background image

 

 

Setup and Operation Manual 

 

Integra 1221 

 

Panel Mounted Energy Meter 

for Single and Three Phase 

Electrical Systems 

 

 

 
 
 
 
1 Introduction 

This  document  provides  operating,  maintenance  and  installation  instructions. 
This unit measures and displays the characteristics of Single Phase Two Wire 
(1P2W), Three Phase Three Wire (3P3W) and Three Phase Four Wire (3P4W) 
networks.  The  measuring  parameters  include  Voltage  (V),  Current  (A), 
Frequency (Hz), Power (kW/KVA/KVAr), Power Factor (PF), Imported, Exported 
and  Total  Energy  (kWh/kVArh).  The  unit  also  measures  Maximum  Demand 
Current and Power, this is measured  over preset periods  of up to 60 minutes. 
This  particular  model  accommodates  0.1A  Current  Transformers  and  can  be 
used with a wide range of CTs. It also comes with a complete communications 
capability with built in Pulse and RS485 Modbus RTU outputs, configuration is 
password protected. This product is self-powered from any phase of the supply. 
 

1.1 Unit Characteristics 

The Integra 1221 can measure and display: 
• Phase to Neutral Voltage and THD% (Total   
  Harmonic Distortion) of all Phases 
• Line Frequency 
• Current, Maximum Demand Current and Current    
  THD% of all Phases 
• Power, Maximum Power Demand and Power Factor 
• Imported, Exported & Total Active Energy 
• Imported, Exported & Total Reactive Energy 
 
The unit has a Password-Protected set up menu for: 
• Changing the Password 
• System Configuration - 1P2W, 3P3W & 3P4W. 

• Demand Interval Time 
• Reset for Demand Measurements 
• Pulsed Output Duration 
 

1.2 Current Transformer Primary Current 

This  unit  requires  configuring  to  operate  with  the  appropriate  current 
transformer(s). The secondary current is 0.1A. The CT Primary value should be 
set  according to the  CT. It can be used  on primary currents up to 9999A. e.g. 
For a 250/0.1A CT. CT2 = 0.1, CT1 = 250 

 
On the MID Version, you can only program the CT multiplier ONCE. 
 
This cannot be overridden and must be returned to the factory. 
 

1.3 RS485 Serial 

– Modbus RTU 

This  unit  is  compatible  with  remote  monitoring  through  RS485  Modbus  RTU. 
Set-up screens are provided for configuring the RS485 port.  
 

1.4 Pulsed Outputs 

The Integra  1221 has Two Pulsed Outputs. One pulsed  output is configurable 
to active (kWh) or reactive (kVArh) energy. The second pulsed output is fixed to 
3200imp/kWh. 

 

 

2 Start Up Screens

 

 

The  first  screen  lights  up  all  display  segments 
and can be used as a display check. 

 

The  second  screen  indicates  the  firmware 
installed in the unit and its build number. 
 
Please  note: The  numbers  on the  product may 
vary from those shown here.  
 

 

The interface performs a self-test and indicates 
the result if the test passes. 

 

*After a short delay, the screen will display active energy measurements. 

3 Measurements  

The buttons operate as follows: 

 

Selects  the  Power,  Voltage,  Current,  Energy  per  phase  and  the 
system values. 
In Setup Mode, this is “Escape” (hold 3 sec) button. 

 

Selects the Voltage and Current display screens.  
In Setup Mode, this is the “Left” (press) button.  
 
 

 

Select the Frequency and Power factor display screens.  
In Setup Mode, this is the “Up” (press) button. 

 

Select the Power display screens.   
In 

Setup Mode, this is the “Down” (press) button. 

 

Select the Energy display screens.   
In Setup mode, this is the “Right” (press) or “Enter” (hold 3 sec) button. 
 

4 Setup 

To enter set up mode, hold the 

 button for 3 seconds, until the password 

screen appears. 
 

 

The  setup  is  password-protected  so  you  must 
enter the correct password (d

efault ‘1000’) before 

continuing. 
 
