background image

This guide covers all models of MOS-IR and MOS-DT ceiling occupancy sensor.
The MOS-IR product family includes:

MOS-IR-

x

A    Motion sensor with small motion short range lens (1000 sq. ft.)

MOS-IR-

x

B    Motion sensor with large motion large range lens (1900 sq. ft.)

MOS-IR-

x

C    Motion sensor with high bay lens (6300 sq. ft.)

The MOS-DT product family includes:

MOS-DT-

x

A   Motion and audio sensor with small motion short range lens (1000 

sq. ft.)

MOS-DT-

x

B   Motion and audio sensor with large motion large range lens (1900 

sq. ft.)

Where x is the frequency of the unit:  U=902 MHz, Y=868 MHz and J=928 MHz.

The package includes the occupancy sensor, lens mask sticker, mounting 

plate with integrated magnets for T-Bar ceiling, wire straps and installation 

guide. 

These Occupancy Sensors are intended for indoor use only in a dry location.

MOS-IR/DT

W

IReleSS

 C

eIlIng

 M

OunT

 S

enSOR

 

fOR

 O

CCupanCy

 / V

aCanCy

 D

eTeCTIOn

INSTALLATION GUIDE

Note:

                                                                                                    

The MOS is a solar powered device that absorbs solar energy 

storing it for use during low light periods. Before assigning 

the MOS device to a receiver/controller, the device should be 

exposed to a good light source for a minimum of 5 minutes 

or install the start assist battery.    

i

Содержание echoflex MOS-IR Series

Страница 1: ...ns 1900 sq ft Where x is the frequency of the unit U 902 MHz Y 868 MHz and J 928 MHz The package includes the occupancy sensor lens mask sticker mounting plate with integrated magnets for T Bar ceilin...

Страница 2: ...07 01 The sensor must be within range of any linked receivers or controllers installed within 80 24m of each other For applications exceeding 80 24m range telegram repeaters may be needed to extend r...

Страница 3: ...e walls at acute angles This increases the material the telegram must pass through reducing the signal power Avoid large metal obstructions as they create radio shadows Place receivers in alternate lo...

Страница 4: ...stall a battery Installation Instructions Choose a mounting method 1 The axillary mounting plate allows mounting with the integrated magnets to a steel T bar ceiling frame or other metallic surface by...

Страница 5: ...s needed peel off the lens masks to fit the desired area to be blocked 2 Apply the mask gently to the section of the lens exterior to block the required area from occupancy sensing Linking the Sensor...

Страница 6: ...hours 4 160 320 16 32 12 hours 200 hours 5 320 32 6 hours 225 hours The time to fully charge is based on the storage capacitor charging from a non operational condition Discharge time indicates how lo...

Страница 7: ...for 10 seconds Sensor Setting Mode This mode allows adjustment of the PIR Sensitivity Audio Sensitivity and Sensor Occupancy Timer duration False occupancy states caused by external elements can be re...

Страница 8: ...conds until they stop blinking 4 The red LED blinking indicates the motion detection LED is active The green LED blinking indicates the LEDs are inactive Tapping the teach button will toggle between t...

Отзывы: