2136918-04-05/19 (translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CTP-LBI-AP
EN
10.2. Safety in case of faults
Ì
The operating voltage UB and the control voltage IMP are reverse polarity protected.
Ì
The safety outputs FO1A/FO1B are short circuit-proof.
Ì
A short circuit between FO1A and FO1B is detected by the switch.
Ì
A short circuit in the cable can be excluded by laying the cable with protection.
10.3. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number of switches and current required for the
outputs. The following rules apply:
Max. current consumption I
max
I
max
= I
UB
+ I
FO1A
+
FO1B
+ I
OL
+ I
OD
I
UB
= Switch operating current (max. 440 mA)
I
OL
/I
OD
= Load current of monitoring outputs (max. 50 mA per monitoring output)
I
FO1A+FO1B
= Load current of safety outputs FO1A + FO1B (2 x max. 150 mA)
10.4. Requirements for connection cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Ì
Use connection components and connection cables from EUCHNER
Ì
On the usage of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require-
ments.
Observe the following requirements with respect to the connection cables:
For safety switches CTP-…-AP-…-SA-… with plug connector M12, 8-pin
Parameter
Value
Unit
Conductor cross-section, min.
0.25
mm²
R max.
80
W
/km
C max.
120
nF/km
L max.
0.65
mH/km
Recommended cable type
LIYY 8 x 0.25 mm²
10.5. Pin assignment of safety switch CTP-…-AP-…-SA-… with plug connector M12, 8-pin
Wiring diagram C
Plug connector
(view of connection side)
Pin
Designation
Function
Wire color of con-
nection cable
1)
1 x M12
8
5
6
7
2
4
3
1
1
IMP
Operating voltage of guard locking solenoid, 24 V DC
WH
2
UB
Operating voltage of AP electronics, 24 V DC
BN
3
FO1A
Safety output, channel 1
GN
4
FO1B
Safety output, channel 2
YE
5
OI
Diagnostic output
GY
6
OD
Door monitoring output
PK
7
OL
Guard locking monitoring output
BU
8
0 V UB
Operating voltage of guard locking solenoid, 0 V and operating volt-
age of AP electronics, 0 V
RD
1) Only for standard EUCHNER connection cable