If an incorrect password is entered, the display will 
show: 
PASS  Err (Error). 
 

To exit the set up menu, hold the 

 button for 3 seconds, the measurement 

screen will display. 

4.1 Set up Entry Methods 

Some menu items, such as Password and CT, require a four-digit number entry 
while others, such as supply system, require selection from a number of menu 
options. 
 

4.1.1 Menu Option Selection 

1. 

Use the 

 and 

 buttons to scroll through the different options of 

the setup menu. 

2. 

Hold the 

 button for 3 seconds to confirm your selection. 

3. 

If an item flashes, then it can be adjusted by the 

 and 

 buttons. 

 

4. 

Having selected an option from the current layer, hold the 

 button for 

3 seconds to confirm your selection. 

5. 

On  completion  of  setting-up,  hold  the 

  button  for  3  seconds,  the 

measurement screen will then be restored. 
 

4.1.2 Number Entry Procedure 

When  setting  up  the  unit,  some  screens  require  the  entering  of  a  number.  In 
particular, on entry to the setting up section, a password must be entered. Digits 
are set individually, from left to right. The procedure is as follows:  
 

1. 

The current digit to be set flashes and then can be adjusted using the 

 

and 

 buttons. 

2. 

Press the 

 button to move right to the next digit. 

3. 

After setting the last digit, hold the 

 button for 3 seconds to save your 

selection. 
 

5 Setup Menu Structure 

 

Set Comms 
 

Set Address 001-247 

 

Set Baud Rate 2400/4800/9600/19200/384000 

 

Set Parity none/odd/even 

 

Set Stop Bits 1 or 2 

 

CT Configuration  

Set maximum current that can be monitored according to CT in use.  

 

PT 

 

The PT option sets the Primary Voltage (PT1 100-500000V AC L-N 
or 100-500000V AC L-L) and the Secondary Voltage (PT2 100-276V 
AC L-N or 100-480 L-L) of the Voltage Transformer (PT) that may be 
connected to the meter. 

 

Note:  The  unit  is  able  to  measure  from  57.7V  AC  L-N  however 
PT2 must be set from 100-276V AC L-N.  

Set Pulse  

Pulsed Output-Use this section to configure the Pulsed Output Type. 
Units- kVArh (default); kWh. 
Pulse  Rate-  Configure  the  number  of  pulses  to  relate  to  a  defined 
amount of Total Energy. 
Pulse Duration-

 

The energy monitored can be active or reactive and 

the pulse width can be selected as 200, 100 or 60mS. 
 

Set Demand 

DIT (Demand Integration Time) - This sets the period (in minutes) in 
which the Current  and Power readings  are integrated  for maximum 
demand measurement. The options are 0; 5; 8; 10; 15; 20; 30 or 60 
minutes. 

Demand Method- Within this menu, you are able to set whether the 
demand is displayed using a sliding or fixed method 
 

Set Time 

Backlight-  The  back  light  is  a  programmable  time  (in  minutes)  that 
determines  how  long  this  remains  on  for  before  this  goes  into 
standby. 
Display  Scroll  - Within  this menu,  you  can  determine  how  long  the 
screen is displayed for before it scrolls to the next screen. 

 

Set System 

Sytem Type- The unit has a default setting of 3 Phase 4 Wire (3P4W). 
Use  this  section  to  set  the  type  of  electrical  system. 
3P4W/3P3W/1P2W 
CT Connections -The CT connections can be reversed through the 
“Set Sys Cnct” menu, choosing between Forward (Frd) or Reversed 
(Rev) depending on the system. 
Set Password- Use this menu to create a custom 4 digit password. 
Auto Scroll- Use this menu to determine whether you would like he 
display to scroll through the various display screens.

  

 
Reset 

The meter provides a function to reset the maximum demand value 
of current and power. 
Energy/Demand/All 

 

6 Specifications 
 
6.1 Measured Parameters 

The  unit  can  monitor  and  display  the  following  parameters  of  a  Single  Phase 
Two Wire (1P2W), Three Phase Three Wire (3P3W) or Three Phase Four Wire 
(3P4W) system. 
 

6.1.1 Voltage and Current 

• Phase to Neutral Voltages 57.7-276V AC (L-N). 
• Phase to Phase Voltages 100-480V AC (L-L). 
• Percentage Total Voltage  Harmonic Distortion (V %THD) for each Phase to 
Neutral (not for 3P3W supplies). 
• Percentage Total Voltage Harmonic Distortion (V% THD) between Phases (3 
Phase supplies only). 
• Current %THD for each Phase. 
• Burden <15VA (nom 2VA) 
• Self powered from any phase 
 

6.1.2 Power factor and Frequency and Max. Demand 

• Frequency in Hz 
• Instantaneous power:  
• Power 0-3600 MW 
• Reactive power 0-3600 MVAr 
• Volt-amps 0-3600 MVA 
• Maximum Demand Power since last reset 
• Power factor 
• Maximum Neutral Demand Current, since the last  reset (for 3P4W  supplies 
only) 
 

6.1.3 Energy Measurements 

• Imported/Exported active energy 0 to 9999999.9 kWh 
• Imported/Exported reactive energy 0 to 9999999.9 kVArh 
• Total active energy 0 to 9999999.9 kWh 
• Total reactive energy 0 to 9999999.9 kVArh 
 

6.2 Measured Inputs 

Voltage  inputs  through  4-way  fixed  connector  with  2.5mm²  stranded  wire 
capacity. Single Phase Two Wire (1P2W), Three Phase Three Wire (3P3W) or 
Three Phase Four Wire (3P4W) unbalanced. Line frequency measured from L1 
Voltage or L3 Voltage. Three current inputs in a single physical terminal (RJ12) 
for connection of external CTs. Nominal rated input current 0.1A AC RMS. 
 

6.3 Accuracy 

• Voltage 0·5% of range maximum 
• Current 0·5% of nominal 
• Frequency 0·2% of mid-frequency 
• Power factor 1% of unity (0.01) 
• Active power (W) ±1% of range maximum 
• Reactive power (VAr) ±1% of range maximum 
• Apparent power (VA) ±1% of range maximum 
• Active energy (Wh) Class 1 IEC 62053-21 
• Reactive energy (VARh) ±1% of range maximum 
• Total harmonic distortion 2% up to 63rd harmonic 
• Response time to step input 1s, typical, to >99% of final reading, at 50 Hz. 
 
 
 
 

 

Warnings    

   

 

 

During  normal  operation,  voltages  hazardous  to  life 
may be present at some of the terminals of this unit. 

 

At  voltages  below  that  specified  in  the  Range  of  Use 
the  meter  may  shut  down.    However,  voltages 
hazardous  to  life  may  still  be  present  at  some  of  the 
terminals of this unit. 

 

Installation and servicing should be performed only by 
qualified,  properly  trained  personnel  abiding  by  local 
regulations. 

 

Ensure all supplies are de-energised before attempting 
connection or other procedures. 

 

Terminals  should  not  be  user  accessible  after 
installation  and  external  installation  provisions  must 
be sufficient to prevent hazards under fault conditions. 

 

This unit is not intended to function as part of a system 
providing  the  sole  means  of  fault  protection  -  good 
engineering practice dictates that any critical function 
be protected by at  least two independent  and diverse 
means. 

 

The unit does not have internal fuses therefore external 
fuses  must  be  used  for  protection  and  safety  under 
fault conditions. 

 

Never  open-circuit  the  secondary  winding  of  an 
energized current transformer. 

 

This product should only be operated with the CT 
secondary connections earthed. 

 

If this equipment is used in a manner not specified by 
the  manufacturer,  protection  provided  by  the 
equipment may be impaired.

 

Caution: Risk of 
Electric Shock

 

Отзывы: