EVCO S.p.A. | EV3 300 series | Instruction sheet ver. 1.0 | Code 1043300E103 | Page 1 of 

2

 | PT 50/17 

EV3 300 series 

Temperature modules for basic ovens 

 

 

 

 

EN 

ENGLISH 

user interface with push encoder or touch keys (according to the model). 

230 VAC or 12 VAC/DC power supply (according to the model). 

regulation probe (J/K). 

multi-purpose input. 

relay  output,  5  A  res.  @  250  VAC  or  open  collector,  12  VDC,  10  mA  for  SSR  module 

control (according to the model). 

alarm buzzer. 

on-off/PID control. 

hot or cold mode regulation. 

operation with programming key. 

 

 

N.B. 

-  the push encoder is not provided. 

-  for models with a push encoder user interface, it is mandatory. 

-  models with a touch key user interface also operate with push encoder. 

 

Purchasing code 

User interface 

Power supply 

Output 

EV3301J2 

push encoder 

12 VAC/DC 

relay, 5 A res. 

EV3301J7 

push encoder 

230 VAC 

relay, 5 A res. 

EV3301J7VR0 

 

push encoder 

 

230 VAC 

 

open collector, 

12 VDC, 10 mA 

EV3311J2 

touch keys 

12 VAC/DC 

relay, 5 A res. 

EV3311J7 

touch keys 

230 VAC 

relay, 5 A res. 

EV3311J7VR0 

 

touch keys 

 

230 VAC 

 

open collector, 

12 VDC, 10 mA 

 

MEASUREMENTS AND INSTALLATION 

Measurements in mm (in); 39.5 (1 9/16) depth with fixed screw terminal blocks, 52.5 (2 1/16) 

depth with plug-in screw terminal blocks. 

To be fitted to a panel, snap-in brackets provided. 

 

 

 

INSTALLATION PRECAUTIONS 

the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in). 

ensure  that  the  working  conditions  are  within  the  limits  stated  in  the 

TECHNICAL 

SPECIFICATIONS

 section. 

do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 

or shocks. 

in compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them. 

 

ELECTRICAL CONNECTION 

 

 

N.B. 

-  use cables of an adequate section for the current running through them. 

-  ensure that the thermocouple is properly insulated from contact with metal parts or 

use an already insulated thermocouple. 

-  if necessary, extend the thermocouple cable using a compensating cable. 

-  to reduce any electromagnetic interference locate the power cables as far away as 

possible from the signal cables. 

 

 

 

 

 

 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

if using an electrical or pneumatic screwdriver, adjust the tightening torque. 

if the device is moved from a cold to a warm place, humidity may cause condensation 

to form inside. Wait for about an hour before switching on the power. 

make  sure  that  the  supply  voltage,  electrical  frequency  and  power  are  within  the  set 

limits. See the section 

TECHNICAL SPECIFICATIONS

disconnect the power supply before carrying out any type of maintenance. 

do not use the device as a safety device. 

for repairs and for further information, contact the EVCO sales network. 

 

FIRST-TIME USE 

1. 

Carry out the installation following the instructions given in the section 

MEASUREMENTS

 

AND INSTALLATION

2. 

Power  up  the  device  as  set  out  in  the  section 

ELECTRICAL  CONNECTION

:  an  internal 

test will start up. 

 

The test normally takes a few seconds; when it is finished the display will switch off. 

3. 

Configure the device as shown in the section 

Setting configuration parameters

 

Recommended configuration parameters for first-time use: 

PAR. 

DEF. 

PARAMETER 

MIN... MAX. 

SP 

setpoint 

r1... r2 

P0 

type of probe 

2  =  J 

3  =  K 

P2 

temperature measurement unit 

0  =  °C 

1  =  °F 

r5 

 

 

hot or cold mode regulation 

 

0  =  cold mode 

1  =  hot mode 

 

 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section 

CONFIGURA-

TION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make the electrical connection as shown in the section 

ELECTRICAL CONNECTION 

with-

out powering up the device. 

6. 

If necessary, connect the push encoder. 

7. 

Power up the device. 

 

USER INTERFACE AND MAIN FUNCTIONS 

 

 

 

4.1 

Switching the device on/off 

To switch on push encoder models:

 

1. 

 

Press the encoder. 

 

To switch off push encoder models:

 

1. 

 

Press the encoder for 2 s. 

 

To switch on touch key models:

 

1. 

 

Touch the ON/STAND-BY key. 

 

To switch off touch key models:

 

1. 

 

Touch the ON/STAND-BY key for 2 s. 

If  the  device  is  switched  on,  the  display  will  show  the  P5  value  ("regulation  temperature"  de-

fault); if the display shows an alarm code, see the section ALARMS. 

LED 

ON 

OFF 

FLASHING 

OUT1

 

regulator active 

 

 

- regulator protection active 

- setpoint being set 

 

alarm active 

 

 

 

OUT2

 

unused 

 

 

 

SEC

 

unused 

 

 

 

 

device switched off 

 

device switched on 

 

device being switched off 

 

°C/°F

 

temperature display 

 

 

 

unused 

 

 

 

MIN

 

unused 

 

 

 

 

If  Loc  =  1  and  30  s  have  elapsed  without  the  keys  being  pressed,  the  display  will  show  the 

"

Loc

" label and the keypad will lock automatically. 

 

4.2 

Unlocking the keypad 

Touch a key for 1 s: the display will show the label “

UnL

”. 

 

4.3 

Setting the setpoint 

For push encoder models:

 

1. 

