SIGA-CRR Polarity Reversal Relay Module 

Installation Sheet 

 

 

Description 

The SIGA-CRR Polarity Reversal Relay Module is an 
addressable device that is used to power and activate the 
audible sounder in Signature audible detector bases. 

The module can support a 2 A load of bases. Upon command 
from the loop controller, the SIGA-CRR module relay transfers, 
reversing the polarity of its 24 VDC output.  

The module requires one address on the signaling line circuit 
(SLC). Addresses are assigned electronically. There are no 
address switches. 

Diagnostic LEDs provide visible indication of the state of the 
module through the cover plate: 

• 

Normal: Green LED flashes 

• 

Alarm/active: Red LED flashes 

Personality code 

The module requires the loop controller to download the 
personality code that determines how the module operates. 
Use the personality codes described below to configure the 
SIGA-CRR. See Table 1 for listing information. 

Personality code 8: 

Signal - dry contact output. Configures 

the module as a dry relay contact to control external 
appliances (door closers, fans, dampers) or equipment 
shutdown. 

 

 

 

Table 1: Personality code listing information 

Code Description 

UL 

864  CAN/ULC-

S527 

EN 54-18

8  

Signal - dry contact output  Yes 

Yes 

Yes 

Installation 

Notes 

• 

The module is shipped from the factory as an assembled 
unit; it contains no user-serviceable parts and should not 
be disassembled. 

• 

This module does not operate without electrical power. As 
fires frequently cause power interruption, discuss further 
safeguards with the local fire protection specialist. 

Install in accordance with all applicable local codes and 
standards and the local authority having jurisdiction. 

To install the module: 

1.  Wire in accordance with “Wiring” on page 2

2.  Write the address assigned to the module on the label 

provided, and then apply the label to the module. Remove 
the serial number label from the module, and then attach it 
to the project documentation. 

3.  Using the screw provided, mount the wall plate on the 

module. See Figure 1 for mounting details. 

4.  Using the screws provided, mount the wall plate (with the 

module attached) on one of the compatible electrical 
boxes listed in “Specifications” on page 3

© 2012 UTC Fire & Security. All rights reserved. 

1 / 4 

P/N 387336P-EN • REV 6.0 • ISS 29FEB12 

Содержание SIGA-CRR

Страница 1: ...rnal appliances door closers fans dampers or equipment shutdown Table 1 Personality code listing information Code Description UL 864 CAN ULC S527 EN 54 18 8 Signal dry contact output Yes Yes Yes Installation Notes The module is shipped from the factory as an assembled unit it contains no user serviceable parts and should not be disassembled This module does not operate without electrical power As ...

Страница 2: ...fications Each terminal on the module is limited to a single conductor To wire the module 1 Verify that all field wiring is free of opens shorts and ground faults 2 Make all wiring connections as shown in Figure 2 Figure 2 Wiring diagram 1 2 3 4 6 5 1 Auxiliary riser in from power limited regulated power supply listed for fire protective signaling 2 Auxiliary riser out to next sounder base Polarit...

Страница 3: ...ang cover Wire size 12 to 18 AWG 0 75 to 2 5 mm Operating environment Temperature Relative humidity 32 to 120 F 0 to 49 C 0 to 93 noncondensing Storage temperature range 4 to 140 F 20 to 60 C Regulatory Information Manufacturer Edwards A Division of UTC Fire Security Americas Corporation Inc 8985 Town Center Parkway Bradenton FL 34202 USA Authorized EU manufacturing representative UTC Fire Securit...

Страница 4: ...l waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info Contact information For contact information see www utcfireandsecurity com 4 4 P N 387336P EN REV 6 0 ISS 29FEB12 ...

Отзывы: