

6.1 

Setting configuration parameters 

1. 

Touch the SET key for 4 s: the display will show the label “PA”. 

2. 

Touch the SET key. 

3. 

Touch the UP or DOWN key within 15 s to set the PAS value (de-

fault “-19”). 

4. 

Touch the SET key (or do not operate for 15 s): the display will 

show the label “SP”. 

5. 

Touch the UP or DOWN key to select a parameter. 

6. 

Touch the SET key. 

7. 

Touch the UP or DOWN key within 15 s to set the value. 

8. 

Touch the SET key (or do not operate for 15 s). 

9. 

Touch the SET key for 4 s (or do not operate for 60 s) to exit the 

procedure. 

6.2 

Set the date, time and day of the week (available if EVIF23TSX, EVIF25TBX or 

EVIF25TWX module is connected) 

N.B. 

-  Do not disconnect the device from the mains within two minutes since the setting 

of the time and day of the week 

-  if the device communicates with the EVconnect app, the date, time and day of the

week will be automatically set by the smartphone or tablet 

Check that the keypad is not locked. 

1. 

Touch the DOWN key for 4 s. 

2. 

Touch the UP or DOWN key within 15 s to select the label “rtc”. 

3. 

Touch the SET key: the display will show the label “yy” followed 

by the last two figures of the year. 

4. 

Touch the UP or DOWN key within 15 s to set the year. 

5. 

Repeat actions 3. and 4. to set the next labels. 

LAB. 

DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL 

month (01… 12) 

day (01… 31) 

time (00… 23) 

minute (00… 59) 

6. 

Touch the SET key: the display will show the label for the day of 

the week. 

7. 

Touch  the  UP  or  DOWN  key  within  15  s  to  set  the  day  of  the 

week.

LAB. 

DESCRIPTION 

Mon 

Monday 

tuE 

Tuesday 

UEd 

Wednesday 

thu 

Thursday 

Fri 

Friday 

Sat 

Saturday 

Sun 

Sunday 

8. 

Touch the SET key: the device will exit the procedure. 

9. 

Touch the ON/STAND-BY key to exit the procedure beforehand. 

6.3 

Restore the factory settings (default) and store customized settings as default 

N.B. 

-  Check  that  the  factory  settings are appropriate;  see  the  section  CONFIGURATION 

PARAMETERS. 

-  the storing of customized settings overwrites the default. 

1. 

Touch the SET key for 4 s: the display will show the label “PA”. 

2. 

Touch the SET key. 

3. 

Touch the UP or DOWN key within 15 s to set the value. 

VAL. 

DESCRIPTION 

149 

value to restore the factory settings (default) 

161 

value to store customized settings as default 

4. 

Touch the SET key (or do not operate for 15 s): the display will 

show  the  label  “dEF”  (when  value  “149”  is  set)  or  the  label 

MAP” (when value “161” is set). 

5. 

Touch the SET key. 

6. 

Touch the UP or DOWN key within 15 s to set “4”. 

7. 

Touch the SET key (or do not operate for 15 s): the display will 

show for 4 s “-  -  -“ flashing, then the device will exit the proce-

dure. 

8. 

Interrupt the power supply to the device. 

9. 

Touch the SET key 2 s before action 6. to exit the procedure be-

forehand. 

CONFIGURATION PARAMETERS 

N. 

PAR. 

DEF.  SETPOINT 

MIN... MAX.

 

SP 

0.0 

setpoint 

r1... r2 

N. 

PAR. 

DEF.  ANALOGUE INPUTS 

MIN... MAX. 

CA1 

0.0 

cabinet probe offset 

-25... 25 °C/°F

CA2 

0.0 

auxiliary probe offset 

-25... 25 °C/°F

P0 

probe type 

0  = PTC 

1  = NTC 

P1 

enable °C decimal point 

0  = no 

1  = yes 

P2 

temperature  unit  of  measure-

ment 

0  = °C 

1  = °F 

P4 

configurable input 

function 

0  = door 

switch/multi-pur-

pose input 

1  = evaporator probe 

2  = condenser probe 

P5 

value displayed 

0  = cabinet temperature 

1  = setpoint 

2  = auxiliary temperature 

P8 

display refresh time 

0... 250 s : 10 

N. 

PAR. 

DEF.  REGULATION 

MIN... MAX. 

10 

r0 

2.0 

setpoint differential 

1... 15 °C/°F 

11 

r1 

-50

minimum setpoint 

-99 °C/°F... r2

12 

r2 

50.0  maximum setpoint 

r1... 199 °C/°F 