ETC Installation Guide

ArcSystem Pro Multi-Cell

ArcSystem Pro Multi-Cell

Page 10 of 24

ETC

Installing 100–277 V Multi-Cell Fixtures

This section provides the information needed to install 100-277 V Multi-Cell fixtures.

Supplies

The following supplies are required for installation, but not provided:

½ in flex conduit and conduit fittings

Appropriate strain relief connectors for the installation type, as needed

Phillips head screw driver

120

Ω

RJ45 terminator for DMX termination. See

Terminate DMX on page 13

.

Note:

Mounting hardware and installation location must support the weight of the fixture,

conduit hardware, and all cable required for installation.

Electrical and Wiring Specification

Install ArcSystem 100–277 V fixture on a power distribution system with reliably identified earthed
neutral and install a maximum 20 A circuit breaker on the line conductor.

ArcSystem 100–277 V fixtures and drivers accept 100–277 VAC, 50/60 Hz. ETC recommends
installing all wiring in grounded metal conduit.

Wire and Terminal Specifications

Fixture Type

Terminal /

Connector

Conduit

Entry

Wire Range / Specification

Strip Length

Pro Two-Cell,
Pro Four-Cell Square,
Pro Four-Cell Linear,
Pro Eight-Cell

Power Input -
line/neutral/ground

½ in conduit

0.2–4 mm
(24–12 AWG)

11 mm (0.43 in)

DMX In/Thru
RJ45 Connectors

N/A

Cat5e (or better) minimum 24
AWG conductors terminated
to T568B standard

N/A

Note:

ArcSystem fixtures are not self-terminating. You must terminate the last fixture in

line with a 120

Ω

resistor. To purchase an RJ45 terminator, please contact your ETC

customer service representative and request part number N4086.

Содержание ArcSystem ARCP2

Страница 1: ...ture options all with high efficiency optics and an outstanding quality of light ideal for any application This manual provides step by step instruction on the installation and RDM configuration of Ar...

Страница 2: ...nd RDM ARCP8 100 240 V or 100 277 V Pro Eight Cell ARCP8RDM 100 240 V or 100 277 V Pro Eight Cell RDM ArcSystem Multi Cell Emergency Fixtures with Integral Drivers Model Description ARCPE2 100 240 V o...

Страница 3: ...with IEC connector or 100 277 V hard wired input options Emergency 100 125 V with NEMA 5 15 connectors or 100 277 V hard wired input options linear and square yoke mount round and pendant options beam...

Страница 4: ...ETC Installation Guide ArcSystem Pro Multi Cell ArcSystem Pro Multi Cell Page 4 of 24 ETC...

Страница 5: ...rd wired to emergency certified drivers to be considered for UL924 certification Note Emergency fixtures must be installed in a high bay situation Note The number of designated emergency lamps and the...

Страница 6: ...ored WARNING Do not mix 120 V and 277 V between the sense and emergency feeds AVERTISSEMENT Ne pas inverser les alimentations 120 V et 277 V entre les alimentations de d tection et de secours WARNING...

Страница 7: ...graves ou la mort De energize main feed to ArcSystem and follow appropriate Lockout Tagout procedures as mandated by NFPA 70E It is important to note that electrical equipment such as breaker panels...

Страница 8: ...DMX run RJ45 Pinout Information Pin Description 1 Data 2 Data 7 8 ISO ground common Four cell square fixture shown DMX In and Thru connections Power switch Power connection Installation Procedure 1 A...

Страница 9: ...mm or 1 2 13 in with the two provided screws 2 Attach the fixture to the installed threaded rod 3 Plug in the provided power cable 4 If using hard wired DMX plug in the RJ45 connector into the DMX In...

Страница 10: ...cSystem 100 277 V fixture on a power distribution system with reliably identified earthed neutral and install a maximum 20 A circuit breaker on the line conductor ArcSystem 100 277 V fixtures and driv...

Страница 11: ...Mounting hardware and installation location must support the weight of the fixture conduit hardware and all cable required for installation 1 Make sure power is off at the main circuit breaker 2 Atta...

Страница 12: ...ed with three two position WAGO connectors ETC part number J4717 WAGO part number 221 412 See Installing 100 277 V Emergency Multi Cell Fixtures on page 15 for more information about wiring for emerge...

Страница 13: ...he wire is secure 5 Terminate line hot a Locate the WAGO connector on the line hot wire black from the input b Run a line hot wire through conduit to a free position on the WAGO connector Note Line ho...

Страница 14: ...rgency fixture shown Actual cable length is 2 1 m 7 ft ArcSystem 100 125 V multi cell emergency systems include Pro Two Cell Pro Four Cell Square Pro Four Cell Linear Pro Four Cell Round and Pro Eight...

Страница 15: ...wiring compartment B conduit entry for 1 2 in conduit C DMX in and thru D knockout for 1 2 in conduit With the exception of power input terminations ArcSystem 100 277 V emergency system installation r...

Страница 16: ...upplied with one three position WAGO ETC part number J4629 WAGO part number 221 413 and four two position WAGO connectors ETC part number J4717 WAGO part number 221 412 Factory Wire Colors Color Type...

Страница 17: ...Maintained input a Locate the WAGO connector on the line hot wire black from the input labeled Maintained b Run a line hot wire through conduit to a free position on the WAGO connector Note Line hot w...

Страница 18: ...k that all wires are terminated properly and secure in their terminals 2 Tuck wiring and WAGO connectors inside wiring compartment Replace the wiring compartment cover using the screws set aside previ...

Страница 19: ...each DMX line Wireless DMX control requires a TX1 Transmitter and fixtures with the wireless ArcMesh transceiver For wireless DMX installation see the ArcSystem Installation Manual available from etc...

Страница 20: ...LEDs with a single DMX address The multi channel personality controls individual LEDs or pairs of LEDs with up to four channels as shown below Note You cannot manually assign DMX addresses to each cha...

Страница 21: ...2 or 3 Set to 1 is the Default Tungsten Curve aka D04A Set to 2 is Linear Set to 3 is Square Law Curve Description 0x0344 Get returns an ASCII text string Output Response Time 0x0345 0x01 1000 ms 100...

Страница 22: ...ng any cleaning and maintenance AVERTISSEMENT D brancher la lampe de son alimentation et du DMX et la laisser refroidir avant d effectuer un nettoyage ou un entretien WARNING Circuits that are install...

Страница 23: ...ult in serious injury or death AVERTISSEMENT RISQUE DE MORT PAR D CHARGE LECTRIQUE N gliger de d brancher toutes les sources d alimentation du syst me avant l installation l entretien le nettoyage ou...

Страница 24: ...ication DMX Link LED Slow flash normal operation DMX broadcast is being received and DMX data is not changing Solid On active DMX signal is being received Solid On DMX is present DMX Status LED Steady...

Отзывы: