Model:
SELDLEM3
Self Test LED Emergency Downlight
These instructions are provided as a guideline to assist you.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION
AND RETAIN FOR FUTURE REFERENCE
Pack contents:
1 x 1.4W LED downlight c/w
inverter and battery pack
1 x Silver trim
1 x White trim
1 x Maintenance check record
INSTALLATION INSTRUCTIONS
A guide for qualified electricians
EVENTUALLY, YOU MAY WANT TO
REPLACE THIS PRODUCT:
Regulations require the recycling of Waste from Electrical
and Electronic Equipment (European “WEEE Directive”
effective August 2005—UK WEEE Regulations effective
2nd January 2007). Environment Agency Registered
Producer: WEE/GA0248QZ.
WHEN YOUR PRODUCT COMES TO THE END OF ITS
LIFE OR YOU CHOOSE TO REPLACE IT, PLEASE RECYCLE
IT WHERE FACILITIES EXIST - DO NOT DISPOSE WITH
HOUSEHOLD WASTE.
INDUSTRIAL BATTERIES:
Within certain products Eterna Lighting Ltd places lead
acid, lithium ion, nickel cadmium & nickel metal hydride
batteries on the market. Industrial batteries are subject
to waste regulation under the Waste Batteries and
Accumulators Regulations 2009 and should be disposed
of responsibly. Purchasers may be able to dispose of their
waste industrial batteries locally via legitimate licensed
trade waste contractors. Eterna is obliged to take back,
free of charge and within a reasonable time, waste
industrial batteries of the same chemistry supplied to a
Purchaser, for treatment and recycling and is required
to do this in any calendar year new industrial batteries
are placed on the market. In certain circumstances, this
may include batteries not originally supplied by Eterna.
If any Purchaser requires Eterna to take back Industrial
batteries, they should write to the Operations Director,
Eterna Lighting Ltd, Huxley Close, NN8 6AB, who will then
advise on the necessary arrangements for the receipt,
proper treatment and recycling of, the waste industrial
batteries.
SPECIFICATION:
Self test in accordance with BS EN 62034 : 2012.
LAMP REPLACEMENT:
The light source of this luminaire is not replaceable;
when the light source reaches its end of life the whole
luminaire shall be replaced.
BATTERY REPLACEMENT:
If after routine operation check, the lamp does not
remain lit for the three hour period, a new battery
pack may be required.
1) Isolate from mains supply and unplug the battery
plug lead from the socket and re-plug the new
battery.
2) Restore power and allow charging for 24 hours.
REPLACEMENT BATTERY TYPE:
3.6V 2000mAh Ni-Cad - 3 x C Cell.
CLEANING:
Clean this fitting only with a soft dry cloth.
Do not use any chemical or abrasive cleaners.
IF YOU EXPERIENCE PROBLEMS:
If you believe your product is defective, please return it
to the place where you bought it. Our Technical Team will
gladly advise on any Eterna Lighting product, but may not
be able to give specific instructions regarding individual
installations.
Email: [email protected] / [email protected]
Visit our website:
www.eterna-lighting.co.uk
Made in China
Issue 0419
NOTE: please keep this instruction booklet and
the test record in a safe place. A fire officer or
other authorised person may want to see your
record of inspection and testing.