23
2110182-10-02/20 (Translation of the original operating instructions)
Operating Instructions
Non-Contact Safety Switch CES-A-C5H-EX
EN
13.1.1. Technical data, safety switch CES-A-C5H-EX
Parameter
Value
Unit
min.
typ.
max.
Housing material
PBT V0 GF30
Dimensions
Acc. to EN 60947-5-2
mm
Weight
0.4
kg
Ambient temperature at U
B
= DC 24 V
-20
-
+50
°C
Degree of protection
IP65/IP67
Degree of contamination
3
Rated insulation voltage U
i
-
-
300
1)
V
Rated impulse withstand voltage U
imp
-
-
1.5
kV
Rated conditional short-circuit current
-
-
100
A
Resilience to vibration
Acc. to EN 60947-5-2
Installation orientation
Any
Connection
M12 plug connector, 8-pin, shield can be connected
Operating voltage DC (regulated, residual ripple < 5 %)
21
24
27
V DC
For the approval acc. to UL the following applies
Operation only with UL class 2 power supply or equivalent measures
Current consumption
80
mA
Switching load acc. to UL
Max. DC 24 V, class 2
External fuse (operating voltage)
0.25
-
8
A
Power supply for load U(+LA)/U(+LB)
18
-
27
V DC
Safety outputs (LA/LB, 2 semiconductor outputs, p-switching,
short circuit-proof, electrically decoupled)
- Output voltage U(LA/U(LB)
2)
HIGH U(LA)
U(+LA) - 1.5
-
U(+LA)
HIGH U(LB)
U(+LB) - 1.5
-
U(+LB)
V DC
LOW U(LA)/U(LB)
0
-
1
Switching current per safety output
1
-
100
mA
External fuse (U(+LA)/U(+LB), safety circuit
100 mA medium slow-blow
Utilization category acc. to EN 60947-5-2
DC-13 24 V 100 mA
Monitoring output (OUT, semiconductor output, p-switching,
short circuit-proof)
- Output voltage
0.8 x U
B
-
U
B
V DC
- Max. load
-
-
20
mA
Risk time
3)
-
-
180
ms
Discrepancy time
-
-
120
ms
Ready delay
4)
-
-
3
s
Dwell time
5)
0.5
-
-
s
Switching frequency
-
-
1
Hz
Repeat accuracy R acc. to EN IEC 60947-5-3
≤
10
%
Mounting distance between 2 read heads or 2 actuators
80
-
-
mm
EMC protection requirements
Acc. to EN 60947-5-3
LED displays
STATE
LED green: Normal operation
Flashing:
Teach-in operation
OUT/ERROR LED yellow: Actuator detected
OUT/ERROR LED red:
- EMC interference
- Internal electronics fault
- Invalid teach-in operation
Reliability values acc. to EN ISO 13849-1
Category
4
Performance Level (PL)
PL e
PFH
D
3.7 x 10
-9
/ h
Diagnostic coverage DC
99
%
MTTF
D
644
years
Mission time
20
years
1) Tested by employers’ liability insurance association up to 75 V.
2) Values at a switching current of 50 mA without taking into account the cable length.
3) Maximum OFF time for the safety outputs following removal of the actuator.
4) After the operating voltage is switched on, the semiconductor outputs are switched off and the monitoring outputs are set LOW during the ready delay.
5) The dwell time of an actuator inside and outside the actuating range must be at least 0.5 s to ensure reliable detection of internal faults in the evaluation unit (self-monitoring).