ETAtouch controller
[Heating circuit] function block
63
Setting heating limits for the reduced operation
mode
1. Change the selector switch to the reduced
operation mode position (
).
Use the arrow keys to reduce parameter [Heating
threshold], so that the heating circuit in reduced
operation mode switches off at a lower outside
temperature, or increase the value.
At settings below 0 °C, there is a risk of
freezing.
Fig. 5-73: Heating limit for reduced-temperature mode
5.7.4
Text menu - Adjustable parameters
Adjustable parameters
Detailed descriptions of the parameters are provided
below.
Explanation of [Room effect]
Optional: only for room sensor
The flow temperature is calculated on the basis of the
heating curve and the outside temperature. If the room
temperature falls by 1°C, the target flow temperature is
increased by this set value. If the room temperature
rises by 1°C, the target flow temperature is decreased
by the set value.
For underfloor and wall heating with a design
temperature of 30 °C, set the room influence to 1
°C; with a design temperature of 40 °C, set it to 2 °C.
Explanation of [Switch-on diff. room] and [Switch-
off diff. room]
Optional: only for room sensor
These parameters specify the allowed deviation of the
set room temperature for switching the heating circuit
on and off.
Example:
Room temperature setting = 21 °C
[Switch-on diff. room] = 0.5 °C
[Switch-off diff. room] = 2 °C
=> The heating circuit will be switched off as soon as
the room temperature reaches 23 °C (=21 + 2 °C). If
the room temperature falls to 21.5 °C (=21+0.5 °C),
heat is supplied to the heating circuit again.
Heating circuit
Room
Room effect
Switch-on diff. room
Switch-off diff. room
Содержание 13180LP-T
Страница 1: ...2018 05 24 EN 0000000313 V 005 3 43 0 3308 93222 001 Pellet boiler 180 220 kW Operation ...
Страница 29: ...ETAtouch controller Getting to know the control system 29 ...
Страница 39: ...ETAtouch controller BufferFlex function block 39 ...
Страница 47: ...ETAtouch controller Buffer function block 47 ...
Страница 51: ...ETAtouch controller Hot water tank function block 51 ...
Страница 55: ...ETAtouch controller Fresh water module function block 55 ...
Страница 69: ...ETAtouch controller Solar function block 69 ...
Страница 87: ......
Страница 88: ...www eta co at www eta co at downloads DOWNLOAD ...