Operating Instructions Safety Systems
MGB-L1…-AR.-… / MGB-L2…-AR.-… and MGB-L1…-AP.-… / MGB-L2…-AP.-…
30
(Translation of the original operating instructions) 2119167-06-10/20
12.9. Terminal assignment and contact description
X3
X4
X5
X2
LEDs
Power
GN
DIA 1
GN
DIA 2
RD
State
YE
Figure 17: Connections and LEDs
Terminal
Designation
Description
X3.1 to X3.3
-
See the enclosed data sheet
X3.4
UA
Power supply for the guard locking solenoid, monitoring outputs and cover assembly, DC 24 V, must be present continuously so that
the guard locking solenoid functions.
X3.5
0V
Ground, DC 0 V (connected internally to X5.5).
X3.6
IMP2
Control voltage for switching the guard locking on and off, DC 24 V
12.8. Connection of guard locking control on page 29
).
IMP1/IMP2 are usually bridged (jumper) as the default
setting on delivery
X3.7
IMP1
Control voltage for switching the guard locking on and off, DC 24 V
12.8. Connection of guard locking control on page 29
).
X3.8
IMM
Control voltage for switching the guard locking on and off, 0 V (see chapter
12.8. Connection of guard locking control on page 29
X4.1
FI1A
With AR configuration:
enable input for channel A, connect to DC 24 V in separate operation. In case of switch chains, connect
output signal FO1A from previous device.
With AP configuration:
input is not evaluated.
X4.2
FI1B
With AR configuration:
enable input for channel B, connect to DC 24 V in separate operation. In case of switch chains, connect
output signal FO1B from previous device.
With AP configuration:
input is not evaluated.
X4.3
-
See the enclosed data sheet
X4.4
FO1A
Safety output channel A (function dependent on DIP switch setting)
Guard lock monitoring active:
ON when door is closed and locked
.
Guard lock monitoring inactive:
ON when door is closed and bolt tongue is inserted.
X4.5
FO1B
Safety output channel B (function dependent on DIP switch setting)
Guard lock monitoring active:
ON when door is closed and locked
.
Guard lock monitoring inactive:
ON when door is closed and bolt tongue is inserted.
X4.6
RST
Reset input, device is reset if DC 24 V is applied to RST for at least 3 s.
X5.1
OD
Door monitoring output,
ON when the door is closed.
X5.2
OT
Bolt tongue monitoring output,
ON when the door is closed and the bolt tongue is inserted into the locking module.
X5.3
OL
Guard lock monitoring output,
ON when the door is closed and locked.
X5.4
OI
Diagnostics monitoring output,
ON when the device is in the fault state.
X5.5
0V
Ground, DC 0 V
(connected internally to X3.5).
X5.6
UB
Power supply, DC 24 V
X2.1 to X2.8
-
See the enclosed data sheet
X1
-
Reserved for connection of the cover circuit board (only for populated covers)
Table 2: Terminal assignment and contact description