Operating Instructions
Non-Contact Safety Switch CES-A-C5H-EX
12
(Translation of the original operating instructions) 2110182-10-02/20
9. Mounting
WARNING
On use in potentially explosive atmospheres the following applies:
Ì
Protection against mechanical effects on the switch:
-Install switch so that the rear of the housing is entirely covered in order to protect it from me-
chanical damage through impact.
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise
rendered ineffective.
Ì
Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for by-
passing an interlocking device.
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation.
Ì
Safety switches and actuators must not be used as an end stop.
Ì
Observe EN ISO 14119:2013, sections 5.2 and 5.3, for information about mounting the safety
switch and the actuator.
Ì
From the assured release distance S
ar
, the safety outputs are safely shut down.
Ì
When mounting several safety switches, observe the stipulated minimum distance to avoid mutual
interference.
min. 80mm
Ì
If the actuator is installed flush, the operating distances change as a function of the installation
depth and the guard material.
Operating
distance
Actuator
Operating
distance
Actuator
Flush mounting
Surface maounting