SIGA-278 Double Action Fire 

Alarm Station Installation Sheet 

 

Description 

The SIGA-278 Double Action Fire Alarm Station is an addressable, 

normally-open, dry contact signal initiating device that requires two 

user actions to initiate an alarm. First, the upper door marked LIFT 

THEN PULL HANDLE must be raised to access the alarm handle. 

Second, the alarm handle must be pulled to initiate an alarm. The 

single input module mounted on the back of the unit supervises the 

station and sends an alarm signal to the Signature controller when the 

switch is closed (i.e., when the handle is pulled). 
The device requires one address on the signaling line circuit (SLC). 

Addresses are assigned electronically. There are no address switches. 
Diagnostic LEDs provide a visible indication of the status of the module 

when the unit is removed from the electrical box. 

  Normal: green LED flashes 

  Alarm/active: red LED flashes 

Personality codes 

The module requires the loop controller to download a personality 

code that determines how the module operates. Table 1 shows the 

personality codes available for the SIGA-278. 

Table 1: Personality codes 
Code 

Description 

Alarm - NO latching (Class B) 

Active - NO latching (Class B) 

 

Installation 

Install and wire this device in accordance with applicable national and 

local codes, ordinances, and regulations. 

Notes 

  The device is shipped from the factory as an assembled unit; it 

contains no user-serviceable parts and should not be 

disassembled. 

  This device will not operate without electrical power. As fires 

frequently cause power interruption, we suggest that you discuss 

further safeguards with your local fire protection specialist. 

  Electrical supervision requires that the wire run be broken at each 

terminal. Do not loop the field wires around the terminals. 

To install the SIGA-278: 

1.  Insert the key into the cover lock and turn the key to open the 

station, rotating the cover away from the backplate. 

2. 

Verify that all field wiring is free of opens, shorts, and 

ground 

faults. 

3.  Wire the module as shown in Figure 2. 
4.  Write the address assigned to the module on the label provided, 

and apply the label to the module. Remove the serial number labe

from the module, and then attach it to the project documentation. 

5. 

Using the two #6

-32 × 1/2 machine screws provided, mount the 

pull station on the electrical box. 

6

.  Install the glass rod into the mounting brackets inside the cover. 

7.  Set the toggle switch on the backplate 

to the NORMAL position

8. 

Rotate the cover back into position on the backplate, turn the key 

to secure the cover, and then remove the key. 

Figure 1: Mounting the SIGA-278 

 

(1)  Compatible electrical box 

(2)  Backplate 

(3) 

#6

-32 × 1/2 screw (2X) 

 

(4)  Cover lock and key 

(5)  Front cover 

(1)

(2)

(3)

(5)

(4)