ETI PFC 12 RS Скачать руководство пользователя страница 8

 

PAr 

communication control by parity checking 

oFF 

oFF / on /on_o 

CaSC 

ID number of parallel controller in cascade connection 

0 ... 32 

U_Fr 

grid system frequency

 

50

 

50 / 60Hz

 

CodE 

password for access to SET mode 

0000 

any four digits number 0001 ... 9999 

rES 

reset to the factory setting 

 

Table 4. Configuration menu parameters 

 6.1.  Target cosF setting (CoS1, CoS2) 

Press  the  button 

SET

  at  least  for  5  second  for  entering  configuration  mode.  On  the  display  will  appear  parameter  symbol 

CoS1

. After another pressing of button 

SET

 display will show set value. Via buttons 

 set new requested value in the 

limits from 0,8 inductive to 0,8 capacitive. Another pressing of button 

SET

 saves new value to the memory and on display it 

will appear again symbol 

CoS1

For programming 

CoS2

 follow the same instructions as previous case. For changing  from 

CoS1

 to 

CoS2

 it is necessary to 

connect auxiliary supply of 230 V AC to the terminal marked as 

2nd Tariff

 on the connection diagram. 

 6.2.  Setting of transformer ratio (I_tr, U_tr) 

If 

SET

 mode is activated, move by buttons 

 to the parameter 

I_tr

. After pressing button 

SET

, the set value will appear 

on the display. Via buttons 

 is possible to change value of transformer ratio. Another press of button 

SET

 saves new 

value to the memory and on display, symbol 

I_tr

 will appear again. 

It is important to have in mind that the value which is set, is ratio itself. It means that, for example, if primary nominal current 
of transformer is 50 A and secondary is 5 A then set parameter value is 

I_tr

 = 10. 

In case of voltage transformer usage, parameter 

U_tr

 should also be set the same way. 

Caution 

Measurement range of the current inputs is from 3 mA to 6 A. Maximum of the current transformer ratio is 30000 / 5 A. 

 6.3.  Automatic detection of compensation steps (Auto) 

Another parameter in the menu is function 

Auto

. After pressing of button 

SET

, the display will show 

oFF

. Via buttons 

 

change to the  value 

on

. After double pressing of button 

SET

 automatic detection  will start to detect connected stages. The 

symbol 

CoCo

  will  appear  on  the  display,  and  first  capacitor  stage  will  be  switched  on  and  off  6  times  in  the  cycle  of  20 

seconds. 

Detection  of  regulator  connection  to  the  network  is  followed  by  detection  of  power  of  connected  capacitor  stages.  During 
detection, the measured values of each stage are shown on the display. Measured values are being rounded on 0,5 kvar. After 
the detection is finished, the regulator will switch parameter 

Auto 

back to 

oFF

Important 

In some cases regulator is not able to make automatic detection and in place of measured power shows zeros. It can happen 
in  places  with  very  fast  changes  of  network  parameters,  where  measured  values  will  not  be  correct.  In  this  case  regulator 
shows Err1 and it is necessary to set parameters manually, after detailed network measurements. 

 6.4.  Deceleration of regulation at over compensation (SHtd) 

This  parameter  is  represented  by  symbol 

SHtd

.  This  function  is  used  for  slowing  down  the  regulation  during  over-

compensation. At  under-compensation  regulation  is  slowed  down  according  to  average  power  factor. This  function  assures 
reduction  of  switch  on/off  operation  of  contactor  stages.  After  pressing  the  button 

SET

,  display  will  show  set  value  of 

deceleration. By buttons 

 it is possible to change value and button 

SET

 saves this into the memory. Current situation of 

regulation deceleration during over-compensation is shown under parameter 

SHtd

, in the menu of measured values. 

 6.5.  Manual setting of compensation stages (St_P) 

After  parameter 

Shtd

,  the  parameter  that  follows  in  the  menu  is 

St_P

.  Pressing  the  button 

SET

  will  enter  the  sub  menu, 

where it is necessary to select the stage,  which has to be set, via buttons 

. Selected stage  will be signalized by green 

LED. By pressing button 

SET

 on display will appear set value of stage that is signalized by relevant green LED. Via buttons 

  it  is  possible  to  change  the  value  and  by  pressing  button 

SET

  to  save  this  into  memory.  Via  buttons 

  select 

another stage,  which  must be set and  follow the  same procedure as before. After setting  of all stages,  keep pressing button 

SET

 until display will show 

St_P

 and all LED's will be off. 

Содержание PFC 12 RS

Страница 1: ...ETI d d Obrezija 5 SI 1411 Izlake 1 www etigroup eu products services PFC 12 RS Power factor correction controller User and service manual version 3 9 ...

