ERROR CODE FAULT

ACTION

ERROR 1

HIGH 

VOLTAGE 

FAULT

•  Check power supply input value 

•  Check high voltage protection value as parameter P1 

ERROR 2

LOW 

VOLTAGE 

FAULT

•  Check power supply input value 

•  Check low voltage protection value as parameter P2

•  Check power supply cable and connector connections

ERROR 3

PHASE 

SEQUENCE 

FAULT

•  Error 3 is occured on 7 segment display in case phase sequence fault 

and system does not work. Change the sequence of phases on power 

supply input.

ERROR 4

HIGH 

CURRENT 

FAULT

•  Before performing any measurement, make sure there is no mechanical 

congestion in pump

•  Measure the current and compare with motor nominal current value 

printed on motor label. 

•  Check high current value set in the parameter P3 and compare with 

motor nominal current value printed on motor label

•  Check motor cable and connector connections. 

ERROR 5

LOW 

CURRENT 

FAULT

•  Before performing any measurement, make sure there is no mechanical 

congestion in pump

•  Make sure that pump suction valve is not closed.

•  Make sure the pump is deaerate before operation.

•  Check low current protection value parameter P4 

•  Measure the current value when suction valve is closed and motor in 

operation. Be careful the input voltage is between 380-400 V during this 

measurement. 

•  The set parameter of low current protection must be %10 higher than 

measured value

ERROR 6

NO WATER

•  Make sure there is enough water in storage tank.

•  Make sure floater level is adjusted properly

•  Check floater cable and contactor connections

ERROR 7 

BLOCKAGE 

FAULT

•  System is blocked when low current protection algorithm completed and 

there is still low current alarm.

•  Make sure that pump suction valve is not closed

•  Make sure the pump is deaerate before operation

•  Check floater in water storage tank

6. Troubleshooting

Содержание Hydropan

Страница 1: ...Hydropan Single with Alarm Kit Operation and Maintenance Manual...

Страница 2: ...witch Fault warning leds as well as Up Down buttons used to surf in menus Approval button to confirm parameter changes and ON OFF button System parameters can be set easily by using Up Down Approval b...

Страница 3: ...3 www etna com tr Connectors Cable Glands Voltage Transformer 7 Segment Display Connection Cable Current Transformers Power Relays Earth Connection Bar Figure 2 Hydropan Single Internal View...

Страница 4: ...rrent Protection Setting High Current Protection Setting Current and Voltage fault delay time setting General Fault Dry Running and Pressure Switch signal warning leds Pump running currents display on...

Страница 5: ...wer supply on the system Voltage value between L1 L2 L3 and neutral is displayed in sequence as seen on the right hand side when there is no signal from pressure switch In case there is signal from pr...

Страница 6: ...in screen It is possible to enter the submenu by re pressing the Approval button and fault display delay duration value can be set by using Up Down buttons Pump Operation Mode Selection Menu as P6 see...

Страница 7: ...s active when Pump Operation Mode parameter set to 1 or 2 requested time duration for well filling or discharging can be set in minutes If this parameter is set to 0 it becomes out of use Figure 11 We...

Страница 8: ...otor label Check motor cable and connector connections ERROR 5 LOW CURRENT FAULT Before performing any measurement make sure there is no mechanical congestion in pump Make sure that pump suction valve...

Страница 9: ...N 1 30A Relay TR U N MOTOR POWER POWER SUPPLY N L1 30A Relay U V W MOTOR POWER POWER INPUT PRESSURE SWITCH COM RUN FAULT WELL L1 L2 L3 Pe 30A Relay TRANSFORMER HYDROPAN 1 30A Relay TR 30A Relay PRESSU...

Страница 10: ...Dudullu Organize Sanayi B lgesi 2 Cadde No 14 34775 mraniye stanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr customer service...

Отзывы: