This manual is intended as a quick reference installation guide.  Please refer to the 

control panel manufacturers installation manual for detailed system information.
The EM200 series of modules are a family of microprocessor controlled interface 

devices permitting the monitoring and/or control of auxiliary devices.The EM210E-

CZR is used to link a zone of conventional devices to an intelligent system controlled 

by an addressable panel. The CZR has a resistor built in, making it especially suitable 

for connection to a conventional zone that operates in a hazardous area requiring 

intrinsically safe equipment.
The module must only be connected to control panels using compatible proprietary 

addressable communication protocols for monitoring and control. The module is 

compatible with System Sensor intrinsically safe sensors mounted in the B401 base, 

for use with these barriers: 
MTL models 4561 and 5561.
P Fuchs models KFDO-CS-Ex1.51P and KFDO-CS-Ex2.51P.

NOTE:

 When an intrinsically safe system is used on the loop, a short on the sensor 

side of the barrier will result in an alarm. Only a short on the module side of the safety 

barrier will generate a fault signal.
A single tri-colour LED indicates the status of the module. In normal conditions, the 

LED can be set by command from the control panel to blink green when the module 

is polled. In the case of a fire alarm on the conventional zone, the LED is switched 

on constant red by panel command. If a fault is detected on the conventional zone or 

the zone supply voltage drops below 12V, or a fault with the external power supply is 

signalled, the LED will blink yellow if enabled on the control panel. When a short circuit 

is detected on the loop to either side of the module, the LED is switched to show a 

constant yellow light. 

SPECIFICATIONS

Intelligent Loop

 

Operating Voltage Range with Isolator: 15 to 28VDC (Min 17.5VDC for LED operation)

Op. Volt. Range (Isolator Disabled): 15 to 30VDC (Min 17.5VDC for LED operation)

 

18 to 32VDC if conventional zone is loop powered

Max. Standby Current (µA @24 V and 25

o

C) External Supply Conventional Zone:  

No Communication: 

288

Communication LED blink enabled - 5 secs: 

500

Read 16 sec. LED blink 8 sec: 

388

Max. Standby Current (mA @24 V and 25

o

C) Conventional Zone connected to 

resistive EOL only (no detectors), Loop Powered Conventional Zone: 

 

No Communication: 

6.5

Communication LED blink enabled - 5 secs: 

6.7

Read 16 sec. LED blink 8 sec: 

6.6

LED Current (Red): 

2.2mA

LED Current (Yellow): 

8.8mA

Maximum rated continuous current with the 

isolator 

closed (I

c

 max):  1A

Maximum rated isolator switching current (under short circuit) (I

max):  1A

Maximum leakage current (I

max) with the isolator open (isolated state):  15mA

Maximum series impedance with the isolator closed (Z

c

 max): 170 m ohm at 15Vdc

Conventional Zone

External Supply Voltage:  

12 to 28.5 VDC

 

18 to 28.5 VDC if conventional zone is loop powered

Maximum Standby Load Current:   2.8 mA for detectors at 18 VDC

 

3.8 mA for detectors at 24 VDC

Maximum Zone Load:  

60mA (Limited internally)

Maximum Conventional Line Resistance: 50 Ohms

End of Line Resistor:  

3.9 K Ohms, 5% (Supplied)

General 

Humidity: 

5% to 95% relative humidity (non-condensing)

Ingress protection: 

IP50 (Mounted in M200E-SMB)

Maximum Wire Gauge: 

2.5mm²

INSTALLATION

EM200 series modules can be mounted in several ways (See 

Figure 1

):

1:1

  An  M200E-SMB  custom  low  profile  surface-mounting  box. The  SMB  Base  is 

affixed to mounting surface, and then the module and cover are screwed onto 

the base using the two screws supplied. Box dimensions: 132mm(H) x 137mm(W) 

x 40mm(D)

1:2

  An M200E-DIN Adaptor allows mounting onto standard 35mm x 7.5mm "Top Hat" 

DIN rail inside a control panel or other suitable enclosure. Push module into adaptor 

bracket until it clips into place. Locate top clip over DIN rail and rotate bottom down 

to clip into place. To remove, lift up, then rotate top away from the rail.

1:3

  An M200E-PMB Panel Mount Bracket allows the module to be mounted directly 

into a panel or other suitable enclosure. Adaptor bracket is mounted directly into 

panel using 2 x M4 Pan head screws. Module is pushed into adaptor until it clips 

into place.

Wiring to all series EM200 modules is via plug in type terminals capable of supporting 

conductors up to 2.5mm²

CAUTION

Disconnect loop power before installing modules or sensors. 

The module address is selected by means of rotary decade address switches (see 

Figure 3

).  A screwdriver should be used to rotate the wheels to select the desired 

address, either from the front or the top of the module. 

Fig./Abb.  1

1:1 M200E-SMB

1:2 M200E-DIN

1:3 M200E-PMB

EM210E-CZR

INSTALLATION INSTRUCTIONS - EM210E-CZR 

CONVENTIONAL ZONE INTERFACE MODULE

EN

Fig./Abb. 3

a

b

c

d

e

f

g

EM210E-CZR

A

B

C

X

1

0

X

1

6

6

23 mm

Fig./Abb. 2

A

B

C

x10

x1

A  B

1

0

0

1

2

3

4

5

6 7

8 9 10

11

12
13

14

15

0

1

2

3

4

5

6 7

8 9

1

2

3

4

5

6

7

8

9

10

11

12

94 mm
83 mm

93

mm

h

i

j

k