18
Power Control Processor Configuration Manual
• Mode: Displays the configured mode of the circuit.
• Current Level: Displays the current level of the selected circuit from the controlling data source
in percent (%). When no control is present, this is shown as a dash (–).
The following five menu options display the individual levels (if applicable) for DMX, sACN, Arch,
current set level, Panic/Emergency, and Contact Input.
• Breaker: Displays the state of the breaker in the panel as either
On
or
Off
.
• Contact: Displays state of the relay contact as either
Closed
or
Open
.
• Load: Displays the load both as amperes (A) and calculated (VA). The load value displays and
updates in real time. Multiple pole relays will show loads for each pole (load (1), load (2), etc.) For
the Echo Relay Panel Feedthrough, voltage is not measured, so this field will contain a dash (–).
• Voltage: Displays the voltage as received for the output. For Echo Relay Panel Mains Feed and
Sensor IQ, this is equal to the measured voltage coming into the rack. For EchoDIN, this is the
voltage measured from the relay. For Echo Relay Panel Feedthrough voltage is not measured,
therefore this field will contain a dash (–).
• Software: Displays the version number of the installed software in the relay card.
Levels Summary
Displays the output information for each position, including its highest
takes precedence (HTP) control level and winning input source. Use the
[Up]
or [Down]
buttons to view additional lines of text. The
information provided includes:
• DMX input: DMX
• Streaming ACN: sACN
• Set Levels: Set
• Preset, Sequence or Zone: Arch
• Emergency Look: Emerg
• Contact Input: Cont
• No Control of dimmer: – – –
• Hold Last Look: when the control source (DMX or sACN) has been lost, but the circuit is holding
its level received from the last look.
Load Type
Modes
Description
Relay
Normal
For a relay, the output is off below the threshold and on at or above the
threshold. For a dimmer, the output is off below the threshold and dims above
the threshold.
Fluorescent
Used for circuits in conjunction with the 24-Channel, 0–10V Dimming Control
option. The circuit will switch on at the threshold value and control the 0-10V
dimmed levels using the option card.
Latch/Lock
Latch/Lock mode can be used for circuits where extra security is desired when
turning them on or off. To turn the relay or breaker on, the DMX or sACN level
must be held at a specified value for a certain period of time, and at another
value to turn it off. The on and off values are configurable (see
).
DALI
Used for circuits in conjunction with the DALI option card. The circuit will switch
on at the threshold value and control the DALI output using the option card.
Always On
Output is always turned on.
Dimmer
Auto
Automatically detects phase angle control of the connected load
Forward
Forward-phase dimming control
Reverse
Reverse-phase dimming control
Pos Ckt Src Level
1 12 Cont 255
2 1 sACN 125
3 2 Arch 75
4 3 --- ---
5 4 DMX 255
6 5 Emerg 255
7 6 Set 0