Emergency System One-Cell Installation
31
Emergency System One-Cell Installation
With the exception of power input terminations, ArcSystem emergency system installation
requirements are the same as those of the standard ArcSystem. Complete the appropriate steps
for your installation, referencing the following sections for any additional installation details
before wiring the power:
•
Preparing the Ceiling for Recessed Luminaires on page 12
•
Installing One-Cell Recessed Luminaires on page 14
•
Installing One-Cell Yoke-Mounted Luminaires on page 14
•
D4 Series Wall-Mount Driver Installation on page 15
or
Emergency Driver Power Input Wiring
D4 Emergency Drivers are available for systems requiring emergency lighting control.
Note:
The installation must conform to local and national codes.
D4 Emergency Drivers require two branch circuit power input connections, normal sense and
maintained (emergency).
•
Maintained (emergency) provides constant power to the D4 Driver regardless of the state,
enforcing the ability to maintain a lights on condition when needed. The power source
must be connected to an emergency branch circuit with an upstream UL1008 automatic
transfer switch.
•
Normal sense detects when normal power is present. In the event of a normal power
failure, the D4 Driver will force all output channels on the D4 Driver to full (100%). Any
control of the connected output channels will be unavailable until normal power has been
restored.