Chapter 3 

25

WARNING:

RISK OF ELECTRIC SHOCK! This device utilizes high voltage

and should only be installed by a qualified installer or electrician. Follow all
local codes for installation. Before terminating the AC power wiring verify
that the main breaker is in the off position and follow the proper
lockout/tag out procedures required by NFPA Standard 70E.

AVERTISSEMENT :

RISQUE DE DÉCHARGE ÉLÉCTRIQUE! Cette appareil

utilise une haute tension et ne doit être installé que par un installateur
qualifié ou un électricien. Suivez tous les codes locaux pour l'installation.
Avant de raccorder le câblage du courant alternatif, vérifiez que le
disjoncteur principal est en position d'arrêt et suivez les procédures de
Consignation/Déconsignation prescrites par la norme NFPA 70E.

WARNING:

RISK OF ELECTRIC SHOCK! Circuits that are installed without

an accessible power disconnect device cannot be serviced or operated
safely.

AVERTISSEMENT :

RISQUE DE DÉCHARGE ÉLÉCTRIQUE! Il est imprudent

d'utiliser ou de réparer les circuits installés sans qu'un dispositif de
déconnexion de l'alimentation ne soit accessible.

Follow the instructions to wall-mount the W1 Emergency Driver before connecting the Sense
and Maintained inputs. See

Wall-Mount the W1 Driver on page 14

.

Connect the Sense Input

Connect the "Sense" input to a normal branch circuit or to the 48 VDC output from the panic
connector of an F-Drive R12. See

Emergency System Overview on page 7

for details on the

"Sense" functionality.

1. Make sure power is off at the main circuit breaker.
2. See

Electrical and Wiring Specifications on page 12

for specification of wire, strip length, and

terminal torque ratings. Prepare the wires accordingly.

3. Loosen the three screw terminals for NEUTRAL (N), GROUND (

), and LINE (L) connections.

4. Insert the ground wire (typically green) into the GROUND (

) terminal and tighten the

screw.

5. Insert the neutral wire (typically white) into the NEUTRAL (N) terminal and tighten the screw.
6. Connect the line wire (typically black) into the LINE (L) terminal and tighten the screw.
7. Tug gently on the wires to ensure they are secure.

Connect the Maintain Input

Connect "Maintain" input to a normal/emergency branch circuit with upstream UL 1008
automatic transfer switch:

1. Loosen the three screw terminals for NEUTRAL (N), GROUND (

), and LINE (L) connections.

2. Insert the ground wire (typically green) into the GROUND (

) terminal and tighten the

screw.

3. Insert the neutral wire (typically white) into the NEUTRAL (N) terminal and tighten the screw.
4. Connect the line wire (typically black) into the LINE (L) terminal and tighten the screw.
5. Tug gently on the wires to ensure they are secure.

Содержание F-Drive W1 Series

Страница 1: ...F Drive Series W1 Installation Manual Part Number 7148M2110 Rev D Released 2022 01...

Страница 2: ...ademarks and patents go to etcconnect com ip All other trademarks both marked and not marked are the property of their respective owners ETC intends this document whether printed or electronic to be p...

Страница 3: ...Emergency System Overview 7 W1 Emergency Functionality 7 Before You Begin Installation 9 Installation Requirements 9 Power Disconnect Device 9 Chapter 2 W1 Installation 10 Prepare to Install the W1 1...

Страница 4: ...ntrol 27 Navis Luminaire DMX Personalities 28 RDM Parameters 29 On Below Minimum 31 Live Edit Configuration Files 32 Edit Offline and Save Configuration Files to MicroSD32 Firmware Upgrade Instruction...

Страница 5: ...see the resources below F Drive System Design Tool The F Drive System Design Tool etcconnect com Products Power Controls LED Drivers F Drive F Drive System Design Tool aspx allows you to design an F D...

Страница 6: ...r unwanted consequences of an action potential for data loss or an equipment problem WARNING A Warning statement indicates situations where damage may occur people may be harmed or there are serious o...

Страница 7: ...82 USA toll free 1 608 831 4116 service etcconnect com ETC GmbH Germany Austria Switzerland Eastern Europe and Russia Technical Services Department Ohmstrasse 3 83607 Holzkirchen Germany 49 80 24 47 0...

Страница 8: ...mbols for your safety Refer to the product label to see which symbols apply to your product General warning Avertissement g n ral This product should not be discarded as unsorted waste but must be sen...

Страница 9: ...er circuit patching W1E models are UL 924 and CSA C22 2 No 141 listed for emergency lighting control WARNING Connect this equipment to a non dimmable power source in order to avoid damage to the equip...

Страница 10: ...o 200 700 mA fixtures manufactured by others constant current adjustable from 200 700 mA default output 600 mA see Configure the W1 CC Driver on page 22 48 VDC 700 mA 33 W 2 8 A 134 W RJ45 and 4 two p...

Страница 11: ...ncy Driver is a UL924 listed variant of the W1 Driver The W1 Emergency Driver is available in constant current constant voltage and Fade to Warm models Install the W1 Emergency Driver in a location th...

Страница 12: ...e same phase The diagram below shows the recommended installation F Drive W1E Maintain Sense A B C A Battery backed supply B Normal mains supply C Changeover relay Sense Input from F Drive R12 48 VDC...

Страница 13: ...ORT PAR D CHARGE LECTRIQUE N gliger de d brancher toutes les sources d alimentation du syst me avant l installation l entretien le nettoyage ou toute autre modification du syst me peut causer des bles...

Страница 14: ...p style conduit connectors for outputs Phillips screwdriver Flatblade screwdriver Wire stripping and cutting tool Wire ties 5 mm nut driver Four 10 screws and other mounting hardware as needed Note Mo...

Страница 15: ...er is tethered to the backbox Be careful when handling 3 Using the 5 mm nut driver remove the four nuts securing the mounting straps to the back of the W1 Driver Save the mounting straps and nuts for...

Страница 16: ...10 AWG solid or stranded Class 1 wiring only For connections use wire rated for at least 75C 7 mm 1 4 in 0 5 Nm 4 4 in lb Maintained power input ground 2 5 10 mm2 14 6 AWG 10 mm 3 8 in 4 0 Nm 35 in l...

Страница 17: ...X_TERM Wire power and data DMX to the W1 Driver and then run power out to the Navis luminaires or other loads If you are installing a W1 Emergency Driver see W1 Emergency Driver Installation on page 2...

Страница 18: ...stration on the previous page The text on the installed cover will be upright 2 Remove the two screws on the cover of the driver and set them aside 3 Remove the driver cover The cover is tethered to t...

Страница 19: ...RU MAINTAIN MAINTAIN Factory Wire Colors Model Color Type North America and Europe green yellow ground earth North America black line hot North America white neutral Europe brown live Europe blue neut...

Страница 20: ...or operated safely AVERTISSEMENT RISQUE DE D CHARGE L CTRIQUE Il est imprudent d utiliser ou de r parer les circuits install s sans qu un dispositif de d connexion de l alimentation ne soit accessibl...

Страница 21: ...hite DMX Cat5 Preparation and Termination This instruction assumes use of Cat5 or equivalent cable for termination to the three position Cat5 insulation displacement connector IDC provided in the term...

Страница 22: ...the ends of the unused pair of wires with a 2 5 cm 1 in piece of 0 5 cm 3 16 in heat shrink centered over the end of the wires 9 Strip 6 mm 1 4 in of insulation from all of the wires to be used 10 Mai...

Страница 23: ...nect only Navis 100 Fade to Warm luminaires to a W1 Fade to Warm Driver Connect only Navis 100 RGBW luminaires to a W1 Chroma Driver CAUTION Possible damage to equipment Connect only the same types of...

Страница 24: ...Navis 100 Fixed White luminaires RJ45 Pinout for Navis 100 Fixed White and Fade to Warm Luminaires RJ45 Pin Description Typical Wire Color T568B standard 1 Ground white and orange 5 Power white and bl...

Страница 25: ...W1 CC Driver Note Maximum supported wire length between ArcSystem Pro One Cell Standard Small and Micro luminaires and F Drive W1 is 100 m 328 ft Connect ArcSystem Pro One Cell Luminaires to the RJ45...

Страница 26: ...4 The FD BBOX 4T takes a single four channel RJ45 output from an FTW 150 Card or CC 150 Card and provides four separated two pin output channels Visit the F Drive System Design Tool at etcconnect com...

Страница 27: ...r current and complete compliance information view the F Drive W1 Driver datasheet at etcconnect com Products Power Controls LED Drivers F Drive Documentation aspx Wire a W1 Emergency Driver SENSE 1 2...

Страница 28: ...ame conduit according to NEC 700 10 B Note Use suitable conduit where required by local or national code Factory Wire Colors Model Color Type North America and Europe green yellow ground earth North A...

Страница 29: ...ts See Wall Mount the W1 Driver on page 14 Connect the Sense Input Connect the Sense input to a normal branch circuit or to the 48 VDC output from the panic connector of an F Drive R12 See Emergency S...

Страница 30: ...ches one for each output Leave the switch for each output in the default OFF 30 V position to allow the TEST button to work with Navis 100 Fixed White and Navis 100 Fade to Warm luminaires and other l...

Страница 31: ...n ETC Concert software with RDM See DMX System Control below and RDM Parameters on page 29 Identify An identify command can be sent to a control card or to a channel of an output card When you send an...

Страница 32: ...Navis RGBW luminaires to 3000 K Fixed White and Fade to Warm luminaires When all four IRGB channels are set to 100 the output from the RGBW luminaire is 3000 K white light The Warm Trim DMX personali...

Страница 33: ...ll output card channels report their current addresses and a footprint of 1 W1 Chroma Driver will report a footprint of 4 in IRGB mode or 5 in Direct mode See DMX Personality below Device Model Descri...

Страница 34: ...o to Off Sending set to the root determines the behavior if DMX is lost Scenes and Hold Time are not supported DMX Loss Behavior Description 0x810B Sending get to the root returns an ASCII text string...

Страница 35: ...All other models Intensity See DMX System Control on page 27 Get Slot Description 0x0122 Default Slot Value 0x0122 Factory Defaults 0x0090 Set resets the configurations of the control card and all ou...

Страница 36: ...propriate Lockout Tagout procedures as mandated by NFPA 70E or local jurisdiction requirements It is important to note that electrical equipment such as breaker panels can present an arc flash hazard...

Страница 37: ...he microSD card slot 3 Remove the microSD card 4 Save the new R12 firmware files to the root of the microSD card Overwrite the old firmware files on the microSD card The firmware files must be named a...

Страница 38: ...A Safe Working Practices CAUTION RISK OF ELECTRIC SHOCK Disconnect power before servicing ATTENTION RISQUE DE CHOC LECTRIQUE Couper l alimentation avant l entretien Emergency Operation and Test It is...

Страница 39: ...ple blink receiving firmware update DMX 1 green solid on DMX data is present slow blink DMX data is absent DER 1 emergency models only green solid on test passed See Emergency Operation and Test on th...

Страница 40: ...on Visit etcconnect com products for current and complete compliance information including FCC compliance Note This equipment has been tested and found to comply with the limits for a Class A digital...

Страница 41: ...Appendix A 37...

Страница 42: ...38 W1 Installation Manual...

Страница 43: ...Appendix A 39...

Страница 44: ...k NY Orlando FL Los Angeles CA Austin TX Web etcconnect com Support support etcconnect com Contact etcconnect com contactETC 2022 Electronic Theatre Controls Inc Trademark and patent info etcconnect c...

Отзывы: