Installation, Operation and Maintenance 

SH SERIES 

Ultra Quiet   10+ EER 

Wallmount Heat Pumps 

Содержание SH Series

Страница 1: ...REV 7 7 14 1 3090032 Installation Operation and Maintenance SH SERIES Ultra Quiet 10 EER Wallmount Heat Pumps ...

Страница 2: ...e NEC ANS NFPA No 70 1993 and recommendations made by the National Board of Fire Underwriters In our continuing effort to improve our product specifications may change without notice If there are any questions please see the contact information on the last page of this manual In all cases the equipment MUST be installed in accordance with the installation instructions described in this manual WARN...

Страница 3: ... MUST be able to or be made to safely support the weight of the unit 9 Do NOT locate where heat lint or exhaust fumes will be discharged on the unit as from dryer vents C UNIT PREPARATION 1 The S Series model units have a separate top rain flashing accompanying the unit The bottom mounting flange for all models is shipped separately and in place Refer to Section J Unit Installation for the recomme...

Страница 4: ...elow Wire Gauge Maximum Length 20 45 18 60 16 100 14 160 12 250 Refer to wiring diagrams for connection details STAGING OF ELECTRIC HEAT SH series units with electric heat assemblies are wired for two stage heat in normal operation The first stage is refrigerant heat Y and G terminals are energized and the O terminal is de energized The second stage is auxiliary resistance heat W is energized SH s...

Страница 5: ... G at the unit low voltage terminal board The system reversing valve is energized during the cooling mode Power is supplied to the reversing valve solenoid through the low voltage O terminal The low voltage Y terminal to the control will energize the contactor latch coil causing the contactor to energize the compressor When Y2 is engaged the unit switches from the low to high cooling stage The low...

Страница 6: ...mer may be set to a higher time 90 minutes To change the time move the timer jumper to the postmarked 30 for 30 minutes 60 for 60 minutes or 90 for 90 minutes DEFROST TEST POST The defrost control has test posts to speed up the defrost time setting by a factor of 256 If you want to initiate a defrost without waiting for the time to accumulate you can jumper the two test pins marked test If the coi...

Страница 7: ...REV 7 7 14 7 3090032 EXPLODED PARTS DRAWING 36 48 60 ...

Страница 8: ... GROMMET TUBE X X X X X X X X X 14B 454282 BLWR MTR BRKT WASHER TUBE X X X X X X X X X 14C 454284 BLWR MTR BRKT MOUNTING SLEEVE X X X X X X X X X 14D 454236 BLWR MTR BRKT WASHER X X X X X X X X X 14E 750058 BLWR MTR BRKT BOLT 1 4 20 X X X X X X X X X 15 T36 0000B ASSEMBLY LEFT SIDE PANEL HV36 X X X 15A T36 0135 OD GRILL INLET LEFT SIDE HV36 X X X 15 T60 0008 ASSEMBLY LEFT SIDE PANEL HV48 60 X X X ...

Страница 9: ... HV48 60 X X X X X X 33 T36 0015 HEAT SHIELD HV36 X X X 33 T60 0015 HEAT SHIELD HV48 60 X X X X X X 453150 COMP CONTACTOR 1 POLE 1P 25 AMP X X 453770 COMP CONTACTOR 2 POLE 1P 40 AMP X 453772 COMP CONTACTOR 3 POLE 3P 25 AMP X X X X X X 452842 PHASE MONITOR X X X X X X 450502 COMP CAPACITOR 7 5 80X370V X 450370 COMP CAPACITOR 7 5 45X370V X 450378 450377 COMP CAPACITOR 10 70X370V 7 5 10X370V X 450205...

Страница 10: ... 1 59 60 6 10 10 1 OR 2 85 90 4 8 33 52 60 60 10 6 10 10 SH48T00 208 230 3 1 24 30 12 12 6 1 42 60 8 10 9 1 51 60 6 10 SH48D00 460 3 1 12 15 14 14 6 1 21 30 12 12 9 1 26 30 10 10 SH60S00 208 230 1 1 40 60 8 10 5 1 OR 2 66 90 4 8 40 26 60 30 8 10 10 10 10 1 OR 2 92 100 3 8 40 52 60 60 8 6 10 10 SH60T00 208 230 3 1 27 30 10 10 6 1 45 60 8 10 9 1 54 60 6 10 SH60D00 460 3 1 13 15 14 14 6 1 22 30 12 12...

Страница 11: ...REV 7 7 14 11 3090032 ...

Страница 12: ...REV 7 7 14 12 3090032 ...

Страница 13: ...REV 7 7 14 13 3090032 ...

Страница 14: ...ent parts contact National Coil Company 1998 FM 2011 Longview TX 75603 Phone 903 643 2261 Fax 903 643 2222 TV 36 S 10 F B 00 MODEL SERIES OPTION CODE TV AIR CONDITIONER 10 EER SERIES UP TO 5 CHARACTERS TH HEAT PUMP 10 EER SERIES TR REFRIGERATION SERIES CABINET COLOR SV AIR CONDITIONER LOWSOUND SERIES B MESA TAN Std SH HEAT PUMP LOWSOUND SERIES W WHITE NOMINAL COOLING CAPACITY FRESH AIR 36 36 000 B...