7.1 Electrical connection
All electrical connections must be inspected annually and deficiencies (e.g. loose cable strands,
loose screw, clamp connection, etc.) must be identified and eliminated immediately. Any dust de-
posits must be removed regularly.
The AHU is secured with a micro fuse F1 3.15 A (see
, in
chapter 1.5.1 (Overview / con-
). This may have to be changed if necessary. The following steps must be
followed:
1. Pull the fuse holder out of the AHU.
2. Remove the defective micro fuse.
3. Insert a new micro fuse F1 3.15 A into the fuse holder.
4. Reinsert the fuse holder with the new micro fuse into the power supply.
7.2 Fan / motor group
7.2.1 Vibrations
WARNING!
Danger due to high vibrations / resonance frequency
Permanent operation of the fan-motor-unit at inadmissible high vibrations or at
resonant frequency (and multiples of it) can lead to severe damage of the AHU
and subsequently to damages to property or personnel.
During operation of the AHU, an excessive vibration level can occur due an unfavorable air flow,
accumulation of dirt and dust, missing and / or incorrect cleaning and maintenance
7.2.2 Fan
-
Check for dirt, debris, damage, and corrosion, clean if necessary.
-
Coat surface damage of the housing and impeller with zinc dust paint.
-
Check the protection grid for correct installation / damaged (visual inspection).
-
Test the wheel by rotating it by hand for abnormal noises.
-
In case of irregular or unusual sounds, your service partner must be contacted.
-
The theoretical lifetime, depending on the operating conditions, is at least 20,000 hours.
-
The fan bearings are lubricated for life.
-
Visual inspection: Check the wheel for any weld cracking.
DANGER!
Danger due to lack of or incorrect maintenance of the fan wheel
Deposits on the fan wheel can lead to damage (danger of fatigue fracture).
7.2.3 Motor
-
Check the motor for cleanliness and clean if necessary.
-
In case of irregular or unusual sounds, your service partner must be contacted.
Содержание AirSanitizer
Страница 1: ...AirSanitizer INSTRUCTION MANUAL...
Страница 23: ...Instruction manual AirSanitizer 22 28 V12 20 0 9 Circuit diagram...
Страница 25: ...Instruction Manual AirSanitizer 24 28 V12 20 0 10 2 Declaration of conformity M Version...
Страница 27: ...Instruction Manual AirSanitizer 26 28 V12 20 0 11 2 Nameplate M Version Figure 17 Nameplate M Version...