Страница 2: ...St 9 6 9 Fixed capacitor stages FISt 9 6 10 Connection configuration CoCo 9 6 11 Reactive power offset rCPo 10 6 12 Regulation to average or instantaneous power factor ˉCoS 10 6 13 Averaging time for APFR tACo 10 6 14 Recording of number of operations and maximum values C_St 10 6 15 De compensation steps settings E_IC 10 6 16 Alarms 11 6 17 Configuration of RS485 communication port PFC 12 RS 11 6 ...

Страница 3: ... it is ON when instantaneous or average value of cosφ is shown on the display 6 LED amp volt it is ON when value of measured current voltage is shown on the display 7 LED harm it is ON when total harmonic distortion of current voltage is shown on the display 8 LED kvar kW it is ON when powers are shown on the display 9 LED alarm it is ON when alarm is present 10 LED STAGES dichromatic LEDs indicat...

Страница 4: ...r the time longer than 5 seconds After that device will switch to the configuration menu and on the display will appear parameter CoS1 4 By pressing the button SET once again display will show target cosφ Setting the targeting values of cosφ is done via buttons and 5 Confirmation of the set value CoS1 is done by pressing the button SET 6 Press the button until the parameter Itr will appear on the ...

Страница 5: ... current and voltage up to 19th harmonics and counts THD factor of voltage and current The regulator can operate not just with compensation capacitor stages but also with de compensation reactor stages as well at the same time The power of these reactor stages will be registered with the negative numerical sign De compensation reactors has to be connected after last capacitor stage If the automati...

Страница 6: ... SET again regulator will save changed value to the internal memory and on display symbol of the set parameter will appear again Via buttons it is possible to move to another parameter see the table 4 4 If the offered parameter is not the one which is requested to be modified follow via buttons to the requested parameter 5 Regulator turns back automatically from configuration mode after 1 minute w...

Страница 7: ...F off alarm does not operate IH current trigger value for an alarm activation 0 0 8 A t_IH minimum event duration for an alarm activation 0 0 3600 s o_IH alarm event disconnects compensation steps oFF on oFF Co AL alarm for cosφ that is permanently over set limits oFF on oFF off alarm does not operate _Co cosφ level value for an alarm activation 0 0 80 cap 0 80 ind t_Co minimum event duration for ...

Страница 8: ...l start to detect connected stages The symbol CoCo will appear on the display and first capacitor stage will be switched on and off 6 times in the cycle of 20 seconds Detection of regulator connection to the network is followed by detection of power of connected capacitor stages During detection the measured values of each stage are shown on the display Measured values are being rounded on 0 5 kva...

Страница 9: ...closings Number that appears on display has to be multiplied by 1000 6 9 Fixed capacitor stages FISt On the display it is represented by symbol FISt This parameter allows to set stages as a fixed ones The regulator is not counting those stages for regulation cycle Each stage can stay in three working regimes Auto stage is normally regulated by controller oFF always off status indication LED blinks...

Страница 10: ...rage cosφ calculation 15 30 45 and 60 minutes Default value of period for average cosφ calculation is 30 minutes which refers to half period set from factory on 15 minutes It is suitable for most of applications After entering selected parameter currently set value of time period will appear Via buttons it is possible to change this value Another pressing of button SET saves new value into the reg...

Страница 11: ...mative without feedback on the alarm output 6 17 Configuration of RS485 communication port PFC 12 RS Following parameters relate to configuration of serial communication for RS485 port MODBUS communication protocol Id defines the number of device in the RS485 network and can be set from 1 255 bAUd defines communication speed between the controller and PC Default value is 0 PAr by default it is set...

Страница 12: ..._AP three phase apparent power P_rL three phase active power P_rC three phase reactive power rC_P allowed three phase reactive power Shtd deceleration time C1_S number of 1st stage operation C1_t total operation time of 1st step C2_S number of 2nd stage operation C2_t total operation time of 2nd step C12S number of 12th stage operation C12t total operation time of 12th step U_Fr system frequency t...

Страница 13: ...ings is divided to the 12 for PFC 12 independent levels For the first stage the display will show symbol C1_S and after it disappears the number of first stage circuit closings will be displayed By simultaneous pressing of buttons SET and MAN this information can be erased To another level where information about second stage is move by pressing the button The rest of procedure is the same as for ...

Страница 14: ...ge measuring voltage according the type 400 V AC 10 15 Frequency 50 60 Hz Current range 0 003 6 A Measurement accuracy of current input 0 2 Measurement accuracy of voltage input 0 5 THDU and THDI accuracy U 10 Un 5 I 10 In 5 Phase error for I 3 In 3 otherwise 1 Power consumption 6 VA Output channels number 6 or 12 Switching power of alarm output 250 V AC 5 A Switching power of relay contacts 250 V...

Отзывы: