ETC E-DVAC-C-LR Скачать руководство пользователя страница 8

ETC Installation Guide

Dual Tech Vacancy Sensor

Power Up

All EchoConnect terminations in the system must be made before applying
power to the system and sensor. When the sensor is powered up, the PIR and
acoustic detection LEDs illuminate for one minute for calibration and warm-
up. Both the PIR and acoustic detection features of the sensor will
automatically adjust the sensitivity threshold to eliminate nuisance tripping.
During this time configuration is not allowed and no events are triggered.

Configuration

Basic

When the sensor is in Basic configuration mode (DIP switch 2 set to Off), the
sensor will activate a Space Off command when vacancy is detected.

Custom

When functionality other than Space Off is required, place the sensor in
Custom configuration mode (DIP switch 2 set to On). Customization of the
sensor and all actions are configured using the EchoAccess App.

For more detailed information about custom configuration options available
using EchoAccess, see the EchoAccess App integrated help system.

Operation

Dual Technology

When both PIR and acoustic detection are used, the following logic is used:

When the space is vacant, only manual control can switch the state to
occupied.

When the space is occupied, PIR, acoustic detection, and manual
control can reset the vacancy timeout.

When the vacancy timeout in the space has only been reset by acoustic
detection for 60 minutes, acoustic detection is disabled until the next
PIR detection event.

PIR (only) Detection

When acoustic detection is disabled (DIP switch 6 set to On), the following
logic is used:

When the space is vacant, only manual control can switch the state to
occupied.

When the space is occupied, PIR detection and manual control can
reset the vacancy timeout.

Dual Tech Vacancy Sensor

Page 8 of 12

ETC

Содержание E-DVAC-C-LR

Страница 1: ...l The sensor relies on local station control for manual on and provides auto off functionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options...

Страница 2: ...n environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sen...

Страница 3: ...connection and to allow slack for future service needs Note ETC requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for grounding when control...

Страница 4: ...cation junction box or finished surface and strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...ll the sensor wires through the access holes to the unfinished side of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on the sensor...

Страница 6: ...y A buttons and their related LEDs are not used and have no functionality on the Dual Tech Ceiling mount Vacancy Sensor Set Space and Address Two rotary switches on the sensor electronics provide for...

Страница 7: ...are ignored Instead the settings made by the EchoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and...

Страница 8: ...o On Customization of the sensor and all actions are configured using the EchoAccess App For more detailed information about custom configuration options available using EchoAccess see the EchoAccess...

Страница 9: ...gins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period a...

Страница 10: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 11: ...t 3 0 m 10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6...

Страница 12: ...ETC Installation Guide Dual Tech Vacancy Sensor Dual Tech Vacancy Sensor Page 12 of 12 ETC...

Отзывы: