  D A T A   S H E E T

 85001-0609

 

Not to be used for installation purposes.

  Issue 2  

EST Catalog 

u

 Intelligent Input-Output

05-18-11

05-18-11

Overview

SIGA-CC2A and SIGA-MCC2A Single/Dual Input Signal Modules 
are part of EST's Signature Series system. They are intelligent 
analog addressable devices used for connecting, upon command 
from the loop controller, supervised Class A or Class B signal or 
telephone circuits to their respective power inputs. 

Module power inputs may carry polarized 24 Vdc current to oper-
ate audible and visible signal appliances, or 25 and 70 V

RMS

 to 

operate audio evacuation speakers and firefighter’s telephones. 
The SIGA-CC2A/MCC2A may be configured as a three-state or 
four-state telephone riser selector.

The loop controller assigns an address to the module automati-
cally. No addressing switches are used. A custom address can be 
assigned using a laptop computer. 

Diagnostic LEDs provide visible indication of the status of the 
module when the cover plate is removed:

• Normal — green LED flashes
• Alarm/active — red LED flashes

The CC2A mounts in a two-gang electrical box. The MCC2A 
plugs into a UIO motherboard. Both modules provide the same 
functionality.

The actual operation of the module is determined by the “person-
ality code” selected by the installer. It is downloaded to the module 
from the Signature loop controller during system configuration.

 Standard Features

•  Class A or B Operation
•  Supports three- and four-state telephones
•  Dual input (riser) select

Use for connecting supervised 24 Vdc Audible/Visible signal 
circuits, or 25 and 70 VRMS Audio Evacuation and Telephone 
circuits to their power inputs.

•  Ring-tone generator

When configured for telephone circuits, the SIGA-CC2A/MC-
C2A generates its own ring-tone signal eliminating the need for 
a separate ring-tone circuit.

•  Plug-in (UIO) or standard 2-gang mount

UIO versions allow quick installation where multiple modules 
are required. The 2-gang mount version is ideal for remote 
locations that require a single module.

•  Automatic device mapping

Signature modules transmit information to the loop controller 
regarding their circuit locations with respect to other Signature 
devices on the wire loop.

•  Electronic addressing

Programmable addresses are downloaded from the loop con-
troller or a laptop PC; there are no switches or dials to set. 

•  Ground fault detection by address

Detects ground faults right down to the device level.

Signal Modules 

with Class A 

Operation

SIGA-CC2A, SIGA-MCC2A

MEA

Application Notes 

Available

CHINA

S

SIGA-MC

C2A

SIGA-MCC2A

SIGA-CC2A

Содержание SIGA-CC2A

Страница 1: ...onality The actual operation of the module is determined by the person ality code selected by the installer It is downloaded to the module from the Signature loop controller during system configuration Standard Features Class A or B Operation Supports three and four state telephones Dual input riser select Use for connecting supervised 24 Vdc Audible Visible signal circuits or 25 and 70 VRMS Audio...

Страница 2: ...perates as a riser selector for a four state open normal active trouble firefighter s telephone Only one telephone can be used with the CC2A at any given time When a telephone handset is plugged into its jack or lifted from its hook the module generates its own ring tone signal A separate ring tone riser is unnecessary The module sends this signal to the control panel to indicate the presence of a...

Страница 3: ...dentifies each device on the loop and assigns a soft address to each serial number If desired the modules can be addressed using a laptop computer No addressing switches are used Warnings Cautions These modules do not provide supervision of the riser The fire alarm panel must provide this function These modules do not support conventional 2 wire smoke detec tors These modules will not operate with...

Страница 4: ...ller Installation Sheet for wiring specifications 4 These modules will NOT support two wire smoke detectors 5 All wiring power limited and supervised If the input source is non power limited then maintain spacing of 1 4 inch or use FPL FPLP FPLR or equivalent in accord ance with NEC 6 The SIGA UIO6 does not come with TB8 through TB13 7 Supervised and power limited 8 Supervised and power limited wh...

Страница 5: ...Voltage 20 VDC Current Standby 310 µA Alarm 135 µA Ground fault impedance 10 k Ohms Wire Size 12 to 18 AWG 2 5 to 0 75 sq mm Maximum line impedance Refer to the installation manual for your fire alarm control panel Output rat ings special applications 24 VDC 2 A 25 VAC audio 50 W 70 VAC audio 35 W EOL resistor value 47 kΩ Max circuit resistance Refer to manual Max circuit capacitance 0 1 µF Operat...

Страница 6: ...329 F 866 503 3996 Canada Chubb Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T 65 6391 9300 F 65 6391 9306 India T 91 80 4344 2000 F 91 80 4344 2050 Australia T 61 3 9239 1200 F 61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity com 2010 UTC Fire Security All rights reserved ...

Отзывы: