ETC Installation Guide

Unison Paradigm

®

 Occupancy Sensor

Occupancy Sensor Installation Guide

 Page 1 of 8

Electronic Theatre Controls, Inc.

Corporate Headquarters

 

 Middleton, Wisconsin, USA 

 Tel +608 831 4116

 

 Service: (Americas) 

[email protected]

 

London, UK

 

 Tel +44 (0)20 8896 1000 

 Service: (UK)

 

[email protected]

 

Rome, IT 

 Tel +39 (06) 32 111 683 



Service: (UK)

 

[email protected]

 

Holzkirchen, DE

 

 Tel +49 (80 24) 47 00-0



Service: (DE)

 

[email protected]

 

Hong Kong 

 Tel +852 2799 1220 



Service: (Asia)

 

[email protected]

Web:

 

www.etcconnect.com

 

 Copyright © 2016 ETC. All Rights Reserved. 

Product information and specifications subject to change. 



ETC intends this document to be provided in its entirety.

7184M2160

 

 Rev C 



Released 2016-07 

Overview

The Unison Paradigm

®

 Occupancy Sensor is a ceiling mounted sensor that 

utilizes passive infrared (PIR) technology, providing reliable vacancy and 
occupancy detection for lighting control. Paradigm Occupancy Sensors 
integrate with Paradigm lighting control systems, providing energy efficient 
lighting control solutions.

Each sensor is available in neutral white or black finish. Lens masks are 
provided to allow customized occupancy detection fields as required by each 
installation.

Wire Specification

The Paradigm Occupancy Sensor utilizes LinkConnect to power the sensor and 
to provide data to and from the connected Paradigm control system. 
LinkConnect is topology-free and polarity independent. You can install your 
data runs in any desired combination of bus, star, loop, and home-run. ETC 
recommends using Belden 8471 (or equivalent) wire. The total combined 
length of a LinkConnect wire run may not exceed 1,640 feet (500m), with a 
maximum distance of 1,312 feet (400m) between any two devices.

All control wiring should be installed and terminated by a qualified installer 
and should follow standard wiring installation practices and meet local codes. 
Leave approximately 10 inches (254mm) of wiring in the junction box or tied 
back in the ceiling to allow for wiring connections and future service needs.

Note:

ETC requires that all sensors be grounded by using a 14 AWG 
(2.5mm

2

) ESD drain wire.

The Paradigm Occupancy Sensor provides 360 degree coverage 
of the installed location and is available in three models:

P-OCC-SR

- Occupancy Sensor with small room lens 

covers 450 sq. ft. at 8 ft. (41.8m

2

 at 2.4m) / 800 sq. ft. at 

12 ft (74.3m

2

 at 6.65m).

P-OCC

 - Occupancy Sensor with standard room lens 

covers 1,800 sq. ft. at 8 ft. (167m

2

 at 2.4m)/ 3,000 sq. ft. 

at 12 ft. (279m

2

 at 6.65m).

P-OCC-HC

 - Occupancy Sensor with high ceiling lens 

covers 350 sq. ft. at 12 ft. (32.5m

2

 at 2.4m)/ 7,000 sq. ft. 

at 40 ft. (650m

2

 at 12.2m)

Содержание P-OCC-SR

Страница 1: ...ion Wire Specification The Paradigm Occupancy Sensor utilizes LinkConnect to power the sensor and to provide data to and from the connected Paradigm control system LinkConnect is topology free and pol...

Страница 2: ...r adjacent rooms If the installation location cannot avoid these conditions portions of the lens can be masked to block the sensor view of these undesired areas Reference Lens Masking on page 5 Parts...

Страница 3: ...ng Belden 8471 typically black wire into the terminals c Close the levers onto the wires d Repeat the above for the installed typically white Belden 8471 LinkConnect wire and the remaining pigtail fro...

Страница 4: ...igning the tabs on the sensor with the slots on the mounting plate then twist clockwise until the two are locked into place Soft Ceiling Tile Installation Step 1 Pull the Belden 8471 or equivalent and...

Страница 5: ...ion type Step 5 Create a hole for wire pass through in the ceiling tile by poking through the center hole or oblong hole of the mounting plate then pull the wires through Step 6 Strip each wire 5 16 8...

Страница 6: ...the service pin LED blinks The neuron ID is labeled on the sensor control board and can be manually entered into the configuration using LightDesigner software Alternatively the sensor can be identif...

Страница 7: ...t the sensor A green LED will begin to flash indicating the walk test is enabled and the vacancy no vacancy occupancy timer will be shortened to 10 seconds Step 3 Move throughout the space including c...

Страница 8: ...room and confirm the configured vacancy no occupancy state was properly recalled Step 5 Walk test mode will automatically exit after five minutes from the time it was enabled To manually exit the walk...