Eubank TH Series Heat Pump I&O Manual

09/2018 Rev. 10

IMPORTANT

This manual may include information for options and features which may not be 

included on the unit being installed. Refer to the unit data label or Model Identification 

to determine which features and options this unit is equipped with. 

INSTALLER:  

Affix the instructions on the inside of the building adjacent to the thermostat.

END USER:  

Retain this manual for future reference.

Heat Pump Product Manual

Vertical Wall-Mount Heat Pumps

MODELS:

TH36-42-48-60

Installation & Operation Manual 

TH Series 10 EER Vertical Wall-Mount Heat Pumps

Manufactured By:

A Division of the AIRXCEL

®

 Commercial/Industrial Group

P.O. Box 400 • Cordele, Georgia 31010 • 156 Seedling Drive • Cordele, Georgia 31015

(229) 273-3636 • Fax (229) 273-5154

E-mail: [email protected] • Internet: www.EubankWallmount.com

The most current version of this manual can be found at www.EubankWallmount.com.

Eubank TH Series Heat Pump I&O Manual 09/2018 Rev.10

Part #03698

Содержание TH Series

Страница 1: ...at END USER Retain this manual for future reference Heat Pump Product Manual Vertical Wall Mount Heat Pumps MODELS TH36 42 48 60 Installation Operation Manual TH Series 10 EER Vertical Wall Mount Heat Pumps Manufactured By A Division of the AIRXCEL Commercial Industrial Group P O Box 400 Cordele Georgia 31010 156 Seedling Drive Cordele Georgia 31015 229 273 3636 Fax 229 273 5154 E mail eubanksales...

Страница 2: ...k Failure to follow these rules may result in death serious bodily harm property damage and damage to the equipment Important Safety Precautions 1 USE CARE when LIFTING or TRANSPORTING equipment 2 TRANSPORT the UNIT UPRIGHT Laying it down on its side may cause oil to leave the compressor and breakage or damage to other components 3 TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE instal...

Страница 3: ...ocal codes In the absence of local codes refer to the National Electrical Code NEC ANS NFPA No 70 1993 and recommendations made by the National Board of Fire Underwriters In all cases the equipment MUST be installed in accordance with the installation instructions described in this manual WARNING IMPROPER INSTALLATION MAY DAMAGE EQUIPMENT CAN CREATE HAZARD AND WILL VOID THE WARRANTY OPERATING INST...

Страница 4: ...T PREPARATION 1 TH Series model units have top rain flashing built onto the unit The bottom mounting flange for all models is shipped separately and in place Refer to Section J Unit Installation for the recommended use of the bottom flange 2 Electrical entrances are located on the right side and left side of all TH Series units Refer to Section H Electrical Hook up for details 3 Bend the lids of r...

Страница 5: ... The acceptable voltage range of the tap is as follows Tap Voltage Range 240 Volt 253 216 208 Volt 220 187 Six 6 conductor thermostat wires should be run from the thermostat location to the unit If the unit is equipped with a powered fresh air option seven 7 conductor thermostat wires should be run to the unit Thermostat wire should be sized as shown on the table below Wire Gauge Maximum Length Ft...

Страница 6: ...ted on a coil tube When the thermostat closes the timer on the defrost control starts accumulating the compressor run time After the selected time 30 60 or 90 minutes has been accumulated the controller will start the defrost cycle regardless of the outside temperature During the defrost cycle the system is switched back into the cooling mode by the control de energizing the reversing valve soleno...

Страница 7: ...7 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 EXPLODED PARTS DRAWING 36 42 48 60 ...

Страница 8: ...ER WHEEL 100 9T CCW X X X X X X 14 421506 BLWR MTR BRKT X X X X X X X X X 14A 454280 BLWR MTR BRKT GROMMET TUBE X X X X X X X X X 14B 454282 BLWR MTR BRKT WASHER TUBE X X X X X X X X X 14C 454284 BLWR MTR BRKT MOUNTING SLEEVE X X X X X X X X X 14D 454236 BLWR MTR BRKT WASHER X X X X X X X X X 14E 750058 BLWR MTR BRKT BOLT 1 4 20 X X X X X X X X X 15 T36 0000B ASSEMBLY LEFT SIDE PANEL HV36 X X X 15...

Страница 9: ...9 CONTROL PANEL HV48 60 X X X X X X 31A T60 0093 TERMINAL BOARD PANEL HV48 60 X X X X X 32 T36 0036 CONTROL PANEL COVER HV36 X X X 32 T60 0036 CONTROL PANEL COVER HV48 60 X X X X X X 33 T36 0015 HEAT SHIELD HV36 X X X 33 T60 0015 HEAT SHIELD HV48 60 X X X X X X 453150 COMP CONTACTOR 1 POLE 1P 25 AMP X X 453770 COMP CONTACTOR 2 POLE 1P 40 AMP X 453772 COMP CONTACTOR 3 POLE 3P 25 AMP X X X X X X 452...

