ETC echoflex ELED1 Скачать руководство пользователя страница 1

Echoflex Installation Guide

LED Fixture Controller (120-277 VAC) ELED1

Corporate Headquarters

n

Middleton, WI, USA

|

+1 608 831 4116

Web

echoflexsolutions.com

|

Email

[email protected]

|

Support

[email protected]

©2022 Echoflex Solutions, Inc. Trademark and patent info: 

echoflexsolutions.com/ip

Product information and specifications subject to change.
Echoflex intends this document to be provided in its entirety.

8189M2100

Rev D Released 2022-08

Overview

The LED Fixture Controller (120-277 VAC) (ELED1) provides wireless
control of an individual fixture or single zone lighting based on
occupancy state, manual switch action, ambient light levels, and gateway
commands.

ELED1-DUN

ELED1-DUS

This document covers installation of all the ELED1 models. The

Echoflex

LED Fixture Controller ELED1(H) Configuration Guide is available for
download at

echoflexsolutions.com

.

The product package includes the controller, installation guide, and
mounting strap (for ELED1-DUS model).

Prepare for Installation

To ensure optimal function, consider the installation environment and the
following guidelines:

Avoid spaces with high density construction materials and large
metal appliances or fixtures as they may disrupt wireless reception.

For optimal performance, switches and sensors should be installed
within a 24 m (80 ft) unobstructed view of the controller. Consider
adding a repeater to extend the wireless signal, if required.

Mount the controller to an electrical junction box (preferably non-
metallic) or a panel in a location and at a height where it is not
subject to tampering by unauthorized personnel.

Make sure the antenna wire is unrestricted and not in contact with
any metal surface.

Содержание echoflex ELED1

Страница 1: ...e ELED1 models The Echoflex LED Fixture Controller ELED1 H Configuration Guide is available for download at echoflexsolutions com The product package includes the controller installation guide and mounting strap for ELED1 DUS model Prepare for Installation To ensure optimal function consider the installation environment and the following guidelines Avoid spaces with high density construction mater...

Страница 2: ... pour l installation Avant de raccorder le câblage du courant alternatif vérifiez que le disjoncteur principal est en position d arrêt et suivez les procédures de Consignation Déconsignation prescrites par la norme NFPA 70E WARNING For indoor use only Must install to an electrical junction box or wireway AVERTISSEMENT Uniquement pour usage d intérieur Doit être installé sur une boîte de raccordeme...

Страница 3: ...ray and the violet wires to the driver or ballast s dimming interface optional 6 Replace the electrical box cover plate and restore power to the circuit Install ELED1 with Mounting Strap Mount the controller to the exterior of a lighting fixture or appliance using the supplied mounting strap Note Mounting inside a fixture or other metal cabinet will reduce radio range performance 1 Locate the circ...

Страница 4: ...ed Line Hot Dimming 0 10 V violet Dimming COM gray Neutral white Max Dimming Load 100 mA sinking Max Impulse Voltage 4000 V Internal Relay Type 1 C Dimming output is Class 1 circuit Independently mounted control for panel mount surface mount Line Hot black 120 277 V Diagram for Emergency Fixtures 1 of 2 ELED1 LED Driver LED Driver Neutral Normal Control Sense Dimming Dimming Normal Emergency Load ...

Страница 5: ...ange wire is an antenna Do not cut cap or connect this wire Use only UL approved wire when making connections to the controller Connection Color Specification Load Red 14 AWG 600 V Neutral White 14 AWG 600 V Line hot Black 14 AWG 600 V Dimming 0 10 V Violet 18 AWG 600 V Dimming COM Gray 18 AWG 600 V User Interface Note Garibaldi Pro software is the ideal tool to set up your project and configure s...

Страница 6: ... a If the controller has a linked sensor you must press the Teach button on the sensor and complete step 2 within 60 seconds 2 Click the switch paddle ON three times OFF three times and ON three times quickly for a total of nine consecutive clicks The relay will toggle and the Power LED will indicate the switch is linked Clear Button The Clear button can be used to reset the controller either to i...

Страница 7: ...ks that count the sensors Off Photo sensor maximum of 1 3 long blinks followed by short blink that counts the sensor Off Gateways and TimeClocks 4 long blinks followed by short blinks that count the devices Off Demand response 5 long blinks followed by short blinks that count the devices Off Entry door sensors 6 long blinks followed by short blinks that count the sensors Off Window sensors 7 long ...

Страница 8: ...red Power LED repeats a blink code to indicate the type and number of devices currently linked to the controller To test press the Learn button or use a linked switch In factory default state when powered up the Power LED displays solid red to indicate the controller has no linked devices To test press the Learn button or link a switch See relevant switch documentation A maximum of 20 switches or ...

Страница 9: ...to radio communications Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense Contains FCC ID SZV STM300U ISED Compli...

Страница 10: ...Echoflex Installation Guide LED Fixture Controller 120 277 VAC LED Fixture Controller 120 277 VAC Page 10 of 12 Echoflex ...

Страница 11: ...Echoflex Installation Guide LED Fixture Controller 120 277 VAC LED Fixture Controller 120 277 VAC Page 11 of 12 Echoflex ...

Страница 12: ...Echoflex Installation Guide LED Fixture Controller 120 277 VAC LED Fixture Controller 120 277 VAC Page 12 of 12 Echoflex ...

Отзывы: