Instruction Manual ZHK
V07-21.0
97/140
7.9 Lighting
Depending on the number of delivered (optional) lamps, the assignment of the switches and junction
boxes can be found below:
1 Lamp
1 switch
> 1 <= 4 Lamp
1 switch, 1 junction box
> 4 <= 8 Lamp
1 switch, 2 junction box
> 8 <= 12 Lamp
1 switch, 3 junction box
The lamps are mounted and supplied with one side connected and one side with loose cables, suf-
ficient in length to be routed to the nearest junction box or the next switch.
The AHU will be delivered in parts, and for this reason the lights have to be connected on site and
the client is responsible for the completion of this work.
If the AHU require lights to be fitted on site, make sure that sections with condensate (cooling sec-
tions), humidifier sections and wet sections are equipped with lights with appropriate protection of at
least IP55. Switches or junction boxes mounted on the outside of rooftop AHUs must also have at
least protection class IP55.
For AHUs with integrated control and lighting, an additional power supply for the lighting must be
provided and separated from the power supply for the control cabinet. This ensures that the light
also can be switched on during repair work, despite the main switch being switched off (prerequisite
for access to the AHU).
7.10 UV section
This section contains UV-C-lamps to destroy germs on surfaces as well as in the air in the direct
radiation area. If no other configuration is agreed, these lamps should be mounted as evenly as
possible and distributed on the ceiling, the rear sidewall and on the bottom. The number of lamps to
be installed will be determined by consultation with your EUROCLIMA office.
EUROCLIMA is not able to determine the amount of germs killed through the use of UV-C-
lamps.
The lamps will be mounted, cabled, led and fixed to the junction box (inclusive switch) outside of the
AHU by EUROCLIMA.
DANGER!
-
The safety instructions in
chapter 2.3 (Indications for minimizing specific
and the user manual of the lamp manufacturer (delivered with the
present instruction manual) have to be followed and considered.
-
Due to the high voltage of the lamp, maintain it safely and do not work with it
whilst it is active and live.
Danger to life due to electrical shock!
-
DANGER:
UV-risk class 3. These lamps emit strong UV radiation, which could
lead to serious injuries of skin and eyes. Avoid eye and skin contact with un-
screened products. Use them only in a safe and secure environment, which
protects the user against radiation.
WARNUNG!
-
It is highly unlikely that a lamp break would immediately impact on your health,
but repair with caution and safely. If a lamp breaks, air the room for 30
minutes and remove the broken pieces, preferably with cut resistant gloves.
Put the waste into a sealed plastic bag and take them to the local recycling
station. Do not use a vacuum cleaner.
Содержание ZHK
Страница 1: ...ZHK INSTRUCTION MANUAL...