11. Setup
11.1. LED displays
You will find a detailed description of the signal functions in chapter
12. System status table on page 22.
LED
Color
STATE
green
LOCK
yellow
DIA
red
11.2. Teach-in function for actuator (only for unicode evaluation)
The actuator must be allocated to the safety switch using a teach-in function before the system forms a functional unit.
During a teach-in operation, the safety outputs are switched off, i.e. the system is in the safe state.
The teach-in operation is fully automatic. The number of possible teach-in operations is unlimited.
Tip!
Prior to switching on, close the guard on which the actuator to be taught in is installed. The teach-in
operation starts immediately after switching on. This feature simplifies above all teach-in with series
circuits and on large installations.
Important!
Ì
The teach-in operation may be performed only if the device does not have any internal errors.
Ì
Devices in the condition as supplied remain in teach-in standby state until you have successfully
taught in the first actuator. Once taught in, switches remain in the teach-in standby state for ap-
prox. 3 min. after each switch-on.
Ì
The safety switch disables the code of the previous actuator if teach-in is carried out for a new
actuator. Teach-in is not possible again immediately for this actuator if a new teach-in operation is
carried out. The disabled code is released again in the safety switch only after a third code has
been taught in.
Ì
The safety switch can be operated only with the last actuator taught in.
Ì
If the switch detects the actuator that was most recently taught when in the teach-in standby state,
this state is ended immediately and the switch changes to normal state.
Ì
The actuator to be taught in is not activated if it is within the operating distance for less than 30 s.
11.2.1. Actuator teach-in
1. Establish teach-in standby:
-Devices in the condition as supplied: unlimited teach-in standby after switching on
-Switch already taught in: teach-in standby is available for approx. 3 min after switching on
¨
Teach-in standby indication, STATE LED flashes 3x repeatedly
2. Insert the actuator during teach-in standby.
¨
The automatic teach-in operation starts (duration approx. 30 s).
During the teach-in operation the STATE LED flashes (approx. 1 Hz).
Alternate flashing of the STATE and DIA LEDs acknowledges the successful teach-in operation.
Teach-in errors are indicated by the illumination of the red DIA LED and a flashing code on the green State LED (see
12. System status table on page 22
3. Switch off operating voltage UB (min. 3 s).