ProNet Plus Series AC Servo User's Manual
- 134 -
the next slave station; if need not, add balance resistor in CN4 terminal.).It is prohibited to connect CN3 of any two servo
drives directly when multiple ProNet series servo drives are connected.
Example:
When a RS-485 network is composed of a PLC and three servo drives (A, B, and C), the cable wiring is shown as follows:
PLC→CN3 of A, CN4 of A→CN3 of B, CN4 of B→CN3 of C, CN4 of C→120Ω terminating resistance.
In the case of ProNet-
□□□
EG-EC servo drives, the communication method is using the standard mini-USB port. By
using the CP2102chip, it converts the RS232 communication to USB communication. Thus, it is necessary to install the
CP2102 drive in the host computer. In addition, the definitions of the communication connector terminals are as follows.
Terminal No.
Name
Function
1
5V
Isolated Power
2
D-
Communication terminal
3
D+
Communication terminal
4
DI
Reserved
5
G
Isolated ground
6.2 MODBUS Communication Related Parameters
Parameter No.
Description
Setting
Validation
Control Mode
Meaning
Pn700
Hex
After restart
ALL
Pn700.0 MODBUS baud rate
[0] 4800bps
[1] 9600bps
[2] 19200bps
Pn700.1 Communication protocol
[0] 7, N, 2 (MODBUS,ASCII)
[1] 7, E, 1 (MODBUS,ASCII)
[2] 7, O, 1 (MODBUS,ASCII)
[3] 8, N, 2 (MODBUS,ASCII)
[4] 8, E, 1 (MODBUS,ASCII)
[5] 8, O, 1 (MODBUS,ASCII)
[6] 8, N, 2 (MODBUS,RTU)
[7] 8, E, 1 (MODBUS,RTU)
[8] 8, O, 1 (MODBUS,RTU)
Pn700.2 Communication protoco selection
[0] SCI communication with no protocol
[1] MODBUS SCI communication
Pn700.3 Reserved
Pn701
MODBUSaxis address After restart
ALL
Axis address of MODBUS protocol
communication