E-SL 450BD Series Instruction Manual
Parameters
16
1.
LED shows P1: P1 is for setting your run time.
The run time exists to allow to
have the P2 slow down setting. This should always be set at least 5 seconds longer than
it takes to open and close. This will allow the gate to go the full motion when moving
slower on cold or windy days. If the number of P1 is reached on the counter during a
cycle prior to reaching the limit switch the gate will stop on the number. The options are
0-99 sec-onds.
2.
LED shows P2: P2 is for setting your slow down time.
The gate opener will
slow down to partial speed after the counter has reached the setting of P2. If you wish
to have the gate open and close faster make the slow down start time a higher number.
If you want to put less stress on the gears and gate set the slow time lower number.
The options will adjust to match the previously set run time.
3.
LED shows P3: P3 is the force setting
.
the lower the number the easier the gate
will reverse directions when it meets resistance. This number may have to be changed
to a higher setting if your gate is obstructing unexpectedly. The number should be set to
the highest number during initial setup and reduced to the point of reliable operation
that takes into account change in gate resistance through out the year. The options are
0-32.
4.
LED shows P4: P4 is for setting a delay between leafs
.
if you have overlapping
gates or a gate lock. The motor wired into the primary terminals (1) opens first if there
is a delay and closes second. It is recommended to have a delay of 3 seconds to avoid
any jam-ming issues between leafs.
5.
LED shows P5: P5 is the release for the gate lock
– this option determines the
length of time 24VDC will be sent out of terminals E_LOCK. The options are 1-4
seconds.
6.
LED shows P6: P6 is the delay for automatic re-close
from the open position –
this op-tion needs to be turned on using the dip switch on the board. The options are 0-99
sec-onds.