3.2.1 KEY FUNCTIONS (Cont.)
MESSAGE LOG
The Root menu/Goto View/Message log key calls the first Message Log page for the current group to the screen, as
shown in figure 3.2.1c, below. Alternatively, Message Log can be selected from the Alarm & Message options menu,
(
from a pop-up (Goto Group) menu.
If there are more messages than can be displayed in the height of the screen, a scroll bar appears to allow 'hidden'
messages to be displayed.
Messages are retrieved from the history files in batches of 100 messages. If there are more than 100 messages, 'Ear-
lier messages..' appears after the hundredth message. Touching 'Earlier messages..' calls the option menu, and touch-
ing 'Earlier messages..' in this menu, calls the next batch of 100, and so on. If applicable, operating 'Later messages..'
/ 'Later messages..' calls the previously displayed 100 messages.
As can be seen from the figure, the list of messages can be 'filtered' both by type and by time. For example, setting
the message type to 'Alarm' and the period filter to 'Last Day' excludes all messages except alarm messages which
have occurred within the previous 24 hours.
Figure 3.2.1c Message log page showing message-type picklist
MESSAGE TYPE FILTER
All Messages All messages are displayed
System
Only system messages and instrument alarms are listed.
Alarms
Only alarm on/off and acknowledgement messages appear.
Power Up
Displays power up messages only including Config revision and Security revision are included. See
General
Displays messages sent via Modbus, and operator notes/custom messages etc. If the e-mail option is fitted, a
mesage is generated each time an e-mail is sent. See section 11 of the options manual for details of the e-
mail option.
Batches
Not supported by this recorder version
Logins
Not supported by this recorder version
Signings
Not supported by this recorder version
Audit trail
Not supported by this recorder version
Engineer
Group Name
13:36:25
28/01/04
All Messages
All History
28/01/04 11:19:57 Maths Channel Failure
28/01/04 11:19:57 Power Up
28/01/04 10:55:36 Alarm(s) Ackd 2(1) 2(2)
28/01/04 10:48:14 Alarm(s) off 2(1)
28/01/04 10:39:03 Alarm(s) off 1(1)
28/01/04 10:20:16 Engineer,Overheat on turbine - system..
28/01/04 10:19:57 Alarm(s) on 1(1)
28/01/04 10:10:42 Alarm(s) on 2(1)
28/01/04 09:09:12 Maths Channel failure
28/01/04 11:19:57 Power Up
System
Alarms
Power Up
General
Batches
Logins
Signings
Audit Trail
All Messages
Содержание 5100e
Страница 1: ...Model 5100e 100 mm graphics recorder User guide EUROT HERM ...
Страница 2: ......
Страница 4: ......
Страница 104: ...100 MM GRAPHICS RECORDER USER GUIDE HA027271 Issue 12 Mar 04 User Guide Page 100 This page is deliberately left blank ...
Страница 120: ...100 MM GRAPHICS RECORDER USER GUIDE HA027271 Issue 12 Mar 04 User Guide Page 116 This page is deliberately left blank ...
Страница 134: ......
Страница 135: ......
Страница 136: ......