2. TECHNICAL SPECIFICATIONS
Allthesystemcomponentsofthe
EV3 200 WEB controllers meet the requirements of the European Community (EC) for electric
equipment.Theymustbeinstalledinacasingorotherlocationdesignatedforthespecificambientconditionsandtokeepthe
possibility of involuntary contact with dangerous electrical voltages to a minimum. Use metal casings to improve the immunity
of the EV3 200 WEB system to electromagnetic fields. This equipment meets EU requirements as shown in the tables below.
WARNING
MALFUNCTIONING OF THE EQUIPMENT
Do not exceed the nominal values given in this section.
2.1 TECHNICAL SPECIFICATIONS
2.1.1 EV3 200 WEB
Type
Description
The product complies with the following harmonised
standards:
EN60730-1 and EN60730-2-9
Device construction:
Built-in electronic device
Device purpose:
Operating control device
Type of action:
1
Pollution category:
2
Overvoltage category:
III
Rated impulse withstand voltage:
4000 V
Power supply:
115...230Vac,±10%,50/60Hz
Consumption:
10VAmaximum
Ambientoperatingconditions:
-10...50°C(14...122°F)10…90%RHnon-condensing
Transportation and storage conditions:
-20...70°C(-4...158°F)10…90%RHnon-condensing
Software class:
A
Environmental front protection:
IP65
Clock(RTC):
Built-in lithium battery
Clockdrift:
≤60s/monthat25°C(77°F)
Battery life:
30 days
Battery charging time:
24 h through device’s power supply
Data memory:
32 MB
Data memory per device:
~2.7 MB
2.2 I/O FEATURES
2.2.1 EV3 200 WEB
Type
Description
Digital inputs:
2 voltage-free digital inputs
Analogueinputsfortemperature:
2 analogue inputs for NTC probes
Digitaloutputwithnon-hazardousvoltage(SELV):
4 relay outputs
Serial:
1EthernetRJ4510/100MACserialport
1 USB serial port