EVCO S.p.A. | EV3143 | Instruction sheet ver. 1.0 | Code 1043143E103 | Page 1 of 3 | PT 22/19
EV3143
Controller with two independent regulators for refrigerated milk storage
units and ice cream batch freezers
EN
ENGLISH
-
230 VAC or 115 VAC power supply (according to the model)
-
2 analogue inputs (PTC/NTC)
-
door switch/multi-purpose input
-
main relay 16 A res. @ 250 VAC
-
alarm buzzer
-
TTL MODBUS slave port for BMS
-
hot or cold mode regulation.
1
MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
-
the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
-
ensure that the working conditions are within the limits stated in the TECHNICAL SPEC-
IFICATIONS section
-
do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations or
shocks
-
in compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be fixed
in such a way as to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
N.B.
- use cables of an adequate section for the current running through them
- to reduce any electromagnetic interference, locate the power cables as far away as
possible from the signal cables.
The controller is operated mainly by P10 (default "controller with two independent regulators").
P10
OPERATION
PROBE 1
PROBE 2
LOAD 1
LOAD 2
LOAD 3
0
controller with two inde-
pendent regulators
regulator
1
regulator
2
regulator
1
regulator
2
alarm
1
controller for refrigerated
milk storage units
tank
auxiliary
compres-
sor
auxiliary
beater
2
controller for ice cream
batch freezers
tank
plate
compres-
sor
plate
heaters
beater
PRECAUTIONS FOR ELECTRICAL CONNECTION
-
if using an electrical or pneumatic screwdriver, adjust the tightening torque
-
if the device is moved from a cold to a warm place, humidity may cause condensation
to form inside. Wait for about an hour before switching on the power
-
make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS
-
disconnect the power supply before carrying out any type of maintenance
-
do not use the device as a safety device
-
for repairs and for further information, contact the EVCO sales network.
3
FIRST-TIME USE
1.
Carry out the installation following the instructions given in the section MEASUREMENTS
AND INSTALLATION.
2.
Power up the device as set out in the section ELECTRICAL CONNECTION: an internal test
will start up.
The test normally takes a few seconds; when it is finished the display will switch off.
3.
Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use:
PAR.
DEF.
PARAMETER
MIN... MAX.
SP1
0.0
load 1 setpoint
r1... r2
SP2
0.0
load 2 setpoint
r12... r13
SP3
0.0
beater setpoint
r16... r17
P0
1
type of probe
0 = PTC
1 = NTC
P2
0
temperature measurement unit
0 = °C
1 = °F
P10
0
operating logic
0 = controller with two independent
regulators
1 = controller for refrigerated milk
storage units
2 = controller for ice cream batch
freezers
Then check that the remaining settings are appropriate; see the section CONFIGURATION
PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION, with-
out powering up the device.
6.
When connecting to an RS-485 network, connect the EVIF22TSX interface; see the rele-
vant instruction sheets.
7.
Power up the device again.
4
USER INTERFACE AND MAIN FUNCTIONS
4.1
Switching the device on/off
1.
If POF = 1 (default), touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("probe 1 temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED
ON
OFF
FLASHING
compressor on
compressor off
- compressor protection in pro-
gress
- setpoint being set
plate heaters on
plate heaters off
setpoint being set
OUT1
regulator 1 on
regulator 1 off
- load 1 protection in progress
- setpoint being set
defrost active
-
-
beater on
beater off
setpoint being set
alarm active and si-
lenced
-
alarm active and not silenced
°C/°F
temperature displayed
-
-
OUT2
regulator 2 on
regulator 2 off
- load 2 protection in progress
- setpoint being set
device off
device on
device being switched on/off
When 30 s have elapsed without the keys being pressed, the display will show the “Loc” label
and the keypad will automatically lock.
4.2
Unlocking the keypad
Touch a key for 1 s: the display will show the label “UnL”.
4.3
Quick setting:
- of setpoints (if P9 = 1 or 3)
- beater switch on/off times (if P9 = 2 or 3)
Check that the keypad is not locked.
1.
Touch the SET key: the display will show the label “SP1”.
2.
Touch the UP or DOWN key within 15 s to set the load 1 setpoint
value within the limits r1 and r2 (default “-50... 50”).
3.
Touch the SET key: the display will show the label “SP2”.
4.
Touch the UP or DOWN key within 15 s to set the load 2 setpoint
value within the limits r12 and r13 (default “-50... 50”).
5.
Touch the SET key: the display will show the label “SP3”.
6.
Touch the UP or DOWN key within 15 s to set the beater setpoint
value within the limits r16 and r17 (default “-50... 50”).
7.
Touch the SET key: the display will show the label “t0”.
8.
Touch the UP or DOWN key within 15 s to set the time the beater
is switched off within the limits 0... 240 min.
9.
Touch the SET key: the display will show the label “t1”.
10.
Touch the UP or DOWN key within 15 s to set the time the beater
is switched on within the limits 0... 240 min.
11.
Touch the SET key (or take no action for 15 s).
Settings are temporary: when the device is switched back on (and after a power failure), it resets
the values SP1, SP2, SP3, t0 and t1.
4.4
Starting up/interrupting batch freezing (if P10 = 2)
Check that the keypad is not locked.
1.
Touch the ON/STAND-BY key.
4.5
Manually switching on the beater (if P10 = 1)
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
The beater is switched on for time t1.
4.6
Activating manual defrost (if r5 and/or r19 = 0, default)
Check that the keypad is not locked.
1.
Touch the UP key for 4 s.
4.7
Silencing the buzzer (if Pbu = 2 or 3)
Touch a key.
If u4 = 1, the alarm output is also deactivated.
5
OPERATION
5.1
Controller with two independent regulators (P10 = 0, default)
Cold mode regulation regulator 1 (r5 = 0).
Hot mode regulation regulator 1 (r5 = 1).
Cold mode regulation regulator 2 (r10 = 0).
Hot mode regulation regulator 2 (r10 = 1).
5.2
Controller for refrigerated milk storage units (P10 = 1)
Compressor operation.
Beater operation set to t0 and t1 (r14 = 0).
Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Cold mode regulation beater (r19 = 0)
Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Hot mode regulation (r19 = 1).
5.3
Controller for ice cream batch freezers (P10 = 2)
The batch freezing cycle consists of 4 phases:
-
heating
-
cooking
-
cooling
-
conservation.
5.3.1 Heating
The compressor remains off.
Plate heaters operation.
Beater operation.
End of phase.
At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase, it starts back up again from the beginning.
5.3.2 Cooking
The compressor remains off.
Plate heaters operation.