Страница 10: ... 0 40 52 0 60 79 0 80 98 8 100 TH48S 208 230 1 60 33 0 50 59 0 60 85 0 90 105 8 110 TH60S 208 230 1 60 39 0 60 65 0 70 91 0 100 111 8 115 TH36T 208 230 3 60 16 0 30 34 0 40 43 0 50 61 0 70 TH42T 208 230 3 60 23 0 35 41 0 50 50 0 60 68 0 70 TH48T 208 230 3 60 23 0 40 41 0 50 50 2 60 68 0 70 TH60T 208 230 3 60 26 0 40 44 0 50 53 0 60 71 0 80 TH36D 460 3 60 9 0 15 18 0 20 23 0 25 32 0 40 TH42D 460 3 ...

Страница 11: ...11 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 3 Typical Wiring Diagram TH36 60 208 230V 1Ø w Barometric Damper No Heat ...

Страница 12: ...12 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 4 Typical Wiring Diagram TH36 60 208 230V 1Ø w Motorized Damper No Heat ...

Страница 13: ...13 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 5 Typical Wiring Diagram TH36 60 208 230V 1Ø w Economizer No Heat ...

Страница 14: ...14 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 6 Typical Wiring Diagram TH36 60 208 230V 3Ø w Barometric Damper No Heat ...

Страница 15: ...15 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 7 Typical Wiring Diagram TH36 60 208 230V 3Ø w Motorized Damper No Heat ...

Страница 16: ...16 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 8 Typical Wiring Diagram TH36 60 208 230V 3Ø w Economizer No Heat ...

Страница 17: ...17 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 9 Typical Wiring Diagram TH36 60 460V 3Ø w Barometric Damper No Heat ...

Страница 18: ...18 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 10 Typical Wiring Diagram TH36 60 460V 3Ø w Motorized Damper No Heat ...

Страница 19: ...19 Eubank TH Series Heat Pump I O Manual 09 2018 Rev 10 Crispaire Division of AIRXCEL Inc Marvair Cordele GA Figure 11 Typical Wiring Diagram TH36 60 460V 3Ø w Economizer No Heat ...

Страница 20: ...R ELEMENT HEATER FAN PURGE SECONDS DOM MINUTES FAN SPEED Figure 12 Typical Wiring Diagram TH36 60 208 230V 1Ø 5kW Heater Circuit Crispaire Division of AIRXCEL Inc Marvair Cordele GA FAN PURGE SECONDS DOM MINUTES FAN SPEED ELEMENT HEATER ELEMENT HEATER FAN PURGE SECONDS DOM MINUTES FAN SPEED Figure 13 Typical Wiring Diagram TH36 60 208 230V 1Ø 10kW Heater Circuit ...

Страница 21: ... HEATER ELEMENTS HEATER FAN PURGE SECONDS DOM MINUTES FAN SPEED GND SPPE Figure 14 Typical Wiring Diagram TH36 60 208 230V 1Ø 15kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 6 KW HEATER FAN PURGE SECONDS FAN SPEED DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 15 Typical Wiring Diagram TH36 60 208 230V 3Ø 6kW Heater Circuit ...

Страница 22: ...D DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 16 Typical Wiring Diagram TH36 60 208 230V 3Ø 9kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 15 KW HEATER FAN PURGE SECONDS FAN SPEED DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 17 Typical Wiring Diagram TH36 60 208 230V 3Ø 15kW Heater Circuit ...

Страница 23: ...SPEED DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 18 Typical Wiring Diagram TH36 60 460V 3Ø 6 9kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 15 KW HEATER FAN PURGE SECONDS FAN SPEED DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 19 Typical Wiring Diagram TH36 60 460V 3Ø 15kW Heater Circuit ...

Страница 24: ... 699 E 14 356 16 406 F 18 457 30 762 G 8 203 10 254 H 1 7 8 48 2 1 4 57 I 28 711 30 762 J 50 1 2 1 283 57 1 8 1 451 K 1 1 8 29 1 1 8 29 L 71 1 2 1 816 87 1 8 2 213 M 2 1 2 64 2 1 2 64 N 10 1 2 267 10 1 2 267 P 18 1 2 470 18 1 2 470 Q 26 1 2 673 26 1 2 673 R 38 7 8 987 42 1 8 1 070 S 1 1 8 29 1 1 4 32 T 9 1 8 232 9 7 8 251 U 36 3 8 924 39 3 8 1 000 V 2 1 8 54 6 1 2 165 W 2 51 2 51 X 48 1 4 1 226 56...

Страница 25: ... 42 40 000 48 50 000 60 59 000 Power Supply S 208 230V 1ø 60Hz T 208 230V 3ø 60Hz D 460V 3ø 60Hz Ventilation Configuration D Solid door E Economizer capable of 100 of rated cooling capacity using outside air F Barometric Damper M Motorized Damper Electric Heat 00 No Heat 05 5 kW 06 6 kw 09 9 kW 10 10 kW 15 15 kW TH Option Accessory Code 2 Coated Condenser Coil C Low Ambient Kit P 2 Pleated MERV 8 ...