7.5.3 Fire Output
In this submenu the installer can disable/ enable the fire output activation and the time delay operation.
To access the FIRE submenu, enter in the
installer’s menu - 5. PANEL OUTPUTS - FIRE (3).
Attention: In access level 2 you can only review the set delay status (ON/ OFF), with no rights to change it!
The functional buttons have the following action:
(2)
- Press to change the status of the fire output. Every pressing of
the button changes alternatively the ENABLED - DISABLED status.
When the fire output is disabled the LEDs ‘Fire Output Fault/ Disable’
and ‘Disable’ light on permanently.
(4)
- Press to set the time delay operation. Every pressing of the
button changes the ‘Delay’ setting:
•
ON
- The delay of fire output will be active when DAY operation mode is set - see the description for menu
6.3 DAY/ NIGHT operation modes.
•
OFF
- No delay of fire output activation. The fire output is activated immediately.
•
SCHEDULE
- The delay of fire output will be active on schedule - see the description for menu 6.3 DAY/
NIGHT operation modes.
All set parameters are confirmed wit ENTER button.
7.5.4 Fault Output
In this submenu the installer can disable/ enable the fault output activation.
To access the FAULT submenu, enter in the
installer’s menu - 5. PANEL OUTPUTS – MORE> (4) – FAULT (1).
The functional button has the following action:
(2)
- Press to change the status of the fault output. Every pressing of
the button changes alternatively the ENABLED - DISABLED status.
When the fault output is disabled the LED ‘Disable’ light on
permanently.
All set parameters are confirmed wit ENTER button.
7.5.5 Relay Outputs
Attention: The relay outputs are available for setting parameters only from access level 3!
In this submenu the installer can the set parameters of the relay outputs on the control panel PCB.
To access the RELAY OUTS submenu, enter in the
installer’s menu - 5. PANEL OUTPUTS - MORE>> - RELAY OUTS
(2).
Attention! The order of the relay numbers follows that on the control panel PCB!
The programming of the relay outputs is analogical.
Use the functional buttons to set parameters for:
1 - Press to set parameters for RELAY 4
2 - Press to set parameters for RELAY 3
3 - Press to set parameters for RELAY 2
4 - Press to set parameters for RELAY 1
For the settings of the relay outputs refer to the description of the menus for MAGPRO-0i4O.
All set parameters are confirmed wit ENTER button.
The exit to the main screen of PANEL OUTPUTS is with pressing the CANCEL button.