 

Rotate the encoder. 

2. 

 

Rotate the encoder within 15 s to set the  value within the limits 

r1 and r2 (default "0... 350”). 

3. 

 

Press the encoder. 

4. 

Take  no  action  for  15  seconds  to  exit  the  procedure  in  advance:  the  device  will  not 

save the entered value. 

 

For touch key models:

 

check that the keypad is not locked. 

1. 

 

Touch the SET key. 

2. 

 

Touch  the  UP  or  DOWN  keys  within  15s  to  set  the  value  within 

the limits r1 and r2 (default "0... 350”). 

3. 

 

Touch the SET key. 

4. 

 

Touch  the  ON/STANDBY  key  (or  take  no  action  for  15 s)  to  exit 

the  procedure  in  advance:  the  device  will  not  save  the  entered 

value. 

 

4.4 Silencing the buzzer 

For push encoder models:

 

rotate or press the encoder. 

 

For touch key models:

 

touch a key. 

 

 

 

 

 

 

 

 

OPERATION WITH ON-OFF CONTROL 

Cold mode regulation (r5 = 0). 

 

 

 

Hot mode regulation (r5 = 1). 

 

 

 

SETTINGS 

6.1 

Setting configuration parameters 

 

 

N.B. 

Changing  parameter  P2  from  °C  to  °F  (and  vice  versa)  causes  the  value  of  the  pa-

rameters whose unit of measurement is ° C or ° F to be changed automatically. 

 

For push encoder models:

 

make sure that the device is switched off. 

1. 

 

Press the encoder for 4 s: the display will show the label “

PA

”. 

2. 

 

Press the encoder. 

3. 

 

Rotate  the  encoder  within  15  s  to  set  the  PAS  value  (default 

-19

”). 

4. 

 

Press  the  encoder  (or  take  no  action  for  15  s):  the  display  will 

show the label “

SP

”. 

5. 

 

Rotate the encoder to select a parameter. 

6. 

 

Press the encoder. 

7. 

 

Rotate the encoder within 15 s to set the value. 

8. 

 

Press the encoder (or take no action for 15 s). 

9. 

 

Press the encoder for 4 s (or take no action for 60 s) to exit the 

procedure. 

 

For touch key models:

 

make sure that the device is switched off. 

1. 

 

Touch the SET key for 4 s: the display will show the label “

PA

”. 

2. 

 

Touch the SET key. 

3. 

 

Touch the UP or DOWN key within 15s to set the PAS value (de-

fault "

-19

"). 

4. 

 

Touch  the  SET  key  (or  take  no  action  for  15s):  the  display  will 

show the label “

SP

”. 

5. 

 

Touch the UP or DOWN key to select a parameter. 

6. 

 

Touch the SET key. 

7. 

 

Touch the UP or DOWN key within 15s to set the value. 

8. 

 

Touch the SET key (or take no action for 15s). 

9. 

 

Touch  the  SET  key  for  4s  (or  take  no action  for  60s)  to  exit  the 

procedure. 

 

6.2 

Restoring factory settings (default) and saving customised settings 

 

 

N.B. 

-  Check  that  the  factory  settings  are  appropriate;  see  the  section 

CONFIGURATION 

PARAMETERS

.

 

-  Saving customised settings overwrites the factory settings. 

 

For push encoder models:

 

make sure that the device is switched off. 

1. 

 

Press the encoder for 4 s: the display will show the label “

PA

”. 

2. 

 

Press the encoder. 

3. 

 

Rotate the encoder within 15 s to set the value. 

 

VAL. 

DESCRIPTION 

 

149 

value for restoring the factory information (default) 

 

161 

value for saving customised settings 

4. 

 

Press  the  encoder  (or  take  no  action  for  15  s):  the  display  will 

show  the  label  “

dEF

”  (for  setting  the  “

149

”  value)  or  the  label 

MAP

” (for setting the “

161

” value). 

5. 

 

Press the encoder. 

6. 

 

Rotate the encoder within 15 s to set the value “

4

”. 

7. 

 

Press  the  encoder  (or  take  no  action  for  15  s):  the  display  will 

show “

-  -  -

“ flashing for 4 s, after which the device will exit the 

procedure. 

8. 

Disconnect the device from the power supply. 

9. 

 

Press the encoder for 2s before action 6 to exit the procedure be-

forehand. 

 

For touch key models:

 

make sure that the device is switched off. 

1. 

 

Touch the SET key for 4 s: the display will show the label “

PA

”. 

2. 

 

Touch the SET key. 

3. 

 

Touch the UP or DOWN key within 15s to set the value. 

 

VAL. 

DESCRIPTION 

 

149 

value for restoring the factory information (default) 

 

161 

value for saving customised settings 

4. 

 

Touch  the  SET  key  (or  take  no  action  for  15  s):  the  display  will 

show  the  label  “

dEF

”  (for  setting  the  “

149

”  value)  or  the  label 

MAP

” (for setting the “

161

” value). 

5. 

 

Touch the SET key. 

6. 

 

Touch the UP or DOWN key within 15s to set "

4

". 

7. 

 

Touch  the  SET  key  (or  take  no  action  for  15  s):  the  display  will 

show  “-  - -“  flashing  for  4  s,  after which  the  device  will  exit  the 

procedure. 

8. 

Disconnect the device from the power supply. 

9. 

 

Touch  the  SET  key  for  2s  before  action  6  to  exit  the  procedure 

beforehand. 

 

 