ETC Installation Guide
D1 & D2 Series Drivers
D1 & D2 Series Drivers
Page 10 of 25
ETC
Installing One-Cell Recessed Luminaires
The installation procedure is similar for all recessed one-cell luminaires (fixed and adjustable). For
Pro One-Cell yoke-mounted luminaires, continue on to
Installing One-Cell Yoke-Mounted
.
WARNING:
ArcSystem Pro One-Cell, One-Cell Small, and One-Cell High
Output fixtures and D1 and D1 High Output drivers are NON-IC rated and
therefore NOT suitable for installation in direct contact with combustible
materials or thermal insulation.
DO NOT INSTALL INSULATION WITHIN 76 mm (3 in) OF ANY PART OF THE
FIXTURE OR DRIVER.
AVERTISSEMENT :
Les lampes One-Cell, One-Cell Small, One-Cell High
Output, et les drivers D1 and D1 High Output ArcSystem sont classés NON-IC, ils
ne conviennent donc PAS pour une installation en contact direct avec des
matières combustibles ou une isolation thermique.
NE PAS INSTALLER D’ISOLATION À MOINS DE 76 mm (3 po) DE TOUTE PARTIE
DE LA LAMPE OU DU DRIVER (DISPOSITIF ÉLECTRONIQUE DE PUISSANCE).
WARNING:
Adjustable ArcSystem Pro One-Cell fixtures and adjustable
ArcSystem Pro One-Cell Small fixtures are suitable for Non-Fire Rated
installations ONLY.
AVERTISSEMENT :
Les lampes Pro One-Cell ArcSystem réglables et Pro One-
Cell Small ArcSystem réglables sont parfaites UNIQUEMENT pour les
installations sans indice de résistance au feu.
Note:
Make sure that the flexible electrical supply can extend through the ceiling
opening so that the driver and luminaire can be inspected and serviced when needed.
Note:
ArcSystem Pro One-Cell Micro luminaires and D2 drivers are Type IC - inherently
protected and suitable for installation in contact with insulation.
1. Fold both retaining clips towards the luminaire body.
2. Place the luminaire through hole.
3. Release the clips, securing the luminaire in place.
4. When applicable, rotate the luminaire so it is roughly
focused to its final resting position. This will assist in
final focus procedures.