GPT-130 INSTALLATION GUIDE  |  PART NO. 

25299

 REV 

B

PACKING LIST

QTY.

PART NO. DESCRIPTION

25170 

TRACON MODEL GPT 130 Single-Point General Purpose Heat–Trace Control

25076 

Temperature Sensor

25299 

GPT 130 Installation Sheet (this document)

25166 

GPT 130 Installation and Operation Manual

MODEL GPT-130

TRACON

®

SINGLE–POINT HEAT–TRACE CONTROL THERMOSTAT

PRIOR TO INSTALLATION

1.  Read these installation instructions and manual prior 

to beginning installation.

2.  Install this device only if you are a qualified electrician 

trained to perform such work.

3.  Before beginning installation, lay out the system 

components, the heat trace cable and the 

temperature probe in their approximate locations to 

visualize the system and evaluate exact component 

and junction box placement, as well as required 

cable and conduit lengths.

INSTALLATION

The GPT 130 Automatic Heat–Trace Control should be 

installed  by  a  qualified,  licensed  electrician.  Installation 

must conform to all applicable local and national electrical 

codes and laws. The unit’s NEMA 4X IP66 enclosure allows 

for indoor or outdoor applications.

The GPT 130 controller has an ambient operating 

temperature range of −40 °F to 131 °F (−40 °C to 55 °C). 

To avoid potential internal condensation mount the unit 

out of direct sunlight.

Install  the  GPT  on  a  fixed,  flat,  vertical  surface  using 

the  unit’s  mounting  flanges.  The  mounting  flanges 

accommodate 1/4” or 6.3 mm fasteners.

The GPT 130’s nonmetallic enclosure has one 1.046” hole 

for conduit entry; this can hold both power and load wiring. 

Use only Listed Type 4X IP66 liquid–tight conduit hubs 

or cable glands. Connect the hub to the conduit system 

before connecting the hub to the enclosure.

The unit comes with two installed liquid–tight cable 

glands. One of these fittings is for the temperature sensor 

cable, and the other is for the alarm relay cable.

The cable glands can accommodate cable diameters 

0.08” to 0.24” (2 mm to 6 mm). The temperature sensor 

may be located up to 2,000’ (610m) from the GPT.

There is a removable electrical insulation divider that 

must be in place when there is power applied to the unit.

All leads should be terminated; no unsecured leads 

should be left inside the wiring compartment.