Operating Instructions
Non-Contact Safety Switch CES-AH-C03-AE-LS
10
(Translation of the original operating instructions) 2105267-10-08/20
8.4. Automatic restart and start button
Pay attention to the notes for the following applications:
Automatic start, with a jumper
(+24 V is continuously present at the START input)
¨
The device restarts automatically after faults.
Manual start
(start via start button)
¨
The start button must be pressed after each restart.
Ì
A sticking start button (fault due to welding, etc.) is not detected by the device and results in an automatic restart.
DANGER
Danger due to automatic start/restart.
An automatic start/restart can occur:
Ì
On closing the guard
Ì
On switching on the power supply
Ì
On automatic restart after the detection of a fault
Ì
Check carefully which start mode is suitable for your application.
Ì
Check whether additional measures are necessary to prevent an automatic restart.
8.5. Safety in case of faults
Ì
The operating voltage U
B
is reverse polarity protected.
Ì
The coLA/LA and +LB/LB are short circuit-proof and protected against reverse polarity.
Ì
To prevent switching on of the load connected in the case of a short circuit between LA or LB and the operating voltage
U
B
, the cables must be laid rigidly and with protection.
8.6. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the current required for the outputs. If both outputs
(LA and LB) are used, protect with a max. 10 A fuse.
8.7. Voltage drop on cables and switch
If a load is applied to the outputs, voltage drops will occur on the supply cables and on the switch.
The voltage drops are to be taken into account during the calculation of the power available in the load connected.
Parameter
Value
Unit
Maximum resistance of an output path
250
m
W
Resistance for further connecting cable
(e.g. 7 x 1 mm², supply and return cables)
25
m
W
/m
Other connection resistances are to be taken into account as necessary.
8.7.1. Calculation example
Ì
10 m cable from the switch to the supply/load
Ì
Supply voltage on the 24 V connection
Ì
Load on channel A: 1 A
Ì
Load on channel B: